MEAN WELL MSP-200 Series 200W Single Output Medical Type
Owner’s Manual
Product Information
Specifications
- Product Name: 200W Single Output Medical Type
- Series: MSP-200
- Input Voltage: Universal AC input / Full range
- Power Factor (PF): >0.95
- Efficiency: Up to 89%
- Surge Input: Withstands 300VAC for 5 seconds
- Protections: Short circuit, Overload, Over voltage, Over temperature
- Cooling: Free air convection
- Constant Current Limiting Circuit: Built-in
- Profile: 1U low profile (38mm)
- Safety Approval: Medical safety approved (MOOP level)
- Remote ON-OFF Control: Built-in
- Standby Power: 5V at 0.3A
- Remote Sense Function: Built-in
- No Load Power Consumption: <0.95/230VAC, <0.99/115VAC at full load
Product Usage Instructions
1. Installation
To install the product, follow the steps below:
- Select a suitable location for the product.
- Ensure proper ventilation around the product.
- Connect the product to the power source using the provided universal AC input.
- If required, use the built-in remote ON-OFF control to turn the product on or off.
- Verify that the product is securely installed and connected.
2. Operating Temperature and Humidity
The product can operate within a temperature range of -40°C to +70°C. It is important to refer to the provided Derating Curve for temperature-dependent performance. The working humidity range is 20% to 90% RH non-condensing.
3. Safety
The product has been approved for medical safety standards and complies with ANSI/AAMI ES60601-1, IEC60601-1, EAC TP TC 004, BS EN/EN60601-1, and BS EN/EN62368-1. It is recommended to follow all safety guidelines provided in the user manual.
4. Protection Features
The product is equipped with several protection features:
- Short Circuit Protection: Automatically activates when a short circuit is detected and recovers automatically after the fault condition is removed.
- Overload Protection: Activates when the output power exceeds 105-135% of the rated output power.
- Over Voltage Protection: Shuts down the output voltage and recovers after re-powering.
- Over Temperature Protection: Activates when the product exceeds the specified temperature range.
FEATURES:
- Universal AC input / Full range
- Built-in active PFC function, PF>0.95
- High efficiency up to 89%
- Withstand 300VAC surge input for 5 seconds
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- 1U low profile 38mm
- Medical safety approved (MOOP level)
- Built-in remote ON-OFF control
- Standby 5V@0.3A
- Built-in remote sense function
- No load power consumption<0.5W (Note.6)
- 5 years warranty
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
SPECIFICATION
MODEL | MSP-200-3.3 | MSP-200-5 | MSP-200-7.5 | MSP-200-12 | MSP-200-15 | MSP-200-24 | MSP-200-36 | MSP-200-48 | |||||||||||||||||||||||||||||||||||||
OUTPUT | DC VOLTAGE | 3.3V | 5V | 7.5V | 12V | 15V | 24V | 36V | 48V | ||||||||||||||||||||||||||||||||||||
RATED CURRENT | 40A | 35A | 26.7A | 16.7A | 13.4A | 8.4A | 5.7A | 4.3A | |||||||||||||||||||||||||||||||||||||
CURRENT RANGE | 0 ~ 40A | 0 ~ 35A | 0 ~ 26.7A | 0 ~ 16.7A | 0 ~ 13.4A | 0 ~ 8.4A | 0 ~ 5.7A | 0 ~ 4.3A | |||||||||||||||||||||||||||||||||||||
RATED POWER | 132W | 175W | 200.3W | 200.4W | 201W | 201.6W | 205.2W | 206.4W | |||||||||||||||||||||||||||||||||||||
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 90mVp-p | 100mVp-p | 120mVp-p | 150mVp-p | 150mVp-p | 250mVp-p | 250mVp-p | |||||||||||||||||||||||||||||||||||||
VOLTAGE ADJ. RANGE | 2.8 ~ 3.8V | 4.3 ~ 5.8V | 6.8 ~ 9V | 10.2 ~ 13.8V | 13.5 ~ 18V | 21.6 ~ 28.8V | 28.8 ~ 39.6V | 40.8 ~ 55.2V | |||||||||||||||||||||||||||||||||||||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±2.0% | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||||||||||||||||||||||||||||||||||||
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.3% | ±0.3% | ±0.2% | ±0.2% | ±0.2% | |||||||||||||||||||||||||||||||||||||
LOAD REGULATION | ±1.5% | ±1.0% | ±1.0% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |||||||||||||||||||||||||||||||||||||
SETUP, RISE TIME | 1000ms, 50ms/230VAC 2500ms, 50ms/115VAC at full load | ||||||||||||||||||||||||||||||||||||||||||||
HOLD UP TIME (Typ.) | 16ms/230VAC 16ms/115VAC at full load | ||||||||||||||||||||||||||||||||||||||||||||
INPUT | VOLTAGE RANGE Note.5 | 85 ~ 264VAC 120 ~ 370VDC | |||||||||||||||||||||||||||||||||||||||||||
FREQUENCY RANGE | 47 ~ 63Hz | ||||||||||||||||||||||||||||||||||||||||||||
POWER FACTOR (Typ.) | PF>0.95/230VAC PF>0.99/115VAC at full load | ||||||||||||||||||||||||||||||||||||||||||||
EFFICIENCY (Typ.) | 80% | 84% | 86% | 88% | 88% | 88% | 89% | 89% | |||||||||||||||||||||||||||||||||||||
AC CURRENT (Typ.) | 2.2A/115VAC 1.1A/230VAC | ||||||||||||||||||||||||||||||||||||||||||||
INRUSH CURRENT (Typ.) | 35A/115VAC 70A/230VAC | ||||||||||||||||||||||||||||||||||||||||||||
LEAKAGE CURRENT Note.7 | Earth leakage current < 300μA/264VAC , Touch leakage current < 100μA/264VAC | ||||||||||||||||||||||||||||||||||||||||||||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | |||||||||||||||||||||||||||||||||||||||||||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | |||||||||||||||||||||||||||||||||||||||||||||
OVER VOLTAGE | 3.96 ~ 4.62V | 6 ~ 7V | 9.4 ~ 10.9V | 14.4 ~ 16.8V | 18.8 ~ 21.8V | 30 ~ 34.8V | 41.4 ~ 48.6V | 57.6 ~ 67.2V | |||||||||||||||||||||||||||||||||||||
Protection type : Shut down o/p voltage, re-power on to recover | |||||||||||||||||||||||||||||||||||||||||||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | ||||||||||||||||||||||||||||||||||||||||||||
FUNCTION | 5V STANDBY | 5VSB : 5V@0.3A ; tolerance±5%, ripple : 50mVp-p(max.) | |||||||||||||||||||||||||||||||||||||||||||
REMOTE CONTROL | RC+/RC- : 4 ~10V or open = power on ; 0 ~ 0.8V or short = power off | ||||||||||||||||||||||||||||||||||||||||||||
ENVIRONMENT | WORKING TEMP. | -40 ~ +70℃ (Refer to “Derating Curve”) | |||||||||||||||||||||||||||||||||||||||||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||||||||||||||||||||||||||||||||||||||||||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | ||||||||||||||||||||||||||||||||||||||||||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | ||||||||||||||||||||||||||||||||||||||||||||
VIBRATION | 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes | ||||||||||||||||||||||||||||||||||||||||||||
SAFETY & EMC (Note 4) |
SAFETY STANDARDS | ANSI/AAMI ES60601-1, IEC60601-1, EAC TP TC 004 approved, Design refer to BS EN/EN60601-1, BS EN/EN62368-1 | |||||||||||||||||||||||||||||||||||||||||||
ISOLATION LEVEL | Primary-Secondary: 2×MOOP, Primary-Earth: 1×MOOP | ||||||||||||||||||||||||||||||||||||||||||||
WITHSTAND VOLTAGE | I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | ||||||||||||||||||||||||||||||||||||||||||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃ / 70% RH | ||||||||||||||||||||||||||||||||||||||||||||
EMC EMISSION | Compliance to BS EN/EN55011 (CISPR11) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020 | ||||||||||||||||||||||||||||||||||||||||||||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN60601-1-2, EAC TP TC 020 | ||||||||||||||||||||||||||||||||||||||||||||
OTHERS | MTBF | 1609.5K hrs min. Telcordia SR-332 (Bellcore) ; 186.2K hrs min. MIL-HDBK-217F (25℃) | |||||||||||||||||||||||||||||||||||||||||||
DIMENSION | 199*98*38mm (L*W*H) | ||||||||||||||||||||||||||||||||||||||||||||
PACKING | 0.77Kg; 18pcs/14.9Kg/0.87CUFT | ||||||||||||||||||||||||||||||||||||||||||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com) 5. Derating may be needed under low input voltages. Please check the derating curve for more details. 6. No load power consumption<0.5W when RC+ & RC- (CN100 pin1,2) 0 ~ 8V or short. 7. Touch current was measured from primary input to DC output. 8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft). ※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
Mechanical Specification
Block Diagram
Derating Curve
Output Derating VS Input Voltage
Function Description of CN100
Pin No. | Function | Description |
1 | RC+ | Turns the output on and off by electrical or dry contact between pin 2 (RC-). Short: Power OFF, Open: Power ON. |
2 | RC- | Remote control ground |
3 | AUX | Auxiliary voltage output, 4.75~5.25V, reference to pin 4(AUXG). The maximum load current is 0.3A. This output has the built-in oring diodes and is not controlled by the “remote ON/OFF control”. |
4 | AUXG | Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V). |
5 | +S | Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V. |
6 | -S | Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V. |
Function Manual
1.Remote Control
The PSU can be turned ON/OFF by using the “Remote
ON/OFF” function
Between RC-(pin2) and RC+(pin1) | Output Status |
SW ON (Short) | OFF |
SW OFF (Open) | ON |
2. Remote Sense
The remote sensing compensates voltage drop on the load wiring up to 0.5V.
Downloaded from Arrow.com.
File Name:MSP-200-SPEC 2022-09-20
Frequently Asked Questions (FAQ)
Q: What are the dimensions of the product?
A: The dimensions of the product are 199mm (length) x 98mm (width) x 38mm (height).
Q: What is the weight of the product?
A: The weight of the product is 0.77kg.
Q: What is the packaging information?
A: The product is packed in a box with a weight of 14.9kg and a volume of 0.87 cubic feet. Each box contains 18 units.
Q: What is the MTBF (Mean Time Between Failures) of the product?
A: The MTBF of the product is 1609.5K hours minimum according to Telcordia SR-332 (Bellcore) and 186.2K hours minimum according to MIL-HDBK-217F (25).