EMERSON EC2-352 Tampilan Case lan Coldroom Controller
Spesifikasi
- Sumber daya: 24VDC
- Konsumsi daya: 4…20mA
- Komunikasi: Kontak SPDT, AgCdO Induktif (AC15) 250V/2A Resistif (AC1) 250V/8A; 12A total bali saiki
- Ukuran konektor plug-in: 24V AC, 0.1 … 1A
- Operasi panyimpenan suhu: 0…80% rh noncondensing
- Kelembapan: IP65 (proteksi ngarep karo gasket)
- Kelas perlindungan: IP65
- Input pemancar tekanan: 24VDC, 4…20mA
- Output relay: (3) Triac output kanggo EX2 Electrical Control Valve Coil (ASC 24V mung)
Pandhuan Panggunaan Produk
Modifikasi Parameter
Kanggo ngowahi parameter, tindakake prosedur ing ngisor iki:
- Akses keypad.
- Goleki parameter sing dikarepake ing Dhaptar Parameter.
- Setel nilai parameter ing kisaran sing ditemtokake.
Aktifake Defrost
Siklus defrost bisa diaktifake sacara lokal saka keypad. Kanggo ngaktifake siklus defrost, tindakake langkah iki:
- Akses keypad.
- Pilih opsi aktivasi defrost.
Fungsi Khusus
Fungsi Khusus bisa diaktifake kanthi:
- Ngakses keypad.
- Milih fungsi khusus sing dikarepake.
Tampilan Data
Kanggo nampilake data ing layar, tindakake langkah iki:
- Pencet tombol SEL kanggo nggulung kabeh data sing bisa ditampilake.
- Tampilan bakal nuduhake pengenal numerik saka data banjur data sing dipilih.
- Sawise rong menit, tampilan bakal bali menyang data sing dipilih.
Indikator Status Logis
- Relay kompresor: Nuduhake status logis relay kompresor.
- IR LED: Nuduhake status LED Infrared.
- LED aktivitas Ethernet: Nuduhake aktivitas Ethernet (mung aktif nalika pin layanan dipencet).
- Fan relay: Nuduhake status logis saka relay penggemar.
- Relay pemanas defrost: Nuduhake status logis relay pemanas defrost.
- Kondisi weker: Nuduhake kondisi weker.
Cathetan:
Dokumen iki ngemot instruksi cekak kanggo pangguna sing berpengalaman. Gunakake kolom pungkasan ing Dhaptar Parameter kanggo nyathet setelan individu sampeyan. Informasi sing luwih rinci bisa ditemokake ing Manual pangguna.
EC2-352 minangka pengontrol kulkas khusus kanthi superheat lan driver kanggo Alco Controls Electric Control Valve EX2. Kajaba iku, EC2-352 ngontrol suhu udara lan ngatur defrost lan penggemar.
Pemancar tekanan PT5 (1) lan sensor suhu pipa ECN-Pxx (2) ngukur tekanan gas nyedhot jenuh lan suhu gas nyedhot ing stopkontak evaporator lan menehi sinyal menyang loop kontrol superheat. Output controller superheat modulates bukaan saka EX2 jembaré pulsa modulated Katup Kontrol Listrik (6) saéngga ngoptimalake aliran massa refrigerant liwat evaporator ing.
Sensor suhu udara ECN-Sxx (3) lan (4) ngukur suhu udara-in lan metu saka evaporator lan sinyal feed menyang termostat suhu udhara. Sensor sirip ECN-Fxx (5) digunakake kanggo mungkasi defrost. Kontroler duwe 3 output relay kanggo ngontrol kompresor (7), pemanas defrost (9) lan penggemar evaporator (8). Mangga takon data teknis (tengen) kanggo rating input lan output.
Ing cilik saka mundhut daya, amarga karakteristik mati-mati positif saka EX2 Control Valves, katup solenoid line Cairan ora perlu kanggo nyegah banjir kompresor.
instruksi safety
- Waca instruksi instalasi kanthi lengkap. Gagal netepi bisa nyebabake piranti gagal, karusakan sistem utawa ciloko pribadi.
- Produk kasebut dimaksudake kanggo digunakake dening wong sing duwe kawruh lan katrampilan sing cocog.
- Priksa manawa rating listrik saben data teknis ora ngluwihi.
- Pedhot kabeh voltages saka sistem sadurunge instalasi.
- Tansah suhu ing watesan nominal.
- Patuhi peraturan listrik lokal nalika kabel
Data Teknis
EC2 Series Controller
sumber daya | 24VAC ± 10%; 50/60Hz; Kelas II |
konsumsi daya | 20VA maks kalebu EX2 |
Komunikasi | TCP/IP Ethernet 10 MBit/s |
Ukuran konektor plug-in | Terminal sekrup sing bisa dicopot ukuran kawat 0.14 … 1.5 mm2 |
Operasi panyimpenan suhu |
-20 … +65°C 0… + 60 ° C |
Kelembapan | 0…80% rh non kondensasi |
Kelas perlindungan | IP65 (proteksi ngarep nganggo gasket) |
Input pemancar tekanan | 24VDC, 4…20mA |
Relay output (3) | Kontak SPDT, AgCdO |
Induktif (AC15) 250V/2A | |
Resistif (AC1) 250V/8A; 12A total bali saiki | |
Triac output kanggo EX2 Electrical Control Valve Coil (ASC 24V mung) | 24V AC, 0.1 … 1A |
menehi tandha | EAC |
Pemasangan:
EC2-352 bisa dipasang ing panel kanthi potongan 71 x 29 mm. Deleng gambar dimensi ing ngisor iki kanggo syarat papan kalebu konektor mburi. Tekan pengontrol menyang potongan panel.(1)
- Priksa manawa lugs soyo tambah siram karo njaba omah controller
- Lebokake tombol allen menyang bolongan panel ngarep lan nguripake searah jarum jam.
- Lug pemasangan bakal nguripake lan mboko sithik pindhah menyang panel (2)
- Nguripake tombol allen nganti lug soyo tambah lagi wae ndemek panel.
- Banjur pindhahake lug pemasangan liyane menyang posisi sing padha (3)
- Kencengake loro-lorone kanthi ati-ati nganti controller diamanake.
- Aja kenceng banget amarga lug sing dipasang bakal gampang pecah.
Instalasi Listrik:
Deleng diagram kabel listrik (ing ngisor) kanggo sambungan listrik. Salinan diagram iki diwenehi label ing controller. Gunakake kabel/kabel sambungan sing cocog kanggo operasi 90°C (EN 60730-1)
Input analog EC2 mung kanggo sensor khusus lan ora kudu disambungake menyang piranti liyane. Nyambungake sembarang input EC2 kanggo voltage bakal ngrusak EC2 permanen.
penting: Supaya controller lan kabel sensor uga dipisahake saka kabel utama. Jarak minimal sing disaranake 30mm.
Pènget: Gunakake trafo kategori kelas II kanggo sumber daya 24VAC (EN 60742). Aja lemah garis 24VAC. Disaranake nggunakake siji trafo saben EC2 controller lan nggunakake trafo kapisah kanggo pengontrol pihak katelu, supaya bisa gangguan utawa masalah grounding ing sumber daya. Nyambungake sembarang input EC3 kanggo voltage bakal ngrusak EC2 permanen.
EC2-352 Tampilan Case lan Coldroom Controller
Posisi Sensor sing Disaranake kanthi rinci:
- Sensor suhu coil-out ECN-Pxx: Posisi langsung sawise evaporator ing garis nyedhot umum.
- Sensor suhu udara-in ECN-Sxx: Posisi ing tengah kabinèt paling dhuwur.
- Sensor suhu udara metu ECN-Sxx: Posisi asimetris luwih cedhak karo katup ekspansi sing paling dhuwur.
- Sensor suhu sirip ECN-Fxx: Posisi ing evaporator, asimetris nyedhaki katup expansion.
Rekomendasi kanggo masang sensor pipa:
Asuransiake kontak termal sing tepat kanthi nggunakake pipa metalik clamp utawa tali plastik tahan suhu. Aja nggunakake bungkus dasi plastik standar (kaya sing digunakake kanggo kabel listrik) amarga bisa dadi longgar saka wektu, sing bisa nyebabake pangukuran suhu sing salah lan kinerja kontrol superheat sing ora apik. Disaranake kanggo ngisolasi sensor suhu pipa nganggo ARMAFLEX™ utawa sing padha. Posisi sensor pipa sing disaranake yaiku antarane jam 9 nganti jam 3 kaya sing ditampilake ing gambar.
- PT5-07M pemancar tekanan nyedhot: Posisi ing garis nyedhot umum cedhak sensor suhu coil-metu
- (2) Loro-lorone sensor suhu udara kudu dipasang ing spacer ing saluran udara supaya ana aliran udara ing saubengé.
Ati-ati: Kabel sensor bisa ditambah yen perlu. Sambungan kudu direksa saka banyu lan bledug. Sensor suhu stopkontak evaporator kudu dipasang ing header nyedhot umum saka evaporator. Koreksi kalibrasi bisa ditindakake kanthi nggunakake parameter u1 (pirsani prosedur ing ngisor iki).
Setup lan Modifikasi Parameter Nggunakake Keypad
Kanggo penak, panrima infra merah kanggo unit remot kontrol IR opsional dibangun, mbisakake modifikasi paramèter sistem kanthi cepet lan gampang nalika antarmuka komputer ora kasedhiya. Utawa, paramèter bisa diakses liwat keypad 4-tombol. Parameter konfigurasi dilindhungi dening sandhi angka. Tembung sandhi standar yaiku "12". Kanggo milih konfigurasi parameter:
- Pencet tombol PRG luwih saka 5 detik, "0" sumunar ditampilake
- Pencet
or
nganti "12" ditampilake (sandi)
- Pencet SEL kanggo konfirmasi sandhi
Kode parameter sing bisa diowahi pisanan ditampilake (/1). Kanggo ngowahi parameter ndeleng modifikasi Parameter ing ngisor iki.
Modifikasi Parameter
tata cara:
- Pencet
or
kanggo nuduhake kode parameter sing kudu diganti;
- Pencet SEL kanggo nampilake nilai parameter sing dipilih;
- Pencet
or
kanggo nambah utawa nyuda regane;
- Pencet SEL kanggo konfirmasi sementara nilai anyar lan nampilake kode;
- Baleni prosedur saka wiwitan "pencet
or
kanggo nuduhake…”
Kanggo metu lan nyimpen setelan anyar:
- Pencet PRG kanggo konfirmasi nilai anyar lan metu saka prosedur modifikasi paramèter.
Kanggo metu tanpa ngowahi parameter apa wae:
- Aja pencet tombol apa wae kanggo paling sethithik 60 detik (TIME OUT).
- Tekan "ESC" pada remote control IR.
Aktifake defrost:
Siklus defrost bisa diaktifake sacara lokal saka keypad:
- Tekan ing
tombol
kanggo luwih saka 5 detik, sumunar "0" ditampilake
- Pencet
or
nganti "12" ditampilake (sandi)
- Pencet SEL kanggo konfirmasi sandhi Siklus defrost diaktifake.
Fungsi Khusus:
Fungsi Khusus bisa diaktifake kanthi:
- Pencet
lan
bebarengan kanggo luwih saka 5 detik, sumunar "0" ditampilake.
- Pencet
or
nganti tembung sandhi ditampilake (standar = 12). Yen tembung sandhi diganti, pilih sandhi anyar.
- Pencet SEL kanggo konfirmasi sandhi, "0" ditampilake lan mode Fungsi Khusus diaktifake.
- Pencet
or
kanggo milih fungsi. Jumlah fungsi khusus iku dinamis lan controller gumantung. Deleng dhaptar ing ngisor iki.
- Pencet SEL kanggo ngaktifake fungsi kasebut tanpa ninggalake mode fungsi khusus.
- Pencet PRG kanggo ngaktifake fungsi lan ninggalake mode fungsi khusus.
Umume Fungsi Khusus bisa digunakake ing mode pilihan, telpon pisanan ngaktifake fungsi kasebut, lan telpon kapindho mateni fungsi kasebut. Indikasi fungsi kasebut mung bisa ditampilake sawise metu saka mode fungsi khusus.
- Tampilan fungsi tes
- Mbusak pesen weker
- Mode reresik. Mode reresik kanthi efektif minangka defrost manual kanthi pilihan penggemar on/off. Mode reresik ngirim ora digunakake kanggo ngisolasi aplikasi kanggo tujuan pangopènan.
- Penggemar mung
- Setel katup kontrol elektronik dadi 100% mbukak
- Nampilake alamat TCP/IP saiki
- Setel alamat TCP / IP controller menyang 192.168.1.101 (nilai standar). Owah-owahan iki mung sak wentoro. A daya mudhun bakal ngreset alamat sadurunge.
- Ngreset kabeh paramèter menyang setelan gawan pabrik. Controller bakal nuduhake "oF" sak reset lan tutup bakal nutup.
Tampilan data:
Data sing bakal ditampilake kanthi permanen ing tampilan bisa dipilih dening pangguna (parameter /1). Yen ana weker, kode weker ditampilake kanthi gantian karo data sing dipilih. Pangguna bisa nyandhet kode weker. Sampeyan bisa kanggo sementara nampilake nilai kasebut. Iki minangka fitur sing migunani nalika wiwitan nyetel sistem tanpa bantuan Webkaca. Pencet tombol SEL kanggo nggulung kabeh data sing bisa ditampilake.
Tampilan bakal nuduhake siji detik pengenal angka saka data (ndeleng parameter / 1) banjur data sing dipilih. Sawise rong menit tampilan bakal bali menyang dening parameter /1 data sing dipilih. Tumindak iki mung valid nalika parameter H2 = 3.
Daftar Parameter
PARAMETER TAMPILAN
/ | PARAMETER TAMPILAN | Min | Maks | Unit | Def. | adat |
/1 | Nilai kanggo nuduhake | 0 | 9 | – | 0 | —— |
0 = Suhu kontrol termostat karo Temp. keselarasan / C
1 = Suhu udara mlebu °C 2 = Suhu metu udara °C 3 = Suhu weker °C 4 = Suhu mandhek defrost °C 5 = Suhu coil-in °C diitung saka tekanan 6 = Suhu coil-out °C 7 = Superheat sing diitung °K 8 = Bukaan katup ing % 9 = Nuduhake status defrost |
||||||
/2 | Pateni weker 0 = mati, 1 = urip | 0 | 1 | – | 0 | —— |
/5 | Unit Suhu 0 = °C, 1 = °F | 0 | 1 | – | 0 | —— |
/6 | Titik desimal 0 = ya, 1 = ora | 0 | 1 | – | 0 | —— |
/7 | Tampilan nalika defrost | 0 | 2 | – | 0 | —— |
0 = dF (= mode defrost); 1 = dF + suhu mandhek defrost.
2 = dF + suhu kontrol |
||||||
/C | Alignment suhu kanggo /1=0 | -20 | 20 | K / °F | 0.0 | —— |
PARAMETER ALARM
A0 | Rata-rata suhu weker faktor | 0 | 100 | % | 100 |
A1 | Wektu tundha weker suhu rendah | 0 | 180 | min | 5 |
A2 | Wektu tundha weker suhu dhuwur | 0 | 180 | min | 5 |
A3 | Tundha weker sawise defrost | 0 | 180 | min | 10 |
AH | Watesan weker suhu dhuwur | AL | 70 | °C / K | 40 |
AL | Watesan weker suhu rendah | -55 | AH | °C / K | -50 |
At | Jinis watesan weker | 0 | 1 | – | 0 |
0=suhu mutlak °C; 1 = suhu relatif K kanggo setpoint |
r PARAMETER TERMOSTAT
r1 | Min setpoint | -50 | r2 | °C | -50 | —— |
r2 | Setpoint maks | r1 | 60 | °C | 40 | —— |
r3 | Kontrol dina / wengi 0 = mati, 1 = aktif | 0 | 1 | – | 1 | —— |
r4 | Mode termostat | 0 | 4 | – | 1 | —— |
0 = mati, ora ana fungsi termostat, terus hawa adhem ing sensor
ngawasi mati, ora suhu. weker kui 1 = cooling, kontrol deadband potong ing = set-point + prabédan Cut metu = set-point 2 = cooling, modulating thermostat cut in = set-point Cut metu = set-titik - prabédan / 2 3 = panas, kontrol deadband kethok = set-point – bedane cut out = set-point 4 = ing, kontrol external nggunakake nvi Valve liwat SNMP. Pemantauan sensor udara mlebu lan metu. Temp. weker bakal digawe |
||||||
r6 | Setpoint wengi | r1 | r2 | °C | 4.0 | —— |
r7 | Diferensial wengi | 0.1 | 20.0 | K | 2.0 | —— |
r8 | Faktor rata-rata, operasi dina | 0 | 100 | % | 100 | —— |
r9 | Faktor rata-rata, operasi wengi | 0 | 100 | % | 50 | —— |
rd | Dina diferensial | 0.1 | 20.0 | K | 2.0 | —— |
St | Setpoint dina | r1 | r2 | °C | 2.0 | —— |
d PARAMETER DEFROST
d0 | Mode defrost | 0 | 2 | – | 1 |
0 = defrost alami, pemanas defrost ora diaktifake
defrost pulsed ora bisa 1 = defrost dipeksa, defrost pemanas diaktifake, defrost pulsed bisa 2 = defrost paksa, pemanas defrost diaktifake, defrost pulsa bisa, mungkasi defrost nggunakake nviStartUp liwat SNMP |
|||||
d1 | Pemberhentian dening: | 0 | 3 | – | 0 |
0 = mungkasi kanthi suhu,
mandap dening wektu bakal ngasilake weker 1 = mandap dening wektu, mandap dening suhu bakal generate weker 2 = pisanan, apa wae pisanan utawa suhu, ora weker 3 = pungkasan, dening wektu lan suhu, ora weker |
|||||
d2 | Sensor terminasi defrost | 0 | 1 | – | 1 |
0 = Sensor defrost khusus kudu diinstal
1 = Sensor air-out digunakake kanggo mandap defrost |
PARAMETER | Min | Maks | Unit | Def. | adat | |
d3 | Defrost pulsa | 0 | 1 | – | 0 | |
0 = mati, ora ana defrost pulsa, pemanas dipateni nalika mungkasi defrost
suhu dt utawa max. wektu dP apa wae sing dipilih 1 = urip, defrost pulsa, dd lan dH digunakake, pemanas dipateni ing dH lan diuripake maneh ing dH – dd |
||||||
d4 | Defrost nalika wiwitan 0 = ora, 1 = ya | 0 | 1 | – | 0 | —— |
d5 | Tundha daya munggah defrost | 0 | 180 | min | 0 | —— |
d6 | Pump mudhun wektu tundha | 0 | 180 | sek | 0 | —— |
Kompresor bakal mbukak nalika tundha pompa mudhun nalika katup ditutup | ||||||
d7 | Tundha saluran | 0 | 15 | min | 2 | —— |
d8 | Tundha injeksi | 0 | 180 | sek | 0 | —— |
Katup mbukak nalika wektu tundha injeksi nalika kompresor ora mlaku | ||||||
d9 | Panjaluk mode defrost
0 = mati, 1 = on, 2 = on bebarengan karo wektu defrost |
0 | 2 | – | 0 | —— |
dd | Diferensial defrost pulsa | 1 | 20 | K | 2 | —— |
dH | Setpoint defrost pulsa | -40 | dt | °C | 5 | —— |
dt | Defrost suhu mandap | -40 | 90 | °C | 8 | —— |
dP | Durasi defrost maksimal | 0 | 180 | min | 30 | —— |
dI | Interval Defrost | 0 | 192 | h | 8 | —— |
du | Mulai tundha sawise synch | 0 | 180 | min | 30 | —— |
F PARAMETER FAN
F1 | Penggemar wiwitan dening: 0 = ing | 0 | 4 | – | 0 |
1 = telat wektu Fd, kesalahan ing suhu
2 = dening suhu Ft, kesalahan ing wektu 3 = pisanan, apa wae sing teka pisanan utawa suhu, ora weker 4 = pungkasan, wektu lan suhu kudu teka, ora weker |
|||||
F2 | Sajrone ora cooling | 0 | 2 | – | 0 |
0 = ing; 1 = mati; 2 = telat dening F4; 3 = mati, nalika lawang mbukak | |||||
F3 | Sajrone defrost 0 = on, 1 = off | 0 | 1 | – | 0 |
F4 | Mungkasi wektu tundha | 0 | 30 | min | 0 |
F5 | Sajrone reresik 0 = mati, 1 = on | 0 | 1 | – | 0 |
Fd | Penundaan kipas sawise defrost | 0 | 30 | min | 0 |
Ft | Ing suhu sawise defrost | -40 | 40 | °C | 0 |
C PARAMETER KOMPRESOR
C0 | Tundha wiwitan pisanan sawise daya munggah | 0 | 15 | min | 0 |
C1 | Wektu siklus | 0 | 15 | min | 0 |
C2 | Min. wektu mandheg | 0 | 15 | min | 0 |
C3 | Min. wektu mlaku | 0 | 15 | min | 0 |
PARAMETER SUPERHEAT
u0 | Refrigerant 0 = R22 1 = R134a 2 = R507 3 = R404A 4 = R407C
5 = R410A 6 = R124 7 = R744 |
0 | 7 | – | 3 |
u1 | Koreksi glide / dp
Glide = nilai positif Penurunan tekanan = nilai negatif |
-20.0 | 20.0 | K | 0.0 |
u2 | kontrol MOP
0 = MOP mati, 1 = MOP aktif |
0 | 1 | – | 0 |
u3 | suhu MOP | -40 | 40 | °C | 0 |
u4 | Mode superheat 0 = mati 1 = superheat tetep
2 = superheat adaptif |
0 | 2 | – | 1 |
u5 | Superheat init setpoint | u6 | u7 | K | 6 |
u6 | Titik setel superheat min. | 3 | u7 | K | 3 |
u7 | Superheat setpoint maks. | u6 | 20 | K | 15 |
uu | Miwiti mbukak | 25 | 75 | % | 30 |
P PARAMETER SENSOR ANALOG
P1 | Pemilihan tipe sensor tekanan 0 = PT5-07M; 1 = PT5-18M; 2 = PT5-30M | 0 | 2 | – | 0 |
H PARAMETER LAIN
H2 | Akses tampilan | 0 | 4 | – | 3 | —— |
0 = kabeh dipatèni (Ati-ati, akses menyang controller mung liwat TCP / IP Ethernet
jaringan bisa) 1 = Keyboard aktif 2 = IR remot kontrol aktif 3 = Keyboard lan remot kontrol IR; Tampilan data sementara lan defrost manual diaktifake. 4 = Keyboard lan remot kontrol IR; Tampilan data sementara dipateni. Kontrol setpoint karo SEL tombol lan defrost manual aktif. |
||||||
H3 | kode akses IR | 0 | 199 | – | 0 | —— |
H5 | Sandi | 0 | 199 | – | 12 | —— |
Formula kanggo Faktor Rata-rata A0, r8, r9
Pitungan suhu kanthi rumus ing ngisor iki: Suhu = Airin * (1 – Faktor Rata-rata / 100) + Airout * Faktor Rata-rata / 100
Examples:
- Faktor rata-rata = 0 Suhu = Udara ing
- Faktor rata-rata = 100 Suhu = Udara metu
- Faktor rata-rata = 50 Suhu = Rata-rata antarane Air-in lan Air-out
Kode Weker
- E0 Sensor tekanan alarm
- E1 Coil metu sensor weker
- E2 Weker sensor udhara Kode Weker iki diblokir yen ora ana sensor udhara sing digunakake (A0, r8 lan r9 = 100)
- E3 Weker sensor udara metu Kode Weker iki diblokir yen ora ana sensor udara metu (A0, r8 lan r9 = 0) lan sensor sirip dipasang (d2 = 1)
- Weker sensor sirip E4 Kode Weker iki diblokir yen ora ana sensor sirip sing digunakake (d2 = 0)
- Panjelasan kanggo E0 … E4 Weker: Ora ana sensor sing nyambung, utawa sensor lan/utawa kabel sensor rusak utawa short-circuited.
- Er Data tampilan kesalahan - metu saka sawetara
- Data sing dikirim menyang tampilan ora ana jangkauan.
- AH Weker suhu dhuwur
- AL weker suhu rendah
- Operasi darurat AE Thermostat
- Gagal sensor udara, sistem ana ing mode pendinginan terus
- Status Katup AF
- Katup ditutup amarga kompresor safety loop aktif
- Ao Superheat, operasi darurat Sensor gagal
- Ar Ora ana aliran refrigerant sing dideteksi
- Ora ana aliran refrigeran sing dideteksi
- Au Valve mbukak 100% luwih saka 10 menit
- dt Penghentian defrost paksa (wektu utawa suhu)
- Ft Dipaksa penggemar wiwitan (wektu utawa suhu)
Pesen
- - Ora ana data sing ditampilake
Tampilan bakal nuduhake "-" nalika wiwitan simpul lan nalika ora ana data sing dikirim menyang tampilan. - Ing Reset menyang nilai gawan diaktifake
Tampilan bakal nuduhake "Ing" nalika set data konfigurasi standar pabrik diwiwiti. - Panjaluk Id Wink ditampa
Tampilan bakal nuduhake sumunar "Id" nalika panjalukan nglirik ditampa. "Id" sing sumunar bakal ditampilake ing tampilan nganti tombol layanan bakal dipencet, utawa wektu tundha 30 menit bakal kadaluwarsa utawa panjaluk nglirik kapindho ditampa. Fungsi iki mung tumindak nalika nggunakake protokol SNMP - OF Node offline
Node kasebut offline lan ora ana aplikasi sing mlaku. Iki minangka asil saka printah manajemen jaringan lan bakal kelakon kanggo example nalika instalasi simpul.- dS Defrost siyaga
- dP Pompa mudhun
- dF siklus defrost
- dd Defrost saluran tundha
- dI Defrost injeksi tundha
- du Defrost wiwitan tundha
- Cn Cleaning
- Weker CL diresiki
- Visualisasi Data: Webkaca
A TCP/IP Controller-Readme file kasedhiya ing www.emersonclimate.eu websitus kanggo nyedhiyani informasi rinci babagan TCP / IP panyambungan Ethernet. Mangga deleng iki file yen sampeyan butuh informasi ngluwihi isi lembar instruksi iki. EC2-352 nduweni antarmuka komunikasi Ethernet TCP/IP sing ngidini pengontrol disambungake langsung menyang PC utawa jaringan liwat port Ethernet standar. Kontroler EC2-352 wis dipasang WebKaca supaya pangguna bisa nggambarake dhaptar parameter kanthi gampang nggunakake label teks nyata.
Ora ana piranti lunak utawa hardware khusus sing dibutuhake.
- Sambungake EC2-352 nggunakake ECX-N60 kabel Déwan opsional menyang jaringan utawa hub sing mbisakake controller kanggo nampa TCP dinamis / alamat IP. Yen server DHCP ora kasedhiya, controller bisa disambungake menyang komputer nggunakake kabel silang kepasang langsung menyang port Ethernet. Ing kasus iki, alamat TCP/IP komputer kudu diowahi kanthi manual supaya kompatibel karo alamat standar pengontrol. Deleng TCP/IP Controller-Readme file kanggo rincian liyane.
- Bukak program browser Internet ing komputer lan ketik alamat TCP / IP standar controller menyang baris alamat browser Internet: 192.168.1.101 utawa alamat dinamis saka server DHCP. Deleng TCP/IP Controller-Readme file yen port tartamtu dibutuhake.
- Sawise sawetara wektu, kaca ngawasi standar kudu ditampilake. Yen browser ora mbukak kaca standar utawa nampilake data aktif, pangguna kudu mriksa konfigurasi "Pilihan" browser Internet. Deleng TCP/IP Controller-Readme file.
- Kaca Pemantauan lan Weker mung diwaca lan mulane ora perlu ngetik jeneng pangguna utawa sandhi. Jeneng pangguna lan sandhi bakal dijaluk nalika panyuwunan wiwitan kanggo sapa wae web kaca. Setelan standar pabrik yaiku:
Jeneng panganggo: Emerson
Sandi: 12
- Setelan gawan bisa diowahi ing kaca konfigurasi Tampilan.
- Pencet tab ing sisih ndhuwur kaca Pemantauan kanthi ngeklik kiwa tombol mouse kanggo ngetik masing-masing web kaca.
- Parameter bakal digambarake ing teks nyata bebarengan karo kode program kaya sing ditegesake ing dhaptar parameter ing ngisor iki.
Sawise paramèter wis diowahi, dhaptar lengkap setelan bisa disimpen ing memori komputer lan digunakake mengko kanggo ngunggah menyang controller liyane. Iki bisa ngirit wektu akeh nalika nggunakake macem-macem pengontrol lan sajrone sawetara wektu, perpustakaan bisa digawe ngemot dhaptar parameter kanggo peralatan kanggo macem-macem aplikasi.
Sampeyan uga bisa nampilake data grafis langsung saka controller. Kajaba iku, log permanen 30 dina file ngemot suhu kontrol ing 15 interval menit disimpen ing memori non-molah malih mengko ditransfer nggunakake FTP kanggo komputer. Log file bisa diimpor menyang program spreadsheet standar kayata Excel. Deleng TCP/IP Controller-Readme file kanggo gambaran lengkap fitur kasedhiya kanggo TCP / seri IP pengontrol.
Emerson Climate Technologies GmbH www.kesmasi.eu Am Borsigturm 31 I 13507 Berlin I Jerman Tanggal: 13.06.2016 EC2-352_OI_DE_R07_864925.doc
FAQ
Ing endi bisa nggoleki informasi sing luwih rinci babagan pengontrol EC2-352?
Informasi sing luwih rinci bisa ditemokake ing Manual pangguna.
Dokumen / Sumber Daya
![]() |
EMERSON EC2-352 Tampilan Case lan Coldroom Controller [pdf] Manual pangguna EC2-352 Display Case lan Coldroom Controller, EC2-352, Tampilan Case lan Coldroom Controller, Case lan Coldroom Controller, Coldroom Controller, Controller |