Schneider Electric RE17RAMU

Schneider Electric Harmony RE17R Timing Relay User Manual

Model: RE17RAMU

Introduction

This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Schneider Electric Harmony RE17R Timing Relay. This dual-function timing relay offers precise control over operations, ensuring devices and circuits function in a coordinated manner. It is designed for integration into hard-wired logic schematics and is suitable for various industrial automation, HVAC systems, and other applications requiring precise timing control.

The RE17R relay features a compact 17.5mm width, allowing for flexible DIN rail installation, and offers simple, precise settings via rotary trimmers. It includes a diagnostic button for quick circuit checks and supports both on-delay and pause timing functions.

Safety Information

Always observe the following safety precautions to prevent personal injury or damage to the equipment:

  • Installation and maintenance should only be performed by qualified personnel.
  • Disconnect all power before working on the device or connected circuits.
  • Ensure proper grounding to prevent electrical shock.
  • Verify that the supply voltage and current ratings match the device specifications.
  • Do not operate the device if it is damaged or malfunctioning.

Setup and Installation

The Harmony RE17R timing relay is designed for easy installation on a DIN rail.

Mounting

The relay's slim 17.5mm form-factor allows it to be mounted on a standard DIN rail, occupying the same space as a modular 1-pole DIN device. Ensure the DIN rail is securely fastened in a suitable enclosure.

Side view of Schneider Electric Harmony RE17R Timing Relay mounted on a DIN rail

Figure 1: Side view of the RE17R relay, illustrating its DIN rail mounting capability.

Wiring

The relay supports both screw and spring terminals for adaptable wiring. Refer to the terminal markings on the device for correct connections.

  • Power Supply (A1, A2): Connect the appropriate 24 V DC or 24-240 V AC/DC power supply to terminals A1 and A2.
  • Control Input (Y1): For specific timing functions (e.g., pause, summation), connect the control signal to terminal Y1.
  • Output Contacts (15, 16, 18): The relay features 1 changeover contact SPDT (Single Pole Double Throw).
    • Terminal 15: Common contact
    • Terminal 16: Normally Closed (NC) contact
    • Terminal 18: Normally Open (NO) contact
Front view of Schneider Electric Harmony RE17R Timing Relay showing terminals A1, 15, Y1, 18, 16, A2

Figure 2: Front view of the RE17R relay, highlighting the terminal connections for power, control, and output.

Operating Instructions

The Harmony RE17R offers dual timing functions and precise time setting capabilities.

Time Setting

The timing relay can be set for delays ranging from 0.1 seconds to 100 hours using the rotary trimmers on the front panel. The sealable cover helps secure the settings once configured.

  • Time Range Selection: Use the upper rotary switch to select the desired time range (e.g., 0.1s-1s, 1s-10s, 1h-10h, 10h-100h).
  • Time Value Adjustment: Use the lower rotary switch to fine-tune the specific time value within the selected range.
Timing diagram showing input signal U and output relay R1 with a time delay T

Figure 3: Example timing diagram illustrating the delay (T) between an input signal (U) and the relay output (R1).

Diagnostic Button

An instant diagnostic button is built into the device. Pressing this button allows for quick checks of downstream circuits, which can significantly reduce troubleshooting time during installation or maintenance.

Dual Functionality

The RE17R supports dual functions, including on-delay and pause timing, as well as summation control signals. Consult the specific wiring diagrams for your application to utilize these advanced features.

Maintenance

The Schneider Electric Harmony RE17R Timing Relay is designed for reliable operation with minimal maintenance. However, periodic checks can ensure optimal performance and longevity.

  • Visual Inspection: Regularly inspect the relay for any signs of physical damage, discoloration, or loose connections.
  • Terminal Tightness: Periodically check that all terminal connections are secure. Loose connections can lead to overheating or intermittent operation.
  • Cleaning: If necessary, gently clean the exterior of the relay with a dry, soft cloth. Do not use abrasive cleaners or solvents.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature failure.

Always disconnect power before performing any maintenance tasks.

Troubleshooting

If the Harmony RE17R timing relay is not functioning as expected, consider the following common issues and solutions:

ProblemPossible CauseSolution
Relay does not energizeNo power supply; incorrect wiring; faulty relayCheck power connections (A1, A2); verify supply voltage; inspect wiring for errors; test relay with known good power source.
Incorrect timing delayIncorrect time range or value setting; control signal issueAdjust rotary trimmers to the desired time range and value; verify control signal (Y1) is applied correctly.
Output contacts not switchingOverload; faulty contacts; incorrect load wiringCheck load current against 8A rating; verify wiring to contacts (15, 16, 18); use diagnostic button to check downstream circuit.
Diagnostic button no responseInternal fault; no power to relayEnsure relay is powered; if power is present and button still unresponsive, the unit may require replacement.

If problems persist after attempting these solutions, contact Schneider Electric technical support for further assistance.

Specifications

FeatureDetail
Model NumberRE17RAMU
BrandSchneider Electric
Timing Range0.1 seconds to 100 hours
FunctionsDual Function (On-delay, Pause), Summation Control
Supply Voltage24 V DC, 24 to 240 V AC/DC
Output Rating8 Amps
Contact Type1 Changeover Contact SPDT (Single Pole Double Throw)
Contact MaterialSilver Alloy
Mounting TypeDIN Rail Mount
Width17.5mm
Product Dimensions2.83 x 0.69 x 3.54 inches
Weight2.47 ounces
Connector TypeQuick Connect

Warranty and Support

For information regarding product warranty, technical support, or service, please refer to the official Schneider Electric website or contact their customer service department. Details can typically be found in the product packaging or on the manufacturer's website.

You can visit the Schneider Electric Store for more products and information.

Related Documents - RE17RAMU

Preview Schneider Electric Harmony Timer Relays RE22R2MMU Data Sheet
Detailed product data sheet for the Schneider Electric Harmony Timer Relay, model RE22R2MMU. Includes specifications, technical descriptions of functions, dimensions, wiring diagrams, environmental data, and ordering information.
Preview Schneider Electric RE22R2MYMR Multifunction Relay Technical Specifications
Detailed technical specifications, dimensions, and product information for the Schneider Electric RE22R2MYMR multifunction relay, featuring 8A DPDT output and 24-240V AC/DC input.
Preview Schneider Electric Harmony 3 Phase Control Relay RM17, RM22, RM35 Datasheet
Detailed datasheet for Schneider Electric Harmony 3-phase control relays (RM17, RM22, RM35 series). Covers product features, dimensions, safety information, installation, connection examples, setting examples, function diagrams, LED indications, and diagnostics.
Preview Schneider Electric RNF22R2MMW Timer Relay Technical Specification
Detailed technical specifications, functions, LED indications, wiring diagrams, and setup guide for the Schneider Electric RNF22R2MMW timer relay. This document covers various operational modes and electrical connections.
Preview Schneider Electric IH 24h Mechanical Time Switch Operating Instructions
Operating instructions for the Schneider Electric IH 24h mechanical time switch, covering installation, setting the time and switching times, technical data, and safety precautions.
Preview Schneider Electric A9A27003 Mounting Plate Installation Guide
Detailed instructions for installing the Schneider Electric A9A27003 mounting plate accessory for circuit breakers. Includes steps for DIN rail mounting, assembly, and surface installation, with torque values and dimensions. Compliant with installation regulations.