SVI 2xxx Commissioning Instructions
1 Information about this document
This document supplements the SVA/SVI locks' assembly instructions and contains technical information for the mounting and commissioning of a SVI 2xxxF lock.
1.2 Target group
The locks may only be mounted by technical specialists who have been trained for this purpose by dormakaba.
1.3 Other applicable documents
- SVA/SVI locks assembly instructions
- Manual for the connecting cable SVP-A 1100/2100
- Technical documents for the selected control unit
- Commissioning instructions for the SVA lock
- Bolt contact switch SVA/SVI assembly instructions
- Assembly instructions for the fittings used, e.g. door handles, panic bar or knob.
1.4 Abbreviations
Term | Description |
---|---|
SVA | Active, self-locking (anti-)panic lock for the active door leaf in 2-leaf door units |
SVI | Inactive, self-locking (anti-)panic lock for the passive door leaf in 2-leaf door units |
2xxx/2xxxF | All versions of a lock; the exact lock type is marked with 3 digits instead of xxx. |
G | Active door leaf |
S | Passive door leaf |
1.5 Symbols used
1.5.1 Hazard categories
[WARNING] This signal word indicates a possible hazardous situation that may result in death or serious injury if not averted.
[ATTENTION] This signal word indicates a possible hazardous situation that may result in damage to property or the environment if not averted.
1.5.2 More symbols
[NOTE] This signal word indicates useful information for efficient and trouble-free operation.
[Item number] Item numbers used in image caption
2 Safety
2.1 Intended use
The SVI 2xxxF is a motor lock for the passive door leaf on 2-leaf door units. The door unit's active door leaf must be equipped with a dormakaba SVA 2xxx or SVA 2xxxF lock.
- Only use the components approved by dormakaba for mounting.
- Only mount combinations of lock and fitting that have been tested and approved in accordance with EN 179 or EN 1125. The list of approved components can be found in the constancy of performance certificate at www.dormakaba.com. Other combinations on request.
- Mounting on fire and smoke protection doors is only permitted if the usability certificates for these doors provide for this mounting and if the requirements are followed.
- The SVI 2xxxF is suitable for use on fire and smoke protection doors.
2.2 Non-intended use
- The lock must not be opened by third parties. If the lock is opened by a third party, there is a risk that safety-relevant functions (e.g. escape/panic functions) will no longer exist.
- The identification plate on the lock contains important information required by law and must not be damaged or obscured.
2.3 Reasonably foreseeable misuse
- Cannot be combined with SVP locks.
- Do not make any changes to the door unit that are not described in this manual.
- If door seals (e.g. profile seals, floor seals) are used, they must not impede the intended function.
3 Product description
The SVI lock on the passive door leaf serves as a strike box for the SVA lock. The SVI lock locks automatically by extending the espagnolette bolt as soon as the passive door leaf is closed. In case of emergency, the door can be opened in the escape direction at any time. The SVI 2xxxF can query the status of the espagnolette bolt and the door handle/panic bar. The SVI 2xxxF contains an integrated Power Reserve module. The functions are controlled electronically. Control is via the control unit of the SVA 2xxx or SVA 2xxxF active door leaf lock.
Automatically opening installation example
Figure 1 illustrates a barrier-free installation situation. It shows an active door leaf [item 1] with an SVA 2xxx/2xxxF lock and a passive door leaf [item 2] with an SVI 2xxxF lock. A panic door fitting [item 3] is present. Cable transfer [item 4] connects the components, along with a connecting cable [item 5] to the operator and control unit [item 6]. Other components shown include sequential locking control [item 7], door contact [item 8], carry bar [item 9], and access control components [item 10].
3.1 Parts included
- SVI lock
- Forend (pre-mounted if necessary)
- Screws required for mounting
- Commissioning instructions SVI 2xxxF
3.2 Variants
Variants for rebated solid doors
235 x 20 mm with angled forend 12 mm, Rear backset: 33 mm
- SVI 2071F: Backset 65 mm, DIN left
- SVI 2072F: Backset 65 mm, DIN right
- SVI 2081F: Backset 80 mm, DIN left
- SVI 2082F: Backset 80 mm, DIN right
- SVI 2091F: Backset 100 mm, DIN left
- SVI 2092F: Backset 100 mm, DIN right
Variants for solid butt doors
235 x 24 with lipped or flat forend, Rear backset: 33 mm
- SVI 2077F: Backset 65 mm, DIN left/right
- SVI 2087F: Backset 80 mm, DIN left/right
- SVI 2097F: Backset 100 mm, DIN left/right
Variants for tubular frame doors
380 x 24 with lipped or flat forend, Rear backset: 15 mm
- SVI 2119F: Backset 35 mm, DIN left/right
- SVI 2129F: Backset 40 mm, DIN left/right
- SVI 2139F: Backset 45 mm, DIN left/right
- Further versions available on request
3.3 Door fittings required
Inner side of the door: Door handle or panic bar
Outer side of the door: without door fitting
Locking pin: 9 mm square for passive door leaf set (half pin)
3.4 Technical data
Parameter | Value |
---|---|
Temperature range | -25°C to +70°C |
Relative humidity | up to 95% at 55°C; no condensation |
Supply voltage | 24 V DC stabilized (+/-10%) |
Max. power consumption | 0.5 A |
Quiescent current consumption | 0.08 A |
Bolt contact's contact load capacity* | 0.5 A at max. 30 V DC |
"Locked" signal | output switches to GND, 30 mA at max. 30 V DC |
* only for special items
3.5 Integrated Power Reserve module
The integrated Power Reserve module is tested 5 mins after the power is turned on and then every 48 hrs. If the test completes with an error, the corresponding flashing code appears once according to the error messages (see Chapter 6). The test is then performed a second time after a further 5 minutes. If this test is also negative, the flashing code is permanently displayed.
3.6 LED display
With the SVI 2xxxF, colored light signals in the area around the latch holder indicate general operational readiness. In addition, the LED display shows the error messages (see Chapter 6).
Figure 2 shows LED displays in the latch holder. The table below details LED display, color, duration, cable color (SVP-A 1100/2100), and connection/function.
LED display
LED display | Color | Duration | Cable color (SVP-A 1100/2100) | Connection / function |
---|---|---|---|---|
Ready for operation | 2xxx s | Black | GND | |
Red | not in use | |||
White | +24 V DC | |||
Brown | not in use | |||
Violet | Locked, output switches to GND, 30 mA at max. 30 V DC | |||
Red-blue | not in use | |||
Blue | not in use | |||
Green | not in use | |||
Gray-pink | Bolt contact*2 | |||
Yellow | Bolt contact*2 | |||
Gray | RS485 N*1 | |||
Pink | RS485 P*1 |
*1 Only in combination with SVA 2xxx/SVA 2xxxF
*2 Optional, see bolt contact switch manual SVA/SVI, WN 059826
3.7 Classification
3.7.1 Tubular frame locks
Manufacturer | Product | Declaration Number | Standard | Classification | DOP |
---|---|---|---|---|---|
dormakaba Deutschland GmbH DORMA Platz 1 - 58256 Ennepetal | SVI 2xxxF RR | 0432-CPR-00026-11 | EN 179:2008 | 3 7 7 B 1 4 5 2 A C | 18 DOP_0166 |
SVI 2xxxF RR | 0432-CPR-00026-01 | EN 1125:2008 | 3 7 7 B 1 4 2 1/2 A/B C | 18 DOP_0167 |
3.7.2 Solid door locks
Manufacturer | Product | Declaration Number | Standard | Classification | DOP |
---|---|---|---|---|---|
dormakaba Deutschland GmbH DORMA Platz 1 - 58256 Ennepetal | SVI 2xxxF VB | 0432-CPR-00026-11 | EN 179:2008 | 3 7 7 B 1 4 5 2 AC | 18 DOP_0162 |
SVI 2xxxF VB | 0432-CPR-00026-02 | EN 1125:2008 | 3 7 7 B 1 4 2 1/2 A/B C | 18 DOP_0163 |
4 Pin assignment
[Note] For earthed door frames, the bridge on the SVP-A x100 connection cable's plug must be disconnected.
4.1 Block diagram SVI 2xxxF with SVA 2xxx
The diagram shows the SVI 2xxxF function with SVA 2xxx(F). It details the connections for SVA 2xxx/SVA 2xxxF and SVI 2xxxF. The connections include:
- Black: GND (3)
- Brown: not in use
- Pink/gray: not in use
- Red: not in use
- White: +24 V DC (1) (stabilized) (only in combination with SVI 2xxxF)
- Yellow: not in use
- Green: not in use
- Gray: RS485 N (only in combination with SVI 2xxxF)
- Pink: RS485 P (only in combination with SVI 2xxxF)
- Red/blue: not in use
- Blue: not in use
- Violet: "SVI locked" max. 30 mA Out
5 Mounting
See SVA/SVI assembly instructions.
Link to SVA/SVI assembly instructions: https://techdoc.dormakaba.com/cds/go/SVA-SVI
Link to SVA commissioning instructions: https://techdoc.dormakaba.com/cds/go/SVA
6 Error messages
LED display | Cause | Activity |
---|---|---|
●●●●●● | Voltage supply outside the tolerance range (24 V DC +/- 10%) | Check power supply unit. |
●●●●●● | Power reserve function test is faulty | Replace lock. |
●●●●●● | Unlocking/locking not successful | Test, bolt, or espagnolette bolts are blocked from outside the lock. If not, call dormakaba Service |
●●●●●● | General error | Disconnect and reactivate the power supply for the door. If the error persists, call dormakaba Service. |
●●●●●● | SVA-SVI bus connection interrupted | Check correct wiring, especially the wiring of the SVA and SVI lock. |
7 Disassembly and disposal
Disassembly is carried out in reverse order of the mounting instructions.
The product must not be disposed of in domestic waste.
Dispose of the product in an environmentally friendly manner at the arranged acceptance and collection points.
Refer to the statutory regulations for your country.