R. STAHL LS Leitungsschutzschalter 8530/1-MCB-STA102-B10-000-2

Article Number: 293915

Product Overview

The R. STAHL 8530/1-MCB-STA102-B10-000-2 miniature circuit breakers offer good current limitation for short circuits and a high breaking capacity of 10, 15, or 25 kA. This results in reduced stress on conductors and higher selectivity with upstream fuses. The modules are designed for modularity, available in 1- to 4-pole versions, and for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 modular units (TE).

Key features include:

Technical Data

Explosion Protection

Einsatzbereich (Zonen) 1, 2
Einsatzbereich (Zonen) Hinweis Usable in Zone 21 / 22 when protected by enclosure Ex tb / tc
IECEx Bescheinigung Gas IECEx FMG 19.0029U
IECEx Gasexplosionsschutz Ex db eb IIC Gb
ATEX Bescheinigung Gas FM19ATEX0191U
ATEX Gasexplosionsschutz II 2 G Ex db eb IIC Gb
Bescheinigungen ATEX (FM), Brazil (ULB), IECEx (FM), People's Republic of China (CQST)
Konformitätserklärungen Konformitätsbescheinigung (ATEX)

Elektrische Daten

Bemessungsbetriebsspannung AC 230/400 V
Bemessungsbetriebsstrom 10 A
Frequenz 50/60 Hz
Bemessungsschaltvermögen 10 kA
Elektrische Lebensdauer 2 x 10⁴
Mechanische Lebensdauer 2 x 10⁴
1. Hilfsfunktion ohne
Bemessungsspannung 1. Hilfsfunktion AC -
Max. Bemessungsstrom 1. Hilfsfunktion -
2. Hilfsfunktion ohne
Max. Spannung 2. Hilfsfunktion DC -
Auslösecharakteristik B
Polzahl 2-polig

Umgebungsbedingungen

Umgebungstemperatur -40 °C ... 70 °C (-40 °F ... 158 °F)
Umgebungstemperatur Hinweis Deviating ambient temperatures are available upon request based on current certificates.

Mechanische Daten

Schutzart (IP) (IEC 60529) IP2X
Gehäusematerial Thermoplast
Anschlussquerschnitt min. 1.5 mm²
Anschlussquerschnitt max. 25 mm²
Anschlussquerschnitt AWG min. 16 AWG
Anschlussquerschnitt AWG max. 4 AWG
Anschlussquerschnitt 2 min. 1.5 mm²
Anschlussquerschnitt 2 max. 10 mm²
Anschlussquerschnitt 2 AWG min. 16 AWG
Anschlussquerschnitt 2 AWG max. 8 AWG
Anzugsdrehmoment min. 2 N·m
Anzugsdrehmoment max. 3 N·m
Anschlussquerschnitt Hinweis 2-conductor connection (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (A cross-section difference between the upper and lower chamber is permissible.) The permissible combination possibilities of the connection cross-sections can be found in the operating manual.
Breite 65 mm (2.56 in)
Länge 165 mm (6.5 in)
Einbautiefe 138.3 mm (5.44 in)
Gewicht 1 kg (2.205 lb)

Montage / Installation

Anzugsdrehmoment 2-3 N·m (17.7 ... 26.6 lbf·in)
Anzugsdrehmoment Hilfskontakt 0.4-0.6 Nm (3.5 ... 5.3 lbf·in)

Technical Drawings

Trip Characteristic B:

A diagram shows the trip characteristic curve for tripping current versus time for AC and DC. The curve is labeled as the limit characteristic from the cold state.

Dimensional Drawings (all dimensions in mm [inch]):

Diagrams illustrating the dimensions of the 8530/1; 2 modular units, showing width, height, and depth.

Accessories

Abschließvorrichtung vierfach (Lock-out/Tag-out Device)

A lock-out/tag-out shear for individually locking the component using up to 4 padlocks.

Description Article No.
A lock-out/tag-out shear for fastening the component onto the mounting plate without a top-hat rail. 276618

Zylinderschloss (Cylinder Lock)

Description Article No.
For locking (shackle Ø 3) 107115

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-b10-000-2-293915-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-C25-000-2: Technical Data and Features
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C25-000-2 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL MCB Miniature Circuit Breaker 8530/1-MCB-STA102-B10-000-2: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530 series MCB miniature circuit breaker (Art. No. 293915), including explosion protection, electrical data, mechanical data, and mounting information.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-B16-000-2 - Technical Data
Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA102-B16-000-2. Includes information on explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C20-000-2 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-C20-000-2 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and installation information.
Preview R. STAHL 8530/1-MCB-STA102-C40-000-2 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C40-000-2 Miniature Circuit Breaker, including electrical data, explosion protection, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C2-500-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C2-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Features include high current limiting, modular design, and ATEX/IECEx certifications.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA103N-B63-000-4: Technical Data and Features
Comprehensive technical specifications and features for the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA103N-B63-000-4. Details include explosion protection, electrical data, mechanical data, and accessories.