TOSHIBA Carrier Vertical Air Handling Unit Engineering Databook R454B

Model Name: MMD-UB___1VHN-UL

Revision: July, 2025 Revision 01

Manufacturer: Carrier Corporation

Contents

1. Specifications

Model Name Power supply Running current (A) Power consumption (W) Indoor external static pressure (in.WG) Throttle type Cooling capacity (Btu/h) Cooling capacity (kW) Heating capacity (Btu/h) Heating capacity (kW) MCA (A) MOP (A) Air Filter
MMD-UB0091VHN-UL 208~230V/1Ph/60Hz 0.55 65 0.4 Electronic expansion valve 9000 2.6 10000 2.9 4 6 Self-prepared
MMD-UB0121VHN-UL 208~230V/1Ph/60Hz 0.62 73 0.4 Electronic expansion valve 12000 3.5 13500 4 4 6 Self-prepared
MMD-UB0181VHN-UL 208~230V/1Ph/60Hz 0.91 112 0.4 Electronic expansion valve 18,000 5.3 20000 5.9 4 6 Self-prepared
MMD-UB0241VHN-UL 208~230V/1Ph/60Hz 1.16 145 0.4 Electronic expansion valve 24,000 7.0 27000 7.9 4 6 Self-prepared
MMD-UB0301VHN-UL 208~230V/1Ph/60Hz 1.86 241 0.6 Electronic expansion valve 30,000 8.8 34000 10.0 5 6 Self-prepared
MMD-UB0361VHN-UL 208~230V/1Ph/60Hz 1.86 241 0.6 Electronic expansion valve 36,000 10.5 40000 11.7 5 6 Self-prepared
MMD-UB0421VHN-UL 208~230V/1Ph/60Hz 3.17 434 0.6 Electronic expansion valve 42,000 12.3 45000 13.2 7 10 Self-prepared
MMD-UB0481VHN-UL 208~230V/1Ph/60Hz 3.14 430 0.6 Electronic expansion valve 48,000 14.1 54000 15.8 7 10 Self-prepared
MMD-UB0601VHN-UL 208~230V/1Ph/60Hz 4.06 569 0.6 Electronic expansion valve 60,000 17.6 67000 19.6 7 10 Self-prepared

Indoor Air Flow

MMD-UB0091VHN-UL MMD-UB0121VHN-UL MMD-UB0181VHN-UL MMD-UB0241VHN-UL MMD-UB0301VHN-UL MMD-UB0361VHN-UL MMD-UB0421VHN-UL MMD-UB0481VHN-UL MMD-UB0601VHN-UL
CFM 278/327/347 340/395/424 468/568/668 462/667/752 632/760/923 1045/1225/1383 1185/1395/1574 1324/1505/1798 2015/2371/2676
m³/h 473/555/590 578/672/721 796/966/1135 785/1134/1279 1074/1292/1569 1776/2083/2351 2015/2371/2676 2251/2559/3056 3422/4025/4556

Indoor Noise Level

MMD-UB0091VHN-UL MMD-UB0121VHN-UL MMD-UB0181VHN-UL MMD-UB0241VHN-UL MMD-UB0301VHN-UL MMD-UB0361VHN-UL MMD-UB0421VHN-UL MMD-UB0481VHN-UL MMD-UB0601VHN-UL
dB(A) 42/43/44 43/44/45 42/45/46 41/45/46 46/49/51 49/52/54 53/55/58 55/58/61 58/61/64

Indoor Dimensions (Unit: WxHxD)

MMD-UB0091VHN-UL MMD-UB0121VHN-UL MMD-UB0181VHN-UL MMD-UB0241VHN-UL MMD-UB0301VHN-UL MMD-UB0361VHN-UL MMD-UB0421VHN-UL MMD-UB0481VHN-UL MMD-UB0601VHN-UL
Unit (in) 19-5/8×45-3/4×22 19-5/8×45-3/4×22 19-5/8×45-3/4×22 19-5/8×45-3/4×22 19-5/8×45-3/4×22 19-5/8×45-3/4×22 19-5/8×45-3/4×22 19-5/8×45-3/4×22 19-5/8×45-3/4×22
Packing (in) 500×1162×560 500×1162×560 500×1162×560 500×1162×560 500×1162×560 500×1162×560 500×1162×560 500×1162×560 500×1162×560
Net / Gross weight (kg) 54/67 54/67 55.5/68.5 59/72 60/73 61/74 74.5/90 78.5/94 80/95
Net / Gross weight (lbs) 119/148 119/148 122.5/151 130/159 132.5/161 134.5/163 164/198.5 173/207 176/209

Connecting Pipe Dimensions

MMD-UB0091VHN-UL MMD-UB0121VHN-UL MMD-UB0181VHN-UL MMD-UB0241VHN-UL MMD-UB0301VHN-UL MMD-UB0361VHN-UL MMD-UB0421VHN-UL MMD-UB0481VHN-UL MMD-UB0601VHN-UL
Liquid side (mm) 9.52 9.52 9.52 9.52 9.52 9.52 9.52 9.52 9.52
Gas side (mm) 19.05 19.05 19.05 19.05 19.05 19.05 22.00 22.00 22.00
Drain port (Nominal dia.) (mm) 19.05 19.05 19.05 19.05 19.05 19.05 19.05 19.05 19.05

Compatible Refrigerant

R454B R454B R454B R454B R454B R454B R454B R454B
MMD-UB0091VHN-UL MMD-UB0121VHN-UL MMD-UB0181VHN-UL MMD-UB0241VHN-UL MMD-UB0301VHN-UL MMD-UB0361VHN-UL MMD-UB0421VHN-UL MMD-UB0481VHN-UL MMD-UB0601VHN-UL
R454B

Operating Pressure

MMD-UB0091VHN-UL MMD-UB0121VHN-UL MMD-UB0181VHN-UL MMD-UB0241VHN-UL MMD-UB0301VHN-UL MMD-UB0361VHN-UL MMD-UB0421VHN-UL MMD-UB0481VHN-UL MMD-UB0601VHN-UL
MPa 3.79 3.79 3.79 3.79 3.79 3.79 3.79 3.79 3.79

Electric Heater

Heat kit model AHU model electric heat(kW) Current (A) 208/230VAC MCA (A) 208/230VAC MAX.Fuse or Breaker (HACR) Ampacity 208 VAC / 230 VAC Fan speed 2 3 4 5
21-4444-06 9K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 9K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-06 12K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 12K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-06 18K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-02 18K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 24K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 24K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 24K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 30K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 30K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 30K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 36K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 36K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 36K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 42K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 42K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 42K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-03 42K 7.5/9.2 36.1/40 46/50 50 / 60
21-4444-06 48K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 48K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 48K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-03 48K 7.5/9.2 36.1/40 46/50 50 / 60
21-4444-06 60K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 60K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 60K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-03 60K 7.5/9.2 36.1/40 46/50 50 / 60

2. Dimensions

The following diagrams illustrate the dimensions of the Vertical Air Handling Unit.

Unit Dimensions (Height "H", Width "W", Depth "D"):

Model Height "H" (inches [mm]) Width "W" (inches [mm]) Dimension "D" (inches [mm]) Air outlet "A" (inches [mm]) Liquid Line / Suction Line (inches [mm])
9K/12K/18K/24K/30K/36K/42K 45-3/4 [1162] 19-5/8 [500] 22 [560] 17-7/8 [454] 3/8 / 3/4 [9.5]/[19]
48K/60K 53-1/8 [1350] 22 [560] 24-1/2 [623] 19-1/2 [496] 3/8 / 7/8 [9.5]/[22]

Filter Dimensions:

Model Filter size inches [mm] Width "W" Inch [mm] Depth "D" Inch [mm] Height "H" Inch [mm] "A" inch [mm] Length "B" inch [mm]
9K/12K/18K/24K/30K/36K/42K 18.1×21.4 [460×544] 18.3 [466] 21.6 [548] 1 [25.4] 20.8 [528] 16.3 [414]
48K/60K 20.5×23.8 [521×605] 20.7 [526] 23.9 [608] 1 [25.4] 23 [584] 18.8 [478]

*Note: 1. The filter is included in the device and must be provided on site; 2. When installing the indoor unit, regardless of the installation method, make sure that the filter is installed as shown.

3. Center of gravity

Vertical orientation:

Model Height (A) Width (B) Depth (C) Center of gravity (D) Center of gravity (E) Center of gravity (F)
9K/12K/18K/24K/30K/36K/42K 1162 500 560 200 280 690
48K/60K 1350 560 623 230 312 800

4. Piping diagram

9-12K (two rows):

Diagram showing the piping connections for the 9-12K models. It includes liquid side, gas side, strainers, pulse motor valve, sensors (TC1, TC2, TCJ, TA), and fan motor. Airflow is indicated by an upward arrow.

18K (three rows):

Diagram showing the piping connections for the 18K models. It includes liquid side, gas side, strainers, pulse motor valve, sensors (TC1, TC2, TCJ, TA), and fan motor. Airflow is indicated by an upward arrow.

24-42K (four rows):

Diagram showing the piping connections for the 24-42K models. It includes liquid side, gas side, strainers, pulse motor valve, sensors (TC1, TC2, TCJ, TA), and fan motor. Airflow is indicated by an upward arrow.

48K (four rows):

Diagram showing the piping connections for the 48K models. It includes liquid side, gas side, strainers, pulse motor valve, sensors (TC1, TC2, TCJ, TA), and fan motor. Airflow is indicated by an upward arrow.

60K (five rows):

Diagram showing the piping connections for the 60K models. It includes liquid side, gas side, strainers, pulse motor valve, sensors (TC1, TC2, TCJ, TA), and fan motor. Airflow is indicated by an upward arrow.

Explanation of functional parts in Indoor unit

Functional part name Function outline
Pulse Motor Valve (PMV) 1) Controls superheat in cooling operation
2) Controls subcooling in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
Temperature sensor (TA) 1) Detects indoor suction temperature
Temperature sensor (TC1) 1) Controls PMV super heat in cooling operation
Temperature sensor (TC2) 1) Controls PMV sub cool in heating operation
Temperature sensor (TCJ) 1) Controls PMV super heat in cooling operation

5. Wiring diagram

The document includes detailed wiring diagrams for the various models and configurations, including power supply, communication wiring, and electrical heater connections.

Power supply wiring diagram: Shows the terminal power out for the indoor unit.

Communication wiring diagram: Illustrates the connection between the indoor unit, outdoor unit, and wired controller. It specifies wire gauge recommendations based on length.

Electrical heater (3.75kW, 5kW): Wiring diagram for electrical heaters of 3.75kW and 5kW capacity.

Electrical heater (7.5kW): Wiring diagram for electrical heaters of 7.5kW capacity.

Electrical heater (10kW): Wiring diagram for electrical heaters of 10kW capacity.

Note: The wiring of refrigerant R454B needs to be connected to port CN220, but R410A does not need to be connected.

6. Electrical data

Electrical Data (Without electric heater):

Model Voltage (V) Hertz (Hz) HP Fan speed MOC (A) MCA (A) MOP (A)
9K 208/230 60 0.33 4 2.6 4 6
12K 208/230 60 0.33 4 2.6 4 6
18K 208/230 60 0.33 4 2.6 4 6
24K 208/230 60 0.33 4 2.6 4 6
30K 208/230 60 0.5 4 3.8 5 6
36K 208/230 60 0.5 4 3.8 5 6
42K 208/230 60 0.75 4 5.4 7 10
48K 208/230 60 0.75 4 5.4 7 10
60K 208/230 60 0.75 4 5.4 7 10

Note: MOC: Maximum operation current; MCA: Minimum Circuit Amps; MOP: Maximum Overcurrent Protection

Electrical Data (with electric heater):

Heat kit model AHU model electric heat(kW) Current (A) 208/230VAC MCA (A) 208/230VAC MAX.Fuse or Breaker (HACR) Ampacity 208 VAC / 230 VAC Fan speed 2 3 4 5
21-4444-06 9K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 9K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-06 12K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 12K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-06 18K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-02 18K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 24K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 24K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 24K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 30K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 30K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 30K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 36K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 36K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 36K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-06 42K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 42K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 42K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-03 42K 7.5/9.2 36.1/40 46/50 50 / 60
21-4444-06 48K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 48K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 48K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-03 48K 7.5/9.2 36.1/40 46/50 50 / 60
21-4444-06 60K 2.8/3.4 13.46/14.8 17/19 20 / 30
21-4444-01 60K 3.8/4.6 18.27/20 23/25 30 / 40
21-4444-02 60K 5.6/6.9 26.92/30 34/38 40 / 50
21-4444-03 60K 7.5/9.2 36.1/40 46/50 50 / 60

7. Sensible Capacity Tables

The following tables provide sensible capacity data for various models under different indoor and outdoor air temperature conditions.

TC: Total capacity [Btu/h], SHC: Sensible capacity [Btu/h]

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
009 7660 6200 8020 6370 8520 6630 9000 6840 9160 6860 9740 6780 10130 6510
012 7260 5880 7600 6040 8080 6280 8540 6490 8690 6510 9240 6420 9610 6180
018 10,21 8,270 10,69 8,500 11,36 8,840 12,00 9,120 12,21 9,150 12,98 9,030 13,51 8,690
024 10,21 8,270 10,69 8,500 11,36 8,840 12,00 9,120 12,21 9,150 12,98 9,030 13,51 8,690
030 10,21 8,270 10,69 8,500 11,36 8,840 12,00 9,120 12,21 9,150 12,98 9,030 13,51 8,690
036 10,21 8,270 10,69 8,500 11,36 8,840 12,00 9,120 12,21 9,150 12,98 9,030 13,51 8,690
042 10,21 8,270 10,69 8,500 11,36 8,840 12,00 9,120 12,21 9,150 12,98 9,030 13,51 8,690
048 10,21 8,270 10,69 8,500 11,36 8,840 12,00 9,120 12,21 9,150 12,98 9,030 13,51 8,690
060 9,910 8,030 10,38 8,250 11,03 8,580 11,65 8,860 11,86 8,880 12,31 8,770 12,81 8,440

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
018 15,32 12,40 16,03 12,74 17,04 13,26 18,00 13,68 18,31 13,72 19,47 13,55 20,27 13,04
024 15,32 12,40 16,03 12,74 17,04 13,26 18,00 13,68 18,31 13,72 19,47 13,55 20,27 13,04
030 14,88 12,04 15,57 12,37 16,55 12,88 17,48 13,28 17,78 13,32 18,91 13,16 19,68 13,04
036 14,52 11,76 15,20 12,08 16,15 12,57 17,06 12,97 17,36 13,01 18,46 12,85 19,22 12,36
042 20,43 16,10 21,37 16,54 22,73 17,22 24,00 17,76 24,41 17,81 25,96 17,59 27,02 16,92
048 20,43 16,10 21,37 16,54 22,73 17,22 24,00 17,76 24,41 17,81 25,96 17,59 27,02 16,92
060 19,84 15,63 20,75 16,06 22,07 16,72 23,30 17,24 23,70 17,29 25,21 17,08 26,24 16,43

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
036 25,53 20,67 26,72 21,24 28,41 22,11 30,00 22,80 30,51 22,86 32,45 22,58 33,78 21,73
042 25,53 20,67 26,72 21,24 28,41 22,11 30,00 22,80 30,51 22,86 32,45 22,58 33,78 21,73
048 25,53 20,67 26,72 21,24 28,41 22,11 30,00 22,80 30,51 22,86 32,45 22,58 33,78 21,73
060 24,79 20,07 25,95 20,62 27,59 21,47 29,13 22,14 29,63 22,20 31,51 21,93 32,80 21,10

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
036 30,64 24,15 32,06 24,82 34,09 25,83 36,00 26,64 36,62 26,72 38,93 26,37 40,54 25,39
042 30,64 24,15 32,06 24,82 34,09 25,83 36,00 26,64 36,62 26,72 38,93 26,37 40,54 25,39
048 30,64 24,15 32,06 24,82 34,09 25,83 36,00 26,64 36,62 26,72 38,93 26,37 40,54 25,39
060 29,75 23,45 31,13 24,10 33,10 25,08 34,96 25,87 35,56 25,95 37,80 25,61 39,36 24,65

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
048 35,75 28,94 37,40 29,73 39,77 30,95 42,00 31,92 42,72 32,01 45,42 31,60 47,29 30,42
060 35,75 28,94 37,40 29,73 39,77 30,95 42,00 31,92 42,72 32,01 45,42 31,60 47,29 30,42

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
048 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85
060 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
048 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85
060 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
048 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85
060 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85

Unit size Indoor air temp.
59 °F WB
71 °F DB
61 °F WB
73 °F DB
64 °F WB
77 °F DB
67 °F WB
80 °F DB
68 °F WB
82 °F DB
72 °F WB
86 °F DB
75 °F WB
90 °F DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
048 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85
060 40,85 32,20 42,74 33,08 45,45 34,44 48,00 35,52 48,82 35,62 51,91 35,16 54,05 33,85

8. Fan characteristics

The document includes fan characteristic curves for various models, showing the relationship between airflow (SCFM) and external static pressure (in. W.G.) for both standard and maximum static pressure conditions. These curves are provided for different fan taps (L, M, H).

Note: The factory wiring corresponds to the standard static pressure. To adjust the indoor unit to the maximum static pressure, the motor wiring needs to be changed. Refer to the IOM for specific operations.

9. Sound data

The document provides sound data, including sound pressure levels and Noise Criteria (NC) curves, for various models. The measurements are taken with a microphone placed at a specified distance from the indoor unit, with different fan taps and external static pressures.

10. Accessories

The following table lists the accessories included with the unit, their quantity, a description of their application, and an image:

Name of accessories Quantity Image Application
Installation & Operation Manual 2 A manual One in English and one in French
Tapping screw 1 [Screw image] Remove the paint on the machine to ensure that the whole machine is reliably grounded.
Ribbon 4 [Ribbon image] Used to bind up the cables and connecting pipes.
Wire grommet 1 [Wire grommet image] Protect communication wires passing through the machine's knockout holes
Wire grommet 1 [Wire grommet image] Protect the power wires through the machine's knockout hole
Seal ring 3 [Seal ring image] Put on the plug or the water outlet to play a sealing role
Sponge 1 [Sponge image] After welding the indoor and outdoor unit connecting pipes, stick them on the pipe cover to insulate the copper pipes
Blank bag 1 [Blank bag image] Used to contain accessories.
Plug 2 [Plug image] Block the drain opening on the unit
Drain joint 1 [Drain joint image] Connect the drain hose for machine drainage
Temperature sensor fixing card 1 [Temperature sensor fixing card image] Fixed room temperature sensor
Sponge 1 [Sponge image] Seal the circuit breaker in the electric heating assembly through the machine knockout (Paste to the outside, used in conjunction with the fixing buckle and the rubber cover on the front panel of the machine)
Sponge 1 [Sponge image] Seal the circuit breaker in the electric heating assembly through the machine knockout (Paste on the inside)
Fixed buckle 1 [Fixed buckle image] Seal the circuit breaker in the electric heating assembly through the machine knockout (Paste to the outside)

Heater Kit Accessories (Optional)

Model Description 9K 12K 18K 24K 30K 36K 42K 48K 60K
21-4444-06 3.75kW heating kit, single-pole circuit breaker
21-4444-01 5kW heating kit, single-pole circuit breaker
21-4444-02 7.5kW heating kit, single-pole circuit breaker × ×
21-4444-03 10kW heating kit, single-pole circuit breaker × × × × × × × × ×

Note: • indicates availability, and × indicates unavailability.

11. PC Board Optional Switch/Connector Specifications (ACD-0006)

This section details the specifications for PC board optional switches and connectors.

Function Connector Pin Function Remarks
Power supply CN01 1 AC230V This is the input of the power supply.
Power supply CN04 1 AC230V This is the input of the power supply.
Fan power supply CN02 1 AC230V This is the input of the fan power supply.
Fan power supply CN03 1 AC230V This is the input of the fan power supply.
Transformer power input CN10 1
3
AC230V
AC230V
This is the input of the transformer power supply.
Transformer output CN11 1
2
AC24V
AC24V
This is the output of the transformer.
Optional fan output CN20 1 Optional fan output When the electric heating is running and fan P01 error occurs, it will be turned on.
Optional fan output CN21 1 AC230V -
Fan output CN32 1
2
DC12V(COM)
Fan output
Factory default setting: ON when indoor unit in operation and OFF when indoor unit at rest.
*Fan can be operated on its own by pressing FAN button on remote control(DN31)
Main bus communication CN40 1
2
Main BUS
Main BUS
This is used for communication between indoor unit and outdoor unit.
Sub bus communication CN41 1
2
Sub BUS
Sub BUS
This is used for communication between indoor unit and remote controller.
Optional output CN60 1
2
3
4
5
6
DC12V(COM)
Defrost output
Thermo output
Cooling output
Heating output
Fan output
ON during defrost.
ON while thermo ON.
ON during cooling.
ON during heating.
ON while fan ON.
HA CN61 1
2
3
4
5
6
ON/OFF input
OV(COM) for pin1,3
Remote control disabling input
In-operation output
DC12V for pin4,6
Alarm output
Can be selected by I.DN[2E]
J01:Connect - Pulse(factory default setting)/ Cut - Static input select
Enables/disables start/stop control via remote control.
ON during operation.
ON while alarm ON.
CHK operation check CN71 1
2
Check mode input
0V
Used for indoor operation check (prescribed operational status output, such as indoor fan "H", to be generated without communication with outdoor unit or remote controller).
DIS display mode CN72 1
2
Display mode input
0V
Product display mode - Communication just between indoor unit and remote control becomes available (upon turning on of power).
Timer short-circuited out (always).
FS unit CN81 1 DC12V(COM) This is connected to the FS unit.
Can be selected by I.DN[FD](Priority of operating mode) and I.DN[FE](System address).
EP valve 2
3
4
EP valve
Balance valve
Intake valve
I.DN[FD]=0 Priority heating(Factory default setting)
I.DN[FD]=1 Priority cooling
I.DN[FD]=2 heating only
I.DN[FD]=3 cooling only
I.DN[FE]=99 not connected
I.DN[FE]System address setting range: 1~64.
Discharge valve 5 Discharge valve -
PMV output CN82 1
2
3
4
5
6
PMV output A
PMV output B
PMV output /A
PMV output /B
DC12V(COM)
DC12V(COM)
This is connected to the PMV coil for controlling PMV opening.
TC1 input CN100 1
2
TC1 temperature sensor input
0V
This is for connecting the TC1 (heat exchanger outlet) temperature sensor.
TC2 input CN101 1
2
TC2 temperature sensor input
0V
This is for connecting the TC2 (middle of the heat exchanger) temperature sensor.
TCJ input CN102 1
2
TCJ temperature sensor input
0V
This is for connecting the TCJ (heat exchanger inlet) temperature sensor.
TA input CN104 1
2
TA temperature sensor input
0V
This is for connecting the TA (ambient) temperature sensor.
Electric heater output or Secondary heating output CN200 1
2
3
4
5
AC24V(COM)
Heater 1 output
Heater 2 output
Heater 3 output
Heater 3 output
Can be selected by I.DN :=
1)Electrical heater output (I.DN[301]=0)-Factory default setting
2)Secondary heating output* (I.DN[301]=1)
*Normal mode or Flip of secondary can be selected by I.DN[C5]
Fan output CN210 1
2
3
4
5
6
FAN tap "HH" output
FAN tap "H" output
FAN tap "L" output
FAN tap "L" output
AC24V(COM)
OV
Fan speed(High).
Fan speed(Med).
Fan speed(Low).
Fan speed(Low).
Refrigerant leak sensor input 2
3
4
Life status input
Alarm status input
5V
The Pulse Width Modulation (PWM) period is 375 ms. The PWM duty cycles are: 0%, 20%, 60%, 80%, 100%
0% Initial operation Up to 2 seconds, until first measurement is ready.
20% Normal operation Measurements are still reliable, but the sensor should be replaced at the next scheduled maintenance.
60% ASC warning
80% ASC limit measurements may no longer be reliable, and the sensor needs to be replaced (PWM 80%).
100% Power supply OFF
The Pulse Width Modulation (PWM) period is 375 ms. The PWM duty cycles are: 0%, 20%, 60%, 80%, 100%
0% Initial operation Up to 2 seconds, until first measurement is ready.
20% Normal operation - monitoring
60% Alarm Concentration of refrigerant above 10'000 ppm. The Alarm signal is on while a concentration above 10'000 ppm is detected and stays on for 30seconds after the concentration has returned below 10'000 ppm.
80% Sensor fault Sensor reading may not be accurate. This can be due to a permanent error, due to a temporary condition (e.g., ambient conditions outside operating range), or due to a temporary internal error.
100% Power supply OFF

PDF preview unavailable. Download the PDF instead.

MA VAHU EngDataBook R454B 20250708 Microsoft Word 适用于 Microsoft 365

Related Documents

Preview Toshiba Carrier Vertical Air Handling Unit Engineering Databook R410A
This engineering databook provides comprehensive technical specifications, dimensions, electrical data, piping and wiring diagrams, fan characteristics, and sound data for the Toshiba Carrier Vertical Air Handling Unit type, R410A models.
Preview TOSHIBA Carrier MMD-UP0121VHG-UL VRF Indoor Unit Submittal Data
Technical submittal data for the TOSHIBA Carrier MMD-UP0121VHG-UL VRF Indoor Unit, a vertical air handler, detailing performance, electrical, physical specifications, and dimensional information.
Preview Toshiba Carrier u-Series Heat Recovery VRF Product Bulletin and Specifications
Product bulletin detailing the new Toshiba Carrier u-Series Heat Recovery VRF units, including standard and Elite Heat models, technical specifications, dimensional comparisons, electrical ratings, sound data, and AHRI performance ratings.
Preview Toshiba Carrier Air Conditioner (Multi Type) Outdoor Unit Installation Manual
This installation manual provides comprehensive guidance for Toshiba Carrier's multi-type air conditioning outdoor units, covering safety precautions, installation procedures, refrigerant piping, electrical wiring, and troubleshooting for various models.
Preview Toshiba Carrier Air Conditioner Owner's Manual: RAV-SM Series
Comprehensive owner's manual for Toshiba Carrier 4-way Cassette type split air conditioners, models RAV-SM182UTP-UL and others. Covers safety precautions, part names, remote controller operation, wind direction adjustment, and maintenance.
Preview TOSHIBA Carrier VRF DX-Coil Interface Advance Service Manual | TCB-IFDMR01UP-UL, RBM-A Series
Comprehensive service manual for the TOSHIBA Carrier VRF DX-Coil Interface Advance, detailing installation, operation, troubleshooting, and parts for the TCB-IFDMR01UP-UL Dx-coil controller and RBM-A series Dx-valve kits.
Preview Toshiba Carrier VRF Outdoor Unit MMY-MUP1201FT9P-UL Heat Recovery Submittal Data
Submittal data for the Toshiba Carrier VRF Outdoor Unit MMY-MUP1201FT9P-UL, a heat recovery system. Includes performance specifications, electrical data, compressor and fan details, physical dimensions, and heat recovery features.
Preview Toshiba Carrier BN Interface Software License Information
Details on the software license information for the Toshiba Carrier BN interface BMS-IFBN1281U-UL, including open-source components and warranty disclaimers.