SmartGen HSM340 Modul Sinkron
LUWIHVIEW
Modul Sinkron HSM340 dirancang khusus kanggo paralel otomatis genset sistem 400Hz. Miturut paramèter sing wis disetel, modul bisa kanthi otomatis ngrampungake deteksi kondisi paralel genset (prabédan volt, prabédan frekuensi lan fase) lan ngirim sinyal paralel nalika kondisi wis disiapake.
HSM340 Synchronous Module ditrapake kanggo kesempatan sing bisa nyinkronake generator menyang bis. Modul punika prasaja kanggo operate, gampang kanggo nginstal lan digunakake digunakake ing genset kapal lan genset tanah.
KINERJA LAN KARAKTERISTIK
Karakteristik utama kaya ing ngisor iki:
- Cocog kanggo 3-phase 4-wire, 3-phase 3-wire, 2-phase 3-wire, sistem daya 2-kawat fase tunggal kanthi frekuensi 400Hz;
- Potensiometer sing bisa diatur ngidini nyetel paramèter utama babagan sinkronisasi;
- Parameter operasi bisa disetel liwat piranti lunak tes PC. Port LINK kudu disambungake menyang komputer liwat modul SG72 (USB to LINK);
- 4 output relay, 2 digunakake kanggo output UP cepet lan output DOWN; 1 relay SYNC digunakake kanggo output cedhak sink, lan 1 relay STATUS digunakake kanggo output status sawise nutup;
- 1 INH "nyandhet sinkronisasi cedhak output" input digital; nalika aktif lan gens nyinkronake karo bis, indikator SYNC bakal madhangi lan nyelarasake relay cedhak dicegah kanggo output;
- Wide power supply sawetara DC (8 ~ 35) V;
- 35mm guide ril soyo tambah;
- Desain modular, terminal pluggable, struktur kompak karo instalasi gampang.
SPESIFIKASI
Tabel 3 - Parameter Produk
barang | Isine |
Kerja Voltage | DC8.0V kanggo 35.0V, sumber daya terus-terusan. |
Konsumsi Sakabèhé | ≤1W (Mode siyaga≤0.5W) |
AC Voltage Input | AC50V~ AC620V (ph-ph) |
Frekuensi AC | 400Hz |
SYNC Output | Output gratis 7A AC250V Volt |
Output UP | 5A AC250V/5A DC30V Volts output free |
TURUN Output | 5A AC250V/5A DC30V Volts output free |
STATUS Output | 5A AC250V/5A DC30V Volts output free |
Ukuran Kasus | 71.6mm x 89.7mm x 60.7mm |
Kondisi Kerja | Suhu: (-25~+70)°C Kelembapan Relatif: (20~95)% |
Kahanan Panyimpenan | Suhu: (-30~+80)°C |
Intensitas Isolasi | Aplikasi AC2.2kV voltage antarane dhuwur voltage terminal lan vol rendahtage terminal;
Arus bocor ora luwih saka 3mA sajrone 1 menit. |
Bobot | 0.20 kg |
INDIKATOR PANEL lan DESKRIPSI TERMINAL
Tabel 4 - LED Definition Description
Indikator | warna | Katrangan | Cathetan |
DC 24V | Ijo | Indikator daya, madhangi nalika daya dianggo kanthi apik. | |
UP | Ijo | Iku madhangi nalika mundhakaken kacepetan pulsa dikirim. | |
TURUN | Ijo | Iku madhangi nalika nyuda kacepetan pulsa dikirim. | |
GENSET | Ijo | Iku tansah madhangi nalika gens voltage lan frekuensi normal; iku
sumunar nalika gens voltage lan frekuensi ora normal; dipateni nalika ora ana daya. |
|
BUS | Ijo | Iku tansah murup nalika bis voltage lan frekuensi normal; kelip-kelip nalika bis voltage lan frekuensi ora normal; iku
dipateni nalika ora ana daya. |
|
ΔF Frekuensi
Bedane. |
Ijo | Iku madhangi nalika gens 'lan bus' frekuensi lan voltagwes biasa ae,
lan prabédan wektu nyata ana ing sawetara sing wis disetel. |
|
ΔU
Volt bedane. |
Ijo | Iku madhangi nalika gens 'lan bus' frekuensi lan voltagwes biasa ae,
lan wektu nyata voltage prabédan ana ing sawetara sing wis disetel. |
|
SYNC Tutup | abang | Nalika output relay cedhak, lamp bakal padhang. Tutup pulsa:
400 ms. |
|
STATUS | abang | Sawise output sinyal cedhak, output relay lan madhangi; nalika sinkronisasi antarane gen lan bis ora dideteksi, relay bakal
ora output lan lamp bakal mateni. |
Tabel 5 - Katrangan Potensiometer
Potentiometer | Range | Katrangan | Cathetan |
TN/ms Length of Control Pulse | (25-500)ms | Min. wektu kontrol pulsa langgeng. | |
Range Proporsi XP/Hz | (0-±2.5)Hz | Ing wilayah iki, jembaré pulsa ana ing proporsi langsung karo nilai panyimpangan frekuensi dirating. | proporsi XP/Hz
jangkoan |
FREQ/Hz | (0.1-0.5)Hz | prabédan frekuensi ditrima. | |
VOLTAGE/% | (2-12)% | Ditrima voltage prabédan | |
BREAKER / ms | (20-200)ms | Wektu saklar ditutup. |
Tabel 6 - Katrangan Sambungan Terminal
Ora. | Fungsi | Ukuran Kabel | Cathetan | ||||
1. | Input Daya DC - | 1.5mm2 | Disambungake karo negatif saka baterei wiwitan. | ||||
2. | Input Daya DC + | 1.5mm2 | Disambungake karo baterei wiwitan positif. | ||||
3. | INH | – | 1.0mm2 | "Tutup Output Nyandhet" Input | |||
4. | IN | 1.0mm2 | |||||
5. | TURUN Output | 1.0mm2 | Output nalika kacepetan suda. | Biasane mbukak; Output gratis volt; 5A Rated | |||
6. | |||||||
7. | Output UP | 1.0mm2 | Output nalika kacepetan mundhak. | Biasane mbukak; Output gratis volt; 5A Rated | |||
8. | |||||||
9. | GEN L1 Phase Input | 1.0mm2 | Gen AC voltage masukan. | ||||
10. | GEN L2 Phase Input | ||||||
11. | BUS L1 Phase Input | 1.0mm2 | Bus AC Voltage masukan. | ||||
12. | BUS L2 Phase Input | ||||||
13. | SYNC | N / O | 1.5mm2 | Output nalika SYNC ditutup. | Relay biasane mbukak, biasane nutup kontak; Output gratis volt; 7A
Dirating |
||
14. | COM | ||||||
15. | N/C | ||||||
16. | STATUS | 1.0mm2 | Nutup output status | Biasane mbukak kontak, Volts gratis; 5A Rated | |||
17. | 1.0mm2 | ||||||
LINK | Digunakake kanggo setelan paramèter utawa upgrade piranti lunak. |
CATETAN: Sambungan pemrograman PC: nggawe port LINK modul SG72 perusahaan kita nyambung karo port LINK modul, lan nindakake setelan parameter lan ngawasi wektu nyata dening piranti lunak PC perusahaan kita. Mangga mirsani Fig. 2.
LINGKUP LAN DEFINISI PARAMETER PROGRAMMABLE
Tabel 7 - Parameter Konfigurasi Modul
Ora. | barang | Range | Defaults | Katrangan |
1. | Sistem AC Gens | (0-3) | 0 | 0: 3P3W, 1: 1P2W,
2: 3P4W, 3: 2P3W |
2. | Gens Rated Voltage | (30-30000) V | 400 | |
3. | Gens PT Fitted | (0-1) | 0 | 0: Diaktifake 1: Diaktifake |
4. | Gens PT Primary Volt. | (30-30000)V | 100 | |
5. | Gens PT Secondary Volt. | (30-1000)V | 100 | |
6. | Gens liwat Volt. Set | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
7. | (100-120) % | 115 | Ambang | |
8. | (100-120) % | 113 | Nilai bali | |
9. | (0-3600) s | 3 | Nilai tundha | |
10. | Gens Ing Volt. Set | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
11. | (70-100) % | 82 | Ambang | |
12. | (70-100) % | 84 | Nilai bali | |
13. | (0-3600) s | 3 | Nilai tundha | |
14. | Gens liwat Frek. Setel | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
15. | (100-120) % | 110 | Ambang | |
16. | (100-120) % | 104 | Nilai bali | |
17. | (0-3600) s | 3 | Nilai tundha | |
18. | Gens Under Frek. Set | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
19. | (80-100) % | 90 | Ambang | |
20. | (80-100) % | 96 | Nilai bali | |
21. | (0-3600) s | 3 | Nilai tundha |
Ora. | barang | Range | Defaults | Katrangan |
22. | Sistem AC Bus | (0-3) | 0 | 0: 3P3W, 1: 1P2W, 2: 3P4W, 3: 2P3W |
23. | Bus Rated Voltage | (30-30000) V | 400 | |
24. | Bus PT Dipasang | (0-1) | 0 | 0: Diaktifake 1: Diaktifake |
25. | Bus PT Prima Volt. | (30-30000)V | 100 | |
26. | Bus PT Secondary Volt. | (30-1000)V | 100 | |
27. | Bus liwat Volt. Set | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
28. | (100-120) % | 115 | Ambang | |
29. | (100-120) % | 113 | Nilai bali | |
30. | (0-3600) s | 3 | Nilai tundha | |
31. | Bus Ing Volt. Setel | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
32. | (70-100) % | 82 | Ambang | |
33. | (70-100) % | 84 | Nilai bali | |
34. | (0-3600) s | 3 | Nilai tundha | |
35. | Bis liwat Frek. Setel | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
36. | (100-120) % | 110 | Ambang | |
37. | (100-120) % | 104 | Nilai bali | |
38. | (0-3600) s | 3 | Nilai tundha | |
39. | Bus Ing Frek. Set | (0-1) | 1 | 0: Diaktifake 1: Diaktifake |
40. | (80-100) % | 90 | Ambang | |
41. | (80-100) % | 96 | Nilai bali | |
42. | (0-3600) s | 3 | Nilai tundha | |
43. | Alamat Modul | (1-254) | 1 | |
44. | TP | (1-20) | 10 | Periode pulsa regulasi kacepetan = TPxTN |
DESKRIPSI FUNGSI
HSM340 Synchronous Module kanggo nyinkronake generator kanggo bis. Nalika voltagprabédan e, prabédan frekuensi lan prabédan fase ana ing nilai sing wis disetel, bakal ngirim sinyal sinkronisasi kanggo nutup gens switch. Amarga wektu respon cedhak switch bisa disetel, modul bisa digunakake kanggo genset saka macem-macem sumber daya.
Pangguna bisa nyetel liwat voltage, miturut voltage, liwat frekuensi lan ing ambang frekuensi saka gen lan bis liwat piranti lunak ngawasi PC. Nalika modul ndeteksi voltage lan frekuensi gen lan bis iku normal, iku bakal miwiti kanggo nyetel kacepetan. Nalika voltagprabédan e, prabédan frekuensi lan prabédan fase ana ing nilai sing wis disetel, bakal ngirim sinyal sinkronisasi kanggo nutup gens switch.
KONTROL OUTPUT RAISE/DROP SPEED SPEED
Nalika area panyimpangan XP disetel minangka 2Hz, prinsip kerja relay kacepetan mundhakaken / nyelehake kaya ing ngisor iki.
Fungsi pangaturan output relay bisa dipérang dadi 5 langkah.
Tabel 8 - Katrangan Istilah
Ora. | Range | Katrangan | Cathetan |
1 | Ndandani Sinyal | Sinyal mundhak terus | Nyetel aktivasi. Kanggo derivasi sing gedhe banget,
relay kudu ngaktifake terus-terusan. |
2 | Pulsa munggah | Angkat pulsa | Aktivasi nyetel sistem. Relay dianggo ing
pulsa kanggo ngilangi derivasi. |
3 | Ora Reg. | Ora ana angger-angger | Ora ana angger-angger ing wilayah iki. |
4 | Down Pulse | Nguripake pulsa | Aktivasi nyetel sistem. Relay dianggo ing
pulsa kanggo mateni derivasi. |
5 | Ndandani Down Signal | Sinyal drop terus | Aktivasi nyetel sistem. Kanggo gedhe banget
derivasi, drop relay bakal tetep ing status aktif. |
Minangka Fig.3 nuduhake, nalika nyetel panyimpangan XP ngluwihi nilai sing wis disetel, relay bakal ing status aktif terus; nalika XP ora gedhe, relay bakal bisa ing pulsa. Ing Up Pulse, derivasi sing luwih cilik, pulsa dadi luwih cendhek. Nalika nilai output regulator cedhak karo "Ora Reg.", Jembar pulsa bakal dadi nilai paling cendhak; nalika nilai output regulator paling cedhak karo "Down Pulse", lebar pulsa bakal dadi nilai paling dawa.
DIAGRAM TIPIKAL
DIMENSI KASUS
CATETAN INSTALASI
OUTPUT lan nggedhekake relay
Kabeh output minangka output kontak relay. Yen perlu kanggo nggedhekake relay, mangga nambah freewheel diode kanggo loro ends saka nggedhekake relay kang gulungan kawat (nalika kumparan relay duwe DC saiki), utawa nambah resistance-kapasitansi daur ulang (nalika kumparan relay duwe AC saiki), kanggo nyegah gangguan kanggo. controller utawa peralatan liyane.
Tahan VOLTAGE TES
AWAS! Nalika controller wis diinstal ing panel kontrol, yen perlu kanggo nindakake vol dhuwurtage test, please medhot relay kang kabeh sambungan terminal, kanggo tujuan nyegah vol dhuwurtage mlebu relay lan ngrusak.
SmartGen - nggawe generator pinter
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Kutha Zhengzhou
Provinsi Henan
PR Cina
Telpon: +86-371-67988888/67981888/67992951
+86-371-67981000(njaba)
Fax: +86-371-67992952
Email: sales@smartgen.cn
Web: www.smartgen.com.cn /www.smartgen.cn
Kabeh hak dilindhungi undhang-undhang. Ora ana bagean saka publikasi iki sing bisa diprodhuksi ing wangun materi apa wae (kalebu fotokopi utawa nyimpen ing media apa wae kanthi cara elektronik utawa liyane) tanpa idin tinulis saka sing duwe hak cipta. Aplikasi kanggo ijin ditulis sing duwe hak cipta kanggo ngasilake bagean saka publikasi iki kudu ditujokake menyang SmartGen Technology ing alamat ing ndhuwur. Sembarang referensi kanggo jeneng produk merek dagang sing digunakake ing publikasi iki diduweni dening perusahaan masing-masing. SmartGen Technology nduweni hak kanggo ngganti isi dokumen iki tanpa kabar sadurunge.
Tabel 1 - Versi Piranti Lunak
Tanggal | Versi | Isi |
2019-06-03 | 1.0 | Rilis asli. |
2020-12-07 | 1.1 | Ngowahi gambar produk tutup, diameteripun kabel lan liyane
katrangan. |
Dokumen / Sumber Daya
![]() |
SmartGen HSM340 Modul Sinkron [pdf] Manual pangguna HSM340 Modul Sinkron, HSM340, Modul Sinkron, Modul |