SmartGen-LOGO

SmartGen HSM340 Modul Sinkron

SmartGen-HSM340-Sinkron-Modul-PRO

LUWIHVIEW

Modul Sinkron HSM340 dirancang khusus kanggo paralel otomatis genset sistem 400Hz. Miturut paramèter sing wis disetel, modul bisa kanthi otomatis ngrampungake deteksi kondisi paralel genset (prabédan volt, prabédan frekuensi lan fase) lan ngirim sinyal paralel nalika kondisi wis disiapake.
HSM340 Synchronous Module ditrapake kanggo kesempatan sing bisa nyinkronake generator menyang bis. Modul punika prasaja kanggo operate, gampang kanggo nginstal lan digunakake digunakake ing genset kapal lan genset tanah.

KINERJA LAN KARAKTERISTIK

Karakteristik utama kaya ing ngisor iki: 

  • Cocog kanggo 3-phase 4-wire, 3-phase 3-wire, 2-phase 3-wire, sistem daya 2-kawat fase tunggal kanthi frekuensi 400Hz;
  • Potensiometer sing bisa diatur ngidini nyetel paramèter utama babagan sinkronisasi;
  • Parameter operasi bisa disetel liwat piranti lunak tes PC. Port LINK kudu disambungake menyang komputer liwat modul SG72 (USB to LINK);
  • 4 output relay, 2 digunakake kanggo output UP cepet lan output DOWN; 1 relay SYNC digunakake kanggo output cedhak sink, lan 1 relay STATUS digunakake kanggo output status sawise nutup;
  • 1 INH "nyandhet sinkronisasi cedhak output" input digital; nalika aktif lan gens nyinkronake karo bis, indikator SYNC bakal madhangi lan nyelarasake relay cedhak dicegah kanggo output;
  • Wide power supply sawetara DC (8 ~ 35) V;
  • 35mm guide ril soyo tambah;
  • Desain modular, terminal pluggable, struktur kompak karo instalasi gampang.

SPESIFIKASI

Tabel 3 - Parameter Produk

barang Isine
Kerja Voltage DC8.0V kanggo 35.0V, sumber daya terus-terusan.
Konsumsi Sakabèhé ≤1W (Mode siyaga≤0.5W)
AC Voltage Input AC50V~ AC620V (ph-ph)
Frekuensi AC 400Hz
SYNC Output Output gratis 7A AC250V Volt
Output UP 5A AC250V/5A DC30V Volts output free
TURUN Output 5A AC250V/5A DC30V Volts output free
STATUS Output 5A AC250V/5A DC30V Volts output free
Ukuran Kasus 71.6mm x 89.7mm x 60.7mm
Kondisi Kerja Suhu: (-25~+70)°C Kelembapan Relatif: (20~95)%
Kahanan Panyimpenan Suhu: (-30~+80)°C
Intensitas Isolasi Aplikasi AC2.2kV voltage antarane dhuwur voltage terminal lan vol rendahtage terminal;

Arus bocor ora luwih saka 3mA sajrone 1 menit.

Bobot 0.20 kg

INDIKATOR PANEL lan DESKRIPSI TERMINAL

SmartGen-HSM340-Sinkron-Modul-1

Tabel 4 - LED Definition Description 

Indikator warna Katrangan Cathetan
DC 24V Ijo Indikator daya, madhangi nalika daya dianggo kanthi apik.
UP Ijo Iku madhangi nalika mundhakaken kacepetan pulsa dikirim.
TURUN Ijo Iku madhangi nalika nyuda kacepetan pulsa dikirim.
 GENSET  Ijo Iku tansah madhangi nalika gens voltage lan frekuensi normal; iku

sumunar nalika gens voltage lan frekuensi ora normal; dipateni nalika ora ana daya.

 BUS  Ijo Iku tansah murup nalika bis voltage lan frekuensi normal; kelip-kelip nalika bis voltage lan frekuensi ora normal; iku

dipateni nalika ora ana daya.

ΔF Frekuensi

Bedane.

Ijo Iku madhangi nalika gens 'lan bus' frekuensi lan voltagwes biasa ae,

lan prabédan wektu nyata ana ing sawetara sing wis disetel.

ΔU

Volt bedane.

Ijo Iku madhangi nalika gens 'lan bus' frekuensi lan voltagwes biasa ae,

lan wektu nyata voltage prabédan ana ing sawetara sing wis disetel.

SYNC Tutup abang Nalika output relay cedhak, lamp bakal padhang. Tutup pulsa:

400 ms.

 STATUS  abang Sawise output sinyal cedhak, output relay lan madhangi; nalika sinkronisasi antarane gen lan bis ora dideteksi, relay bakal

ora output lan lamp bakal mateni.

Tabel 5 - Katrangan Potensiometer 

Potentiometer Range Katrangan Cathetan
TN/ms Length of Control Pulse (25-500)ms Min. wektu kontrol pulsa langgeng.
Range Proporsi XP/Hz  (0-±2.5)Hz Ing wilayah iki, jembaré pulsa ana ing proporsi langsung karo nilai panyimpangan frekuensi dirating. proporsi XP/Hz

jangkoan

FREQ/Hz (0.1-0.5)Hz prabédan frekuensi ditrima.
VOLTAGE/% (2-12)% Ditrima voltage prabédan
BREAKER / ms (20-200)ms Wektu saklar ditutup.

Tabel 6 - Katrangan Sambungan Terminal 

Ora. Fungsi Ukuran Kabel Cathetan
1. Input Daya DC - 1.5mm2 Disambungake karo negatif saka baterei wiwitan.
2. Input Daya DC + 1.5mm2 Disambungake karo baterei wiwitan positif.
3. INH 1.0mm2 "Tutup Output Nyandhet" Input
4. IN 1.0mm2
5.  TURUN Output  1.0mm2 Output nalika kacepetan suda. Biasane mbukak; Output gratis volt; 5A Rated
6.
7.  Output UP  1.0mm2 Output nalika kacepetan mundhak. Biasane mbukak; Output gratis volt; 5A Rated
8.
9. GEN L1 Phase Input 1.0mm2 Gen AC voltage masukan.
10. GEN L2 Phase Input
11. BUS L1 Phase Input 1.0mm2 Bus AC Voltage masukan.
12. BUS L2 Phase Input
13.  SYNC N / O  1.5mm2  Output nalika SYNC ditutup. Relay biasane mbukak, biasane nutup kontak; Output gratis volt; 7A

Dirating

14. COM
15. N/C
16. STATUS 1.0mm2 Nutup output status Biasane mbukak kontak, Volts gratis; 5A Rated
17. 1.0mm2
LINK Digunakake kanggo setelan paramèter utawa upgrade piranti lunak.

 

SmartGen-HSM340-Sinkron-Modul-2CATETAN: Sambungan pemrograman PC: nggawe port LINK modul SG72 perusahaan kita nyambung karo port LINK modul, lan nindakake setelan parameter lan ngawasi wektu nyata dening piranti lunak PC perusahaan kita. Mangga mirsani Fig. 2.

LINGKUP LAN DEFINISI PARAMETER PROGRAMMABLE

Tabel 7 - Parameter Konfigurasi Modul 

Ora. barang Range Defaults Katrangan
1. Sistem AC Gens (0-3) 0 0: 3P3W, 1: 1P2W,

2: 3P4W, 3: 2P3W

2. Gens Rated Voltage (30-30000) V 400
3. Gens PT Fitted (0-1) 0 0: Diaktifake 1: Diaktifake
4. Gens PT Primary Volt. (30-30000)V 100
5. Gens PT Secondary Volt. (30-1000)V 100
6.  Gens liwat Volt. Set (0-1) 1 0: Diaktifake 1: Diaktifake
7. (100-120) % 115 Ambang
8. (100-120) % 113 Nilai bali
9. (0-3600) s 3 Nilai tundha
10.  Gens Ing Volt. Set (0-1) 1 0: Diaktifake 1: Diaktifake
11. (70-100) % 82 Ambang
12. (70-100) % 84 Nilai bali
13. (0-3600) s 3 Nilai tundha
14.  Gens liwat Frek. Setel (0-1) 1 0: Diaktifake 1: Diaktifake
15. (100-120) % 110 Ambang
16. (100-120) % 104 Nilai bali
17. (0-3600) s 3 Nilai tundha
18.  Gens Under Frek. Set (0-1) 1 0: Diaktifake 1: Diaktifake
19. (80-100) % 90 Ambang
20. (80-100) % 96 Nilai bali
21. (0-3600) s 3 Nilai tundha
Ora. barang Range Defaults Katrangan
22. Sistem AC Bus (0-3) 0 0: 3P3W, 1: 1P2W, 2: 3P4W, 3: 2P3W
23. Bus Rated Voltage (30-30000) V 400
24. Bus PT Dipasang (0-1) 0 0: Diaktifake 1: Diaktifake
25. Bus PT Prima Volt. (30-30000)V 100
26. Bus PT Secondary Volt. (30-1000)V 100
27.  Bus liwat Volt. Set (0-1) 1 0: Diaktifake 1: Diaktifake
28. (100-120) % 115 Ambang
29. (100-120) % 113 Nilai bali
30. (0-3600) s 3 Nilai tundha
31.  Bus Ing Volt. Setel (0-1) 1 0: Diaktifake 1: Diaktifake
32. (70-100) % 82 Ambang
33. (70-100) % 84 Nilai bali
34. (0-3600) s 3 Nilai tundha
35.  Bis liwat Frek. Setel (0-1) 1 0: Diaktifake 1: Diaktifake
36. (100-120) % 110 Ambang
37. (100-120) % 104 Nilai bali
38. (0-3600) s 3 Nilai tundha
39.  Bus Ing Frek. Set (0-1) 1 0: Diaktifake 1: Diaktifake
40. (80-100) % 90 Ambang
41. (80-100) % 96 Nilai bali
42. (0-3600) s 3 Nilai tundha
43. Alamat Modul (1-254) 1
44. TP (1-20) 10 Periode pulsa regulasi kacepetan = TPxTN

DESKRIPSI FUNGSI

HSM340 Synchronous Module kanggo nyinkronake generator kanggo bis. Nalika voltagprabédan e, prabédan frekuensi lan prabédan fase ana ing nilai sing wis disetel, bakal ngirim sinyal sinkronisasi kanggo nutup gens switch. Amarga wektu respon cedhak switch bisa disetel, modul bisa digunakake kanggo genset saka macem-macem sumber daya.
Pangguna bisa nyetel liwat voltage, miturut voltage, liwat frekuensi lan ing ambang frekuensi saka gen lan bis liwat piranti lunak ngawasi PC. Nalika modul ndeteksi voltage lan frekuensi gen lan bis iku normal, iku bakal miwiti kanggo nyetel kacepetan. Nalika voltagprabédan e, prabédan frekuensi lan prabédan fase ana ing nilai sing wis disetel, bakal ngirim sinyal sinkronisasi kanggo nutup gens switch.

KONTROL OUTPUT RAISE/DROP SPEED SPEED

Nalika area panyimpangan XP disetel minangka 2Hz, prinsip kerja relay kacepetan mundhakaken / nyelehake kaya ing ngisor iki.

SmartGen-HSM340-Sinkron-Modul-3

Fungsi pangaturan output relay bisa dipérang dadi 5 langkah.

Tabel 8 - Katrangan Istilah

Ora. Range Katrangan Cathetan
1 Ndandani Sinyal Sinyal mundhak terus Nyetel aktivasi. Kanggo derivasi sing gedhe banget,

relay kudu ngaktifake terus-terusan.

2 Pulsa munggah Angkat pulsa Aktivasi nyetel sistem. Relay dianggo ing

pulsa kanggo ngilangi derivasi.

3 Ora Reg. Ora ana angger-angger Ora ana angger-angger ing wilayah iki.
4 Down Pulse Nguripake pulsa Aktivasi nyetel sistem. Relay dianggo ing

pulsa kanggo mateni derivasi.

 5  Ndandani Down Signal  Sinyal drop terus Aktivasi nyetel sistem. Kanggo gedhe banget

derivasi, drop relay bakal tetep ing status aktif.

Minangka Fig.3 nuduhake, nalika nyetel panyimpangan XP ngluwihi nilai sing wis disetel, relay bakal ing status aktif terus; nalika XP ora gedhe, relay bakal bisa ing pulsa. Ing Up Pulse, derivasi sing luwih cilik, pulsa dadi luwih cendhek. Nalika nilai output regulator cedhak karo "Ora Reg.", Jembar pulsa bakal dadi nilai paling cendhak; nalika nilai output regulator paling cedhak karo "Down Pulse", lebar pulsa bakal dadi nilai paling dawa.

DIAGRAM TIPIKAL

SmartGen-HSM340-Sinkron-Modul-4

DIMENSI KASUS

SmartGen-HSM340-Sinkron-Modul-5

CATETAN INSTALASI

OUTPUT lan nggedhekake relay
Kabeh output minangka output kontak relay. Yen perlu kanggo nggedhekake relay, mangga nambah freewheel diode kanggo loro ends saka nggedhekake relay kang gulungan kawat (nalika kumparan relay duwe DC saiki), utawa nambah resistance-kapasitansi daur ulang (nalika kumparan relay duwe AC saiki), kanggo nyegah gangguan kanggo. controller utawa peralatan liyane.

Tahan VOLTAGE TES
AWAS! Nalika controller wis diinstal ing panel kontrol, yen perlu kanggo nindakake vol dhuwurtage test, please medhot relay kang kabeh sambungan terminal, kanggo tujuan nyegah vol dhuwurtage mlebu relay lan ngrusak.

SmartGen - nggawe generator pinter
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Kutha Zhengzhou
Provinsi Henan
PR Cina
Telpon: +86-371-67988888/67981888/67992951
+86-371-67981000(njaba)
Fax: +86-371-67992952
Email: sales@smartgen.cn
Web: www.smartgen.com.cn /www.smartgen.cn

Kabeh hak dilindhungi undhang-undhang. Ora ana bagean saka publikasi iki sing bisa diprodhuksi ing wangun materi apa wae (kalebu fotokopi utawa nyimpen ing media apa wae kanthi cara elektronik utawa liyane) tanpa idin tinulis saka sing duwe hak cipta. Aplikasi kanggo ijin ditulis sing duwe hak cipta kanggo ngasilake bagean saka publikasi iki kudu ditujokake menyang SmartGen Technology ing alamat ing ndhuwur. Sembarang referensi kanggo jeneng produk merek dagang sing digunakake ing publikasi iki diduweni dening perusahaan masing-masing. SmartGen Technology nduweni hak kanggo ngganti isi dokumen iki tanpa kabar sadurunge.

Tabel 1 - Versi Piranti Lunak

Tanggal Versi Isi
2019-06-03 1.0 Rilis asli.