R. STAHL 8530/1-MCB-STA103N-B63-000-4 Circuit Breaker
Article Number: 293852
Product Overview
The R. STAHL 8530/1-MCB-STA103N-B63-000-4 circuit breaker is designed for system technology applications, offering robust current limitation and high breaking capacity (10, 15, or 25 kA). This results in reduced stress on electrical lines and improved selectivity with upstream fuses. The modular design allows for flexible configurations, available in 1 to 4-pole models with nominal currents from 0.5–63 A. The maximum mounting width is 4.5 division units.
Key features include:
- Separating function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or expansion of installations due to modular design
- Simple mounting via DIN rail snap-on in Ex e enclosures
- Fixed thermal and magnetic trip adjustment
- Ergonomic operating lever for safe connection and disconnection
- Padlockable (accessories) for protection against reconnection during maintenance
Technical Data
Explosion Protection
- Applications (zones): 1, 2
- Applications (zones) Note: Usable in zones 21/22 with protection by Ex tb/tc enclosure
- IECEX gas certification: IECEX FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- ATEX gas certification: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certifications: ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
- Certificate of conformity: Certificate of conformity (ATEX)
Electrical Data
- Rated operating voltage AC: 230/400 V
- Rated operating current: 63 A
- Frequency: 50/60 Hz
- Rated switching capacity: 10 kA
- Electrical endurance: 104
- Mechanical endurance: 2 x 104
- 1st Auxiliary function: None
- Rated voltage 1st auxiliary function AC: -
- Max. current 1st auxiliary function: -
- 2nd Auxiliary function: None
- Max. voltage 2nd aux. function DC: -
- Trip characteristic: B
- Number of poles: 3 pole + N
Environmental Conditions
- Ambient temperature: -40 °C ... 70 °C
- Ambient temperature (Fahrenheit): -40 °F ... 158 °F
- Ambient temperature Note: Divergent ambient temperatures based on valid certificates upon request
Mechanical Data
- Degree of protection (IP) (IEC 60529): IP2X
- Enclosure material: Thermoplastic
- Connection terminal cross-section min.: 1.5 mm²
- Connection terminal cross-section max.: 25 mm²
- Connection terminal AWG min.: 16 AWG
- Connection terminal AWG max.: 4 AWG
- Connection terminal 2 cross-section min.: 1.5 mm²
- Connection terminal 2 cross-section max.: 10 mm²
- Connection terminal 2 AWG min.: 16 AWG
- Connection terminal 2 AWG max.: 8 AWG
- Tightening torque min.: 2 N·m
- Tightening torque max.: 3 N·m
- Connection terminal Note: 2 conductor connections (upper and lower chamber simultaneously): max. upper and lower chamber 16 / 10 mm² (only a difference in cross-section between the upper and lower chamber can be fitted). Permitted connection cross-section combinations are listed in the user instructions.
- Width: 110 mm (4.33 in)
- Length: 165 mm (6.5 in)
- Mounting depth: 138.3 mm (5.44 in)
- Weight: 1.8 kg (3.969 lb)
- Mounting/Installation Tightening torque: 2-3 N·m (17.7 ... 26.6 lbf·in)
- Auxiliary contact tightening torque: 0.4–0.6 N·m (3.5 ... 5.3 lbf·in)
Technical Diagrams
Trip Time Curve: A graph illustrating the trip time characteristics for AC and DC, with 'B' as the trip characteristic. It shows time in seconds and minutes against current multiples.
Measurement Diagram: A diagram showing the dimensions of the circuit breaker in millimeters and inches. Key dimensions include width (110 mm / 4.33 in), length (165 mm / 6.50 in), and mounting depth (138.3 mm / 5.44 in). It also indicates the unit is 4 division units.
Accessories
- Cylinder lock: For locking (Ø 3 mm / 0.12 in shackle). Article Number: 107115
- Quadruple immobilization device: Locking/tagging pliers for individual component locking using up to 4 cylinder locks. Article Number: 227232
- Fixing kit: A fixing set for mounting the component on the mounting plate without a top-hat rail. Article Number: 276618