Philips Dynalite DR2PE Revolution Series Button Panel
Installation Instructions
Safety and Installation Requirements
Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
Environmental Conditions:
- Operating Temperature: 0° C (32° F) to 45° C (113° F)
- Humidity: ≤ 90%
Product Dimensions and Cutout
The button panel unit has dimensions of 89 mm (3.50 in) width and height, with a depth of 31 mm (1.22 in). The required wall cutout diameter is Ø 60 mm (2.36 in).
Note: The diagram indicates a quantity of 2 units (X 2) may be relevant for certain configurations.
Tools and Components
Required tools for installation typically include screwdrivers, pliers, a wire stripper, and a measuring tape.
The package may include mounting hardware, indicated by 'X 2' in one diagram.
Electrical Specifications and Wiring
The device operates on a SELV/Class 2 (UL) power source, requiring 12 V ⎓ 20 mA, with a maximum current draw of ≤ 2 A.
It utilizes the RS-485 DyNet communication protocol. Wiring terminals are labeled:
- SHLD (Shield)
- GND (Ground)
- D+ (Data Positive)
- D- (Data Negative)
- +V (Positive Voltage)
Suitable wire gauge is 0.3-2.5mm² (22-12 AWG). Ensure connections are torqued to 0.4 Nm (3.5 Lb-in).
Warning: Do not connect inputs to mains power. ⚡
Mounting and Installation Steps
The installation involves mounting the button panel unit into a prepared wall cutout and connecting it to the electrical system and communication network. Diagrams show the unit being fitted into a wall plate and connected to a wall box.
Specific terminal labels on the back of the unit include PLAN, 000001, 000002, and 000006, likely for configuration or identification.
Regulatory Compliance and Certifications
IEC Standards: The device complies with IEC Pollution Degree II and IEC Overvoltage Category III.
FCC Compliance: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. It generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with instructions, it may cause harmful interference to radio communications. Users are encouraged to correct interference by reorienting/relocating the receiving antenna, increasing separation, or connecting to a different circuit. Modifications not approved by the manufacturer may void the user's authority to operate the device.
Canadian Compliance: This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B).
Certifications: CE, UK CA, FC [FCC logo placeholder] ? [Global/Eco placeholder]