Instruction Manual for RAB models including: SR Series Field Adjustable Strip Lights, SR Series, Field Adjustable Strip Lights, Adjustable Strip Lights, Strip Lights, Lights

P-100266 SR - Strip LED FA Installation 0423

Installation Instructions

LED STRIP 2FT 19/14/10W 5000/4000/3500K JBOX ADAPTOR WHITE | Crescent Electric Supply Company

Instructions

SR Field-Adjustable Strip Lights - RAB Lighting


File Info : application/pdf, 8 Pages, 1.07MB

PDF preview unavailable. Download the PDF instead.

SR Field-Adjustable Strip Light Instructions 2
INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

SR2

SR4

SR8

IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. WARNING: Disconnect or turn OFF power at the electrical panel before installing or maintaining fixture. No User serviceable parts inside fixture. Suitable for damp locations. Suitable for operation in ambient not exceeding 50°C.

SURFACE MOUNTING
The fixture is suitable for indoor ceiling mounting, as follows:
1. Press and hold the Release Buttons (4) on both sides of the Fixture Housing to release the Lens (Fig. 1). When pressing the Release Buttons use one hand to hold the Lens and press the Release Buttons on both sides of the Fixture with the other hand. CAUTION: The Lens may drop out quickly. Lens is supported with (2) Tether Cables (Fig. 3).
2. Attach both Junction Box Cover Plates to the Fixture Housing by sliding in the direction of arrows as shown in Fig. 2. Secure with (2) Screws (provided).
3. Feed supply wires through Wire Access Hole. Secure Fixture Housing to the junction box or building structure per NEC Code (Fig. 3).
4. Make electrical connections as shown in wiring diagram (Fig. 14). Use approved wiring connectors and wire to local NEC codes. Push all wires back into Fixture Housing. Be careful not to pinch wires.
5. Snap Lens back into Fixture Housing and remove protective plastic from Lens.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to sharp objects.

Fig: 1

Fixture Housing

Lens
Fig: 2 Junction Box Cover Plates

Release Buttons (4) Screws (2)

Fig: 3 Fixture Housing

Wire Access Hole

Screws (4)

Tether Cables (2)

Lens

INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

V-HOOK / CHAIN MOUNTING
The fixture can be mounted using V-Hooks and Chain (ordered
separately, CAT# SR VHOOK KIT).
1. Loop the V-Hooks into the Mounting Slots to each end of the Fixture Housing as shown in Fig. 4.
2. Connect the Chains to the mounting surface and hang the Fixture from V-Hooks as shown in Fig. 5.
3. Fixture mounting height and spacing should be determined by application requirements. V-Hook and Chain is suitable to support four (4) times the weight of the Fixture.
4. Press and hold the Release Buttons (4) on both sides of the Fixture Housing to release the Lens (Fig. 1). When pressing the Release Buttons use one hand to hold the Lens and press the Release Buttons on both sides of the Fixture with the other hand. CAUTION: The Lens may drop out quickly. Lens is supported with (2) Tether Cables (Fig. 3).
5. Make electrical connections as shown in wiring diagram (Fig. 14). Use approved wiring connectors and suitable conduit (not provided). Wire to local NEC codes. Push all wires back into Fixture Housing. Be careful not to pinch wires.
6. Snap Lens back into Fixture Housing and remove protective plastic from Lens.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to sharp objects.

Fig: 4

Mounting Slots

V-Hook

Chain

Fig: 5

V-Hook Mounting Surface

Chain

INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

CONTINUOUS RUN MOUNTING (multiple fixtures can be mounted together)

For Surface Mounting
(Multiple fixture wiring kit sold separately, CAT# SR JOIN KIT)
1. Press and hold the Release Buttons (4) on both sides of the Fixture Housing to release the Lens (Fig. 1). When pressing the Release Buttons use one hand to hold the Lens and press the Release Buttons on both sides of the Fixture with the other hand. CAUTION: The Lens may drop out quickly. Lens is supported with (2) Tether Cables (Fig. 3).
2. Use a screwdriver to open the Knockout Hole and install the Wire Guard (provided with Junction Box Cover Plates) to protect wires from sharp edges (Fig. 7).
3. Attach both Junction Box Cover Plates to the Fixture Housing by sliding in the direction of arrows as shown in Fig. 2. Secure with (4) Screws (provided). Only one Fixture needs to be electrically hardwired from above.
4. Feed supply wires through Wire Access Hole (Fig. 6). Secure Fixture Housing to junction box or building structure.
5. Make electrical connections as shown in wiring diagram (Fig. 14). Use approved wiring connectors and wire to local NEC codes. Push all wires back into Fixture Housing. Be careful not to pinch wires.
6. Snap Lens back into Fixture Housing and remove protective plastic from Lens.
CAUTION: The maximum number of fixtures allowed to be linked together is indicated in the table below (Fig. 9).
WARNING: To prevent wiring damage or abrasion, do not
expose wiring to sharp objects.

For V-Hook/Chain Mounting
(Multiple fixture wiring kit sold separately, CAT# SR JOIN KIT)
1. Use a screwdriver to open the Knockout Hole and install
the Wire Guard (provided with Junction Box Cover Plates) to protect wires from sharp edges (Fig. 7).
2. Install Joiner Bracket to connect multiple fixtures together and secure with (8) Screws (Fig. 8).
3. Connect the Chains to the mounting surface and hang Fixture from the V-Hooks as shown in Fig. 5
4. Fixture mounting height and spacing should be determined by application requirements. V-Hook and Chain is suitable to support four (4) times the weight of the fixture.
5. Press and hold the Release Buttons (4) on both sides of the Fixture Housing to release the Lens (Fig. 1). When pressing the Release Buttons use one hand to hold the Lens and press the Release Buttons on both sides of the Fixture with the other hand. CAUTION: The Lens may drop out quickly. Lens is supported with (2) Tether Cables (Fig. 3).
6. Make electrical connections as shown in wiring diagram (Fig. 14). Use approved wiring connectors and suitable conduit (not provided). Wire to local NEC codes. Be careful not to pinch wires.
7. Snap Lens back into Fixture Housing and remove protective plastic from Lens.
CAUTION: The maximum number of fixtures allowed to be linked together is indicated in the table below (Fig. 9).
WARNING: To prevent wiring damage or abrasion, do not
expose wiring to sharp objects.

Fig: 6

Fig: 8

Fig: 7

Wire Guard

Joiner Bracket

Fig: 9
Catalog # SR2 SR4 SR8

Maximum Number of Linked Fixtures Up to 27 fixtures Up to 13 fixtures Up to 9 fixtures

INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

FIELD ADJUSTMENT
Follow instructions below to change the Fixture Power (W) and/or Color Temperature (CCT) from factory settings:

Factory Settings:
SR2 19/14/10W SR4 40/30/20W SR4L 28/21/14W SR8 60/50/40W SR8H 85/75/54W

19W / 4000K 40W / 4000K 28W / 4000K 60W / 4000K 85W / 4000K

1. Locate the Field Adjustable Switches on the side of Fixture Housing as shown in Fig. 10.
2. Select Power (W) and Color Temperature (CCT) by sliding respective switch to the desired value (Fig. 10).

Fig: 10
e

40W 30W 20W

5000K 4000K 3500K

Power (W)
Color Temperature (CCT)

SR VHOOK ACCESSORY KIT
SR VHOOK Kit includes the following:
· 40" Chain (2) · V-Hooks (2)

SR JOIN ACCESSORY KIT

SR JOIN Kit includes the following:

· Joiner Bracket w/ 8 Screws

· Nuts (12)

· Wires (12 - Tinned copper)

0-10V DIMMABLE WIRING
RISK OF FIRE. Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. For 0-10V dimming follow the wiring directions as shown in Fig. 11.
1. Connect the black fixture lead to the LINE supply lead.
2. Connect the white fixture lead to the COMMON supply lead.
3. Connect the green GROUND wire from fixture to supply ground.
4. Connect the purple fixture lead to the (V+) DIM lead.
5. Connect the pink fixture lead to the (V-) DIM lead.
6. Cap the yellow fixture lead, if present. Do NOT connect.

Fig. 11

LINE COMMON ( + ) DIMV ( - ) DIMV

GROUND

BLACK
WHITE PURPLE PINK Vaux 12V
RED
GROUND

LIGHT FIXTURE

PIR MODELS (External)

Screw Sensor Head onto the Bracket (RAAS) as shown in Fig. 12. See factory settings below (optional remote sold separately for custom
settings, CAT# MSR1).

Factory Settings:
· Brightness: 100% · Hold Time: 1 Minute · Daylight: Disabled

· Sensitivity: 100% · Stand-by dimming level: 20% · Stand-by time: 1 Minute

Bracket (RAAS)

Sensor Head

Fig. 12

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

MVS MODELS (Internal)

(optional remote sold separately for custom settings, CAT# MSR1).

Factory Settings:
· Brightness: 100% · Hold Time: 1 Minute · Daylight: Disabled

· Sensitivity: 100% · Stand-by dimming level: 20% · Stand-by time: 1 Minute

INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

LIGHTCLOUD® BLUE MVS & PIR MODELS
This is a 12V low voltage controller with an integrated occupancy sensor. Screw the Sensor Head onto the Bracket (RAAS) as shown
Factory Settings: Uncommissioned State
· Motion Sensitivity: High · Brightness when triggered: 100% · Hold time: 1 Minute · Standby to dim: 20% · Stand-by time: 1 Minute
Factory Settings: Commissioned State
· Motion Sensitivity: High · Brightness when triggered: Last on status · Hold time: 20 Minutes · When vacant: Off
CONTROLLING LIGHTCLOUD BLUE DEVICE
1. Confirm your device is powered on. 2. Download the Lightcloud Blue app from the Apple® App
store or Google PlayTM store. 3. Launch the App and create an account or login. 4. Tap the "add device" icon in the app to start connecting
devices. 5. Follow the remaining steps in the app. Create Areas and
Groups and add Scenes to organize and control your devices.

ENABLE DEVICE PAIRING MODE
If your Lightcloud Blue Low Voltage Controller+Sensor is already paired there are various options to choose from to return the device to the default factory settings.
Method 1: Delete from the App Open the app and access the device settings for the paired device. Be sure that the device is online with a strong connection and select `Delete'. The fixture will flash 3x, then reset to 100% brightness.
Method 2: Rapid Reset Tool The Rapid Reset process must be done by a professional electrician qualified by RAB. Reach out to your RAB sales manager to request a Rapid Reset Tool. The tool simply needs to be placed directly on the side of the device for 2s or until the fixture flashes 3x, then resets to 100% brightness.
Bumps
Fig:13
BRACKET RAAS INSTALLATION
Connect the Low Voltage Controller/Sensor to the Bracket (RAAS): Unscrew the 1/2" knockout on the Bracket (RAAS) with a screwdriver and screw on the Low Voltage Controller/Sensor. Connect the Bracket (RAAS) to a 1/2" knockout on a compatible fixture. Follow the wiring instructions as shown in Fig. 14.

TROUBLESHOOTING
1. Check that the line voltage at the fixture is correct. Refer to wiring diagram.
2. Be sure the fixture is grounded properly.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized. 1. Clean polycarbonate lens with non-abrasive cleaning solution. 2. Do not open the fixture to clean the LEDs. Do not touch the LEDs.

INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com
BRACKET RAAS WIRING DIAGRAM
Fig:14

INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com
BATTERY BACKUP MODELS

WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY. To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join BATTERY connector until installation is complete.
NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver. Reference Fig.15 for wiring diagram. For Battery Backup Modes with BRACKET (RAAS) reference wiring diagram as shown in Fig. 17.
CAUTION: Do not use any supply voltage other than 120-277V.
50/60 Hz.
1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
2. If using an UNSWITCHED circuit, connect UNSWITCHED and
SWITCHED lines together.
3. If using a SWITCHED circuit, connect SWITCHED HOT lead to the switch.
4. For 0-10V dimming, connect DIM (+) purple and DIM (-) pink leads to 0-10V dimming connection.
5. All unused leads must be capped and insulated.
6. When power is on, the fixture should be on and the CHARGING INDICATOR LIGHT should illuminate to indicate the battery is
charging.
7. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button as shown in Fig. 16.
8. After the battery has charged for 24 hours, a long duration test can be performed by disconnecting power to the fixture.

OPERATION
1. When AC power is applied the charging indicator light is illuminated indicating that the BATTERY is being charged.
2. When power fails the standby power automatically switches to emergency power (internal battery) operating at reduced illumination.
3. When AC power is restored the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
3. Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
1. Be sure the fixture is grounded properly. 2. If the charging indicator light does not illuminate after pressing
and releasing the Test Button (Fig. 16), check power and check if battery is connected properly.

Purple/DIM+ Pink/DIM­

FIG. 16

LIGHT FIXTURE
FIG. 15

Black/Switched Line Red/Unswitched Line
White/Neutral Green/Ground WIRING DIAGRAM

SR2 Test Button

SR4 Test Button

SR8 Test Button

© 2023 RAB LIGHTING Inc.
SR - IN - 0423 P-100266

Easy Answers

rablighting.com Visit our website for product info

Tech Help Line Call our experts: 888 722-1000

e-mail Answered promptly - sales@rablighting.com

RAB WARRANTY: RAB's warranty is subject to all terms and conditions found at rablighting.com/warranty

Free Lighting Layouts Answered online or by request

INSTRUCTIONS
FIELD-ADJUSTABLE SRTM INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com
BRACKET (RAAS) WITH BATTERY BACKUP INSTALLATION
Fig:17
SENSOR



References

Adobe PDF Library 17.0 Adobe InDesign 18.2 (Windows)