Beijer-logo

Beijer ELECTRONICS GT-4214 Analog Output Module

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module PRODUCT

About This Manual

This manual contains information on the software and hardware features of the Beijer Electronics High Speed Counter Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product.

Symbols Used in This Manual
This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information. The corresponding symbols should be interpreted as follows:

WARNING
The Warning icon indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury, and major damage to the product.

CAUTION
The Caution icon indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury, and moderate damage to the product.

NOTE
The Note icon alerts the reader to relevant facts and conditions.

IMPORTANT
The Important icon highlights important information

Safety

Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions!
In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product.
The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.

Product Certifications
The product has the following product certifications.

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (2)

General Safety Requirements

WARNING

  • Do not assemble the products and wires with power connected to the system. Doing so cause an “arc flash”, which can result in unexpected dangerous events (burns, fire, flying objects, blast pressure, sound blast, heat).
  • Do not touch terminal blocks or IO modules when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
  • Never let external metallic objects touch the product when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
  • Do not place the product near inflammable material. Doing so may cause a fire.
  • All wiring work should be performed by an electrical engineer.
  • When handling the modules, ensure that all persons, the workplace and the packing are well grounded. Avoid touching conductive components, the modules contain electronic components that may be destroyed by electrostatic discharge.

CAUTION

  • Never use the product in environments with temperature over 60℃. Avoid placing the product in direct sunlight.
  • Never use the product in environments with over 90% humidity.
  • Always use the product in environments with pollution degree 1 or 2.
  • Use standard cables for wiring.

About the G-series System

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (3)System overview

  • Network Adapter Module – The network adapter module forms the link between the field bus and the field devices with the expansion modules. The connection to different field bus systems can be established by each of the corresponding network adapter module, e.g., for MODBUS TCP, Ethernet IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc.
  • Expansion Module – Expansion module types: Digital IO, Analog IO, and Special modules.
  • Messaging – The system uses two types of messaging: Service messaging and IO messaging.

IO Process Data Mapping
An expansion module has three types of data: IO data, configuration parameter, and memory register. The data exchange between the network adapter and the expansion modules is made via IO process image data by internal protocol.Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (4)

Data flow between network adapter (63 slots) and expansion modules
The input and output image data depend on the slot position and the data type of the expansion slot. The ordering of input and output process image data is based on the expansion slot position. Calculations for this arrangement are included in the manuals for network adapter and programmable IO modules.
Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data.

Specifications

Environmental Specifications

Operating temperature -20°C – 60°C
UL temperature -20°C – 60°C
Storage temperature -40°C – 85°C
Relative humidity 5% – 90% non-condensing
Mounting DIN rail
Shock operating IEC 60068-2-27 (15G)
Vibration resistance IEC 60068-2-6 (4 g)
Industrial emissions EN 61000-6-4: 2019
Industrial immunity EN 61000-6-2: 2019
Installation position Vertical and horizontal
Product certifications CE, FCC, UL, cUL

General Specifications

Power dissipation Max. 70 mA @ 5 VDC
Isolation I/O to logic: Photocoupler isolation
UL field power Supply voltage: 24 VDC nominal, Class 2
Field power Not used. Field power bypass to next expansion module
Wiring IO cable max. 2.0 mm² (AWG 14)
Torque 0.8 Nm (7 Ib-in)
Weight 60 g
Module size 12 mm x 99 mm x 70 mm

DimensionsBeijer-ELECTRONICS-GT-4214-Analog-Output-Module (5)

Wiring Diagram

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (6)

Pin no. Signal description
0 Analog output channel 0
1 Analog output channel 1
2 Analog output channel 2
3 Analog output channel 3
4 Output channel common (AGND)
5 Output channel common (AGND)
6 Output channel common (AGND)
7 Output channel common (AGND)
8 Frame ground
9 Frame ground

LED Indicator

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (7)

LED no. LED function / description LED color
0 OUTPUT channel 0 Green
1 OUTPUT channel 1 Green
2 OUTPUT channel 2 Green
3 OUTPUT channel 3 Green

LED Channel Status

Status LED Indication
Normal operation Green Normal operation
Field power error All channels repeat green and off Field power is unconnected

Data Value / Current

Current range: 4 – 20 mA

Current 4.0 mA 8.0 mA 12.0 mA 20.0 mA
Data(Hex) H0000 H0400 H0800 H0FFF

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (8)

Mapping Data From the Image Table

Output image value

Bit no. Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0 Analog output Ch 0 low byte
Byte 1 Analog output Ch 0 high byte
Byte 2 Analog output Ch 1 low byte
Byte 3 Analog output Ch 1 high byte
Byte 4 Analog output Ch 2 low byte
Byte 5 Analog output Ch 2 high byte
Byte 6 Analog output Ch 3 low byte
Byte 7 Analog output Ch 3 high byte

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (9)Output module data – 8 byte output data

Analog output Ch 0
Analog output Ch 1
Analog output Ch 2
Analog output Ch 3

Parameter Data

Valid parameter length: 4 bytes

Bit no. Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0 Fault action for channel 3 Fault action for channel 2 Fault action for channel 1 Fault action for channel 0
00: Fault value / 01: Hold last state / 10: Low limit / 11: High limit
Byte 1 Not used
Byte 2 Fault value low byte
Byte 3 Not used Fault value high byte

Hardware Setup

CAUTION

  • Always read this chapter before installing the module!
  • Hot surface! The surface of the housing can become hot during operation. If the device is used in high ambient temperatures, always let the device cool down before touching it.
  • Working on energized devices can damage the equipment! Always turn off the power supply before working on the device.

Space Requirements
The following drawings show the space requirements when installing the G-series modules. The spacing creates space for ventilation, and prevents conducted electromagnetic interference from influencing the operation. Installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion.

CAUTION
NOT following the space requirements may result in damaging the product.

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (10)Mount Module to DIN Rail
The following chapters describe how to mount the module to the DIN rail.

CAUTION
The module must be fixed to the DIN rail with the locking levers.

Mount GL-9XXX or GT-XXXX Module
The following instructions apply to these module types:

  • GL-9XXX
  • GT-1XXX
  • GT-2XXX
  • GT-3XXX
  • GT-4XXX
  • GT-5XXX
  • GT-7XXX
  • GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module.Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (11)

Mount GN-9XXX Module
To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructionBeijer-ELECTRONICS-GT-4214-Analog-Output-Module (12)Mount Removable Terminal Block
To mount or dismount a removable terminal block (RTB), see the instructions below.Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (13)

Connect Cables to Removable Terminal Block
To connect/disconnect cables to/from the removable terminal block (RTB), see the instructions below.

WARNING
Always use the recommended supply voltage and frequency to prevent damage to the equipment and ensure optimal performance.

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (14)Field Power and Data Pins
Communication between the G-series network adapter and the expansion module, as well as system / field power supply of the bus modules is carried out via the internal bus. It is comprised of 2 Field Power Pins and 6 Data Pins.

WARNING
Do not touch the data and field power pins! Touching can result in soiling and damage by ESD noise.

Beijer-ELECTRONICS-GT-4214-Analog-Output-Module (1)

Pin no. Name Description
P1 System VCC System supply voltage (5 VDC)
P2 System GND System ground
P3 Token output Token output port of processor module
P4 Serial output Transmitter output port of processor module
P5 Serial input Receiver input port of processor module
P6 Reserved Reserved for bypass token
P7 Field GND Field ground
P8 Field VCC Field supply voltage (24 VDC)