ScanLog (Pen Drive)
4 / 8 / 16 Channel Recorder + Pen-Drive Interface
Operation Manual
ScanLog 16 Channel Recorder and Pen-Drive Interface
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
OPERATOR PARAMETERS
Parameters | Settings |
Stop Copy | No Yes |
Select Option | 1. None 2. Copy (New) 3. Re-copy (Old) 4. Read Chan Names 5. Recover (Default : None) |
Batch Start | No Yes |
Balance Slot Time | Read Only |
Batch Stop | No Yes |
ALARM SETTINGS
Parameters | Settings (Default Value) |
Select Channel | Pen Drive Version For 4C : Channel-1 to Channel-4 For 8C : Channel-1 to Channel-8 For 16C : Channel-1 to Channel-16 |
Select Alarm | AL1, AL2, AL3, AL4 (The actual available options depends on the numbers of Alarms set per channel on Alarm configuration page) |
AL1 Type | None Process Low Process High (Default : None) |
AL1 Setpoint | Min. to Max. of selected input type range (Default : 0) |
AL1 Hysteresis | 1 to 30000 (Default : 20) |
AL1 Inhibit | No Yes (Default : No) |
DEVICE CONFIGURATION
Parameters | Settings (Default Value) |
Delete Records | No Yes
(Default : No) |
CHANNEL CONFIGURATION
Parameters | Settings (Default Value) | ||||||||||||||||||||||||
All Chan Common | No Yes (Default : No) | ||||||||||||||||||||||||
Select Channel | Pen Drive Version For 4C : Channel-1 to Channel-4 For 8C : Channel-1 to Channel-8 For 16C : Channel-1 to Channel-16 | ||||||||||||||||||||||||
Parameters | Settings (Default Value) | ||||||||||||||||||||||||
Input Type | Refer Table 1 (Default : 0 to 10 V) | ||||||||||||||||||||||||
Resolution | Refer Table 1 | ||||||||||||||||||||||||
Signal Low |
| ||||||||||||||||||||||||
Signal High |
| ||||||||||||||||||||||||
Range Low | -30000 to +30000 (Default : 0) | ||||||||||||||||||||||||
Range High | -30000 to +30000 (Default : 1000) | ||||||||||||||||||||||||
Low Clipping | Disable Enable (Default : Disable) | ||||||||||||||||||||||||
Low Clip Val | -30000 to High Clip Val (Default : 0) | ||||||||||||||||||||||||
High Clipping | Disable Enable (Default : Disable) | ||||||||||||||||||||||||
High Clip Val | Low Clip Val to 30000 (Default : 1000) | ||||||||||||||||||||||||
Zero Offset | -30000 to +30000 (Default : 0) |
ALARM CONFIGURATION
Parameters | Settings (Default Value) |
Alarms/chan | 1 to 4 (Default : 4) |
RECORDER CONFIGURATION
Parameters | Settings (Default Value) |
Normal Interval | 0:00:00 (H:MM:SS) to 2:30:00 (H:MM:SS) (Default : 0:00:30) |
Zoom Interval | 0:00:00 (H:MM:SS) to 2:30:00 (H:MM:SS) (Default : 0:00:10) |
Alrm Toggl Rec | Disable Enable (Default : Enable) |
Recording Mode | Continuous Batch (Default : Continuous) |
Batch Time | 0:01 (HH:MM) to 250:00 (HHH:MM) (Default : 1:00) |
Batch Start Batch Stop | No Yes |
RTC SETTING
Parameters | Settings |
Time (HH:MM) | 0.0 to 23:59 |
Date | 1 to 31 |
Month | 1 to 12 |
Year | 2000 to 2099 |
Unique ID Number | Read Only |
UTILITIES
Parameters | Settings (Default Value) |
Lock Unlock | No Yes (Default : No) |
Factory Default | No Yes (Default : No) |
TABLE 1 | ||
Option | Range (Min. to Max.) | Resolution & Unit |
Type J (Fe-K) | 0.0 to +960.0°C | 1 °C or 0.1 °C |
Type K (Cr-Al) | -200.0 to +1376.0°C | |
Type T (Cu-Con) | -200.0 to +387.0°C | |
Type R (Rh-13%) | 0.0 to +1771.0°C | |
Type S (Rh-10%) | 0.0 to +1768.0°C | |
Type B | 0.0 to +1826.0°C | |
Type N | 0.0 to +1314.0°C | |
Reserved for customer specific Thermocouple type not listed above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type. | ||
RTD Pt100 | -199.9 to +600.0°C | 1°C or 0.1 °C |
0 to 20 mA | -30000 to 30000 units | 1 0.1 0.01 0.001 units |
4 to 20 mA | ||
0 to 80 mV | ||
Reserved | ||
0 to 1.25 V | -30000 to 30000 units | |
0 to 5 V | ||
0 to 10 V | ||
1 to 5 V |
FRONT PANEL KEYS
FRONT PANEL KEYS | ||
Symbol | Key | Function |
![]() | Scroll | Press to scroll through various Process Information Screens in Normal Operation Mode. |
Alarm Acknowledge | Press to acknowledge / mute alarm output (if active) & to view Alarm Status screen. | |
![]() | DOWN | Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change. |
![]() | UP | Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change. |
![]() | SET-UP | Press to enter or exit set-up mode. |
![]() | ENTER | In Run Mode, press to toggle between Auto & Manual Scan Mode. (Only for 16 Channel version) In Set-up Mode, press to store the set parameter value and to scroll to the next parameter. |
SCROLLING THROUGH VARIOUS SCREENS
The screen shown below are for 4 Channel Version. The sequence is the same for 8 & 16 Channel Version.
VIEWING ALARM STATUS SCREEN
16 Channel With Alarm Relay Outputs
ELECTRICAL CONNECTIONS