TECH LE-3x230mb DIN Rail Energy Meter

Manufacturer: TECH Sterowniki II Sp. z o.o.

Address: ul. Biała Droga 31, 34-122 Wieprz

Certifications: UK CA, EAC, CE

Product Description

The LE-3x230mb energy meter is designed for mounting on a standard DIN rail (TH-35). It utilizes advanced integrated circuits for energy measurement, digital sample processing, and SMT technology to accurately display the user's actual energy consumption. The LE-3x230mb is a certified energy meter.

Installation and Wiring

Wiring Mode

Three phase four wire direct connection.

Signal Terminal Wiring Diagram

This diagram shows the signal terminal connections for communication and energy pulse output. The communication section includes terminals for RS485 (labeled A, B, 58, 59) and RS232, with a connection for a PC. The energy pulse output section has terminals AP (47, 48).

Device Description

The front panel of the device features an LCD display interface, an energy pulse indication light, user-programmable buttons, and a section for displaying parameters.

Dimensions and Assembly

The LE-3x230mb meter has a width of 72mm, a height of 90mm, and a depth of 45.2mm. It is designed for standard 35mm DIN rail mounting.

Display Overview

DIN-rail mounted energy meters like the LE-3x230mb display measured data including voltage, current, power, power factor, frequency, and energy consumption. Users can switch between different display interfaces by pressing the ◀️ and ▶️ buttons simultaneously.

Energy and Electrical Variables

Display Value (Example)DescriptionDisplay Value (Example)Description
EP = 780.62 kWhImport active energy208.09 kWhTotal multi-rate energy under T1
EP- = -0.00 kWhExport active energy101.06 kWhTotal multi-rate energy under T2
EQ = 18.80 kvarhImport reactive energy382.23 kWhTotal multi-rate energy under T3
EQ- = -7.10 kvarhExport reactive energy89.24 kWhTotal multi-rate energy under T4
Ua = 220.1 VPhase voltage UaQa = 0.108 kvarPhase A reactive power
Ub = 220.2 VPhase voltage UbQb = 0.210 kvarPhase B reactive power
Uc = 220.0 VPhase voltage UcQc = 0.098 kvarPhase C reactive power
Uab = 381.3 VLine voltage UabQ = 0.416 kvarTotal reactive power
Ubc = 381.2 VLine voltage UbcSa = 2.218 kVAPhase A apparent power
Uca = 381.2 VLine voltage UcaSb = 2.207 kVAPhase B apparent power
Ia = 10.10 APhase A currentSc = 2.211 kVAPhase C apparent power
Ib = 10.20 APhase B currentS = 6.636 kVATotal apparent power
Ic = 11.00 APhase C currentPFa = 0.985Phase A power factor
Pa = 2.128 kWPhase A active powerPFb = 0.998Phase B power factor
Pb = 2.040 kWPhase B active powerPFc = 0.988Phase C power factor
Pc = 2.100 kWPhase C active powerPF = 1.000Total power factor
P = 6.267 kWTotal active powerF = 50.00 HzGrid frequency

Sinum System Integration

How to Register

To register the device in the Sinum system, connect it to the Sinum central device via the RS-485 connector. Log in to the Sinum central device via a web browser. Navigate to Settings ⚙️ > Devices > MODBUS devices > Add > Energy meter > Energy meter TECH LE-3x230mb. Configure the following parameters: Communication address: 2, Baud rate: 9600, Parity bit: E.B.1.

Programming Mode

Enter Programming Mode

To enter programming mode, press and hold the ◀️ button for more than 5 seconds when the meter reading is displayed. The screen will show Code. Press the ▶️ button to confirm entry. Enter the initial system password 0001 using the ◀️ and ▶️ buttons to change values and move to the next digit. Press the ▶️ button to confirm. If the password is correct, the settings menu will appear. An incorrect password will result in the display remaining unchanged.

Options Available

Exit Programming Mode

To exit programming mode, press ◀️ and ▶️ simultaneously. The meter will display SALE. Press the ▶️ button, and the meter will display SALE. To save changes, press the ▶️ button to change the status to SALE--YES and confirm by pressing the ▶️ button. To exit without saving, leave the status as is and confirm by pressing the ▶️ button.

Operation Process

The diagram illustrates the button presses for navigating the meter's functions. It shows sequences like pressing the ◀️ button for over 5 seconds, then pressing ▶️ to confirm, followed by sequences like < CYC < LI GH, < AP < 01 SP, < Code < Addr, < bAUd < DAŁA, and < DREA < SALE.

Energy Pulse Output

The energy pulse meter circuit diagram shows a Vcc power source (5V, 12V, or 24V) connected through a resistor (R) to an output terminal. The circuit also includes a capacitor (C) and another resistor (R).

Important Notes

? Do not touch the terminals when the meter is in operation.

? Read this operation instruction carefully and follow all instructions strictly for safe, correct, and efficient use.

? Ensure only qualified technicians perform installation and maintenance.

? Always use a properly rated voltage sensing device to confirm that all power is off before working.

? Connect cables according to the diagrams provided. Disconnecting or connecting the communication plug with power on, or incorrect connection order, may damage the device.

? This product must not be disposed of with household waste. Users are obliged to transfer used equipment to a collection point for recycling of all electric and electronic components.

Technical Data

ParameterValue
Rated voltage3×230/400V
Input current0.25-5 (63) A
Frequency50/60 Hz
Voltage range0.8Un – 1.2Un
Voltage circuit consumption< 4VA
Current circuit consumption< 1VA
Work temperature-25°C ÷ 70°C
Storage temperature-30°C ÷ 80°C
Relative humidity5 ÷ 95% (no condensation)
Accuracy class (voltage, current:)0.2 Class
Accuracy class (active energy)0.5S Class
Accuracy class (reactive energy)2 Class
CommunicationModbus-RTU protocol (RS-485)

EU Declaration of Conformity

Tech Sterowniki II Sp. z o.o., ul. Biała Droga 34, Wieprz (34-122) hereby declares under its sole responsibility that the LE-3x230mb energy meter is compliant with the following Directives: 2014/35/UE, 2014/30/UE, 2009/125/WE, 2017/2102/UE. For compliance assessment, harmonized standards were used, including EN 61010-1:2010+A1:2019, EN IEC 61010-2-030:2021+A11:2021, EN IEC 61326-1:2021, EN IEC 61000-3-2:2019+A1:2021, EN 61000-3-3:2013+A2:2021, and EN IEC 63000:2019 RoHS. Dated: Wieprz, 01.17.2024. Signed by Paweł Jura, Janusz Master (Prezesi firmy).

A QR code ? is provided for accessing the full text of the EU declaration of conformity and the user manual online at www.tech-controllers.com/manuals.

Models: LE-3x230mb Energy Meter, LE-3x230mb, Energy Meter, Meter

File Info : application/pdf, 2 Pages, 2.43MB

PDF preview unavailable. Download the PDF instead.

licznik-energii en

References

Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Windows)

Related Documents

Preview TECH EU-R-8b Plus Room Regulator User Manual and Warranty Information
Comprehensive guide to the TECH EU-R-8b Plus room regulator, covering installation, operation, features, warranty, safety, and technical specifications. Learn how to control your heating zones effectively.
Preview TECH STT-869 Wireless Electric Actuator User Manual and Warranty
Comprehensive user manual and warranty information for the TECH STT-869 wireless electric actuator, detailing installation, operation, troubleshooting, and technical specifications for efficient heating zone temperature management.
Preview Manual de Utilizare Controler Pompă TECH ST-21
Manual complet pentru controlerul de pompă TECH ST-21, oferind instrucțiuni detaliate despre operare, instalare, setări, specificații tehnice și siguranță.
Preview TECH EU-294 Room Regulator User Manual
User manual for the TECH EU-294 room regulator, detailing installation, operation, and safety guidelines for both EU-294 v1 and EU-294 v2 models.