SMP7CTX220 Series Power Supply/Chargers

Installation Guide

Rev. 011604

Models Include:

  • SMP7CTX220, SMP7PMCTX220, SMP7PMCTXX220 - Single Output.
  • SMP7PMP4220 - Four (4) Fuse Protected Outputs.
  • SMP7PMP8220 - Eight (8) Fuse Protected Outputs.
  • SMP7PMP16220 - Sixteen (16) Fuse Protected Outputs.
  • SMP7PMP4CB220 - Four (4) PTC Protected Outputs.
  • SMP7PMP8CB220 - Eight (8) PTC Protected Outputs.
  • SMP7PMP16CB220 - Sixteen (16) PTC Protected Outputs.

For a red enclosure add an "R" suffix to the part #, e.g. SMP7CTX220R

Installing Company: _______________________________ Service Rep. Name: __________________________________

Address: _____________________________________________ Phone #: __________________

Overview

Altronix SMP7CTX220 Series power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz into a regulated 12VDC or 24VDC output with up to 6A of continuous load current.

SMP7CTX220 Series Power Supply Configuration Reference Chart

Altronix Model Number Accessory Power Distribution Module(s) Number of Outputs Fused Outputs PTC Outputs (auto-resettable) Individual Output Rating (A) Supervised
SMP7CTX220-1--6A-
SMP7PMCTX220-1--6A
SMP7PMCTXX220-1--6A-
SMP7PMP4220PD44-3.5A
SMP7PMP4CB220PD4CB4-2.5A
SMP7PMP8220PD88-3.5A
SMP7PMP8CB220PD8CB8-2.5A
SMP7PMP16220PD16W16-3.5A
SMP7PMP16CB220PD16WCB16-2.5A

Note: The chart also indicates 220/50/60Hz Input Current (1.5A) and Total Output Current (6A).

Specifications

Input:

Output:

Battery Backup:

Features:

Supervision (select models):

Visual Indicators:

Electrical:

Mechanical:

Enclosure Dimensions (H x W x D approx.):

Note: The BC400 enclosure accommodating two (2) 12VDC/12AH batteries is also available for other models upon request (contact Altronix).

Power Supply Voltage Output Specifications

Output VDC Switch Position Max. Load DC
12VDCSW1 - ON (See Fig. 1c, pg. 5)6A
24VDCSW1 - OFF (See Fig. 1c, pg. 5)6A

*Specified at 25°C ambient.

Switch Indicator: OFF - 24V, ON - 12V

Installation Instructions

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.

  1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure's upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (refer to Enclosure Dimensions, pgs. 7, 8). Secure enclosure to earth ground.
  2. Slide [Power ON/OFF] switch to OFF position.
  3. Set SW1 on the power supply board to the desired DC output voltage (refer to Power Supply Voltage Output Specification Chart).
  4. Connect AC power to the terminals marked [L & N], connect ground to earth (safety) ground (See Fig. 1, pg. 5). Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
  5. Slide [Power ON/OFF] switch to ON position.
  6. Measure output voltage before connecting devices. This helps avoiding potential damage. Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, Battery Wires). Minimum 0.25" spacing must be provided.
  7. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
  8. Slide [Power ON/OFF] switch to OFF position.
  9. Connect devices to be powered:
    • For Power Supply Board connect to the terminals marked [– DC +].
    • For Power Distribution Module(s) connect devices to the terminal pairs 1 to 4 marked [1P & 1N] through [4P & 4N] (See Fig. 2, pg. 6), 1 to 8 marked [1P & 1N] through [8P & 8N] (See Fig. 3, pg. 6), or 1 to 16 marked [1P & 1N] through [16P & 16N] (See Fig. 4, pg. 6), carefully observing correct polarity.
    Note: The Power ON/OFF switch is used to disconnect the L (HOT) terminal from the rest of the board (See Fig. 1a, pg. 5). When servicing the unit, AC mains should be removed.
  10. When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] (battery leads included).
    • 12VDC operation: Use one (1) 12VDC battery.
    • 24VDC operation: Use two (2) 12VDC batteries connected in series.
    Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
  11. For supervised models only: Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs marked [NC, C, NO] (See Fig. 1b, pg. 5).
  12. Slide [Power ON/OFF] switch to ON position.

LED Diagnostics

Power Supply Board Status:

Red (DC) Green (AC) Status
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery is supplying power.
OFFONNo DC output.
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module Status:

Green Status
ONNormal operating condition.
OFFNo Power Output.

Terminal Identification

Power Supply Board:

Terminal Legend Function/Description
L, G, NConnect 220VAC to these terminals: L to Hot, N to Neutral.
– DC +12VDC / 24VDC @ 6A continuous output.
*AC FAIL NC, C, NOUsed to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC.
*Low Battery NC, C, NOUsed to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC.
– BAT +Stand-by battery connections. Maximum charge rate 0.7A.

*Note: Supervised models only

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:

Terminal Legend (PD4/PD4CB) Terminal Legend (PD8/PD8CB) Terminal Legend (PD16W/PD16WCB) Function/Description
1P to 4P1P to 8P1P to16PPositive DC power outputs.
1N to 4N1N to 8N1N to 16NNegative DC power outputs.

CAUTION: Equipment to be installed / serviced by authorized / trained personnel only. Shut branch circuit power before installing / servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.

[High Voltage Warning]: The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product's enclosure that may be of sufficient magnitude to constitute an electric shock.

[Important Information]: The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.

⚠️ [Caution]: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.

Diagrams and Schematics

Fig. 1: System Layout

This diagram illustrates the general layout of the Altronix SMP7CTX220 Series power supply system within an enclosure. It shows the placement of the Power Supply Board and Power Distribution Module(s). Key connection points are indicated:

Fig. 1a: Explains that the Power ON/OFF switch disables the AC mains line voltage input, but the DC output remains active if stand-by batteries are connected.

Fig. 1b: Shows the connections for AC FAIL and LOW BAT supervisory relay outputs, labeled [NC, C, NO].

Fig. 1c: Details the SW1 switch for selecting between 12VDC (ON) and 24VDC (OFF) output.

Fig. 2: PD4/PD4CB Power Distribution Module

This diagram shows the layout for the PD4 and PD4CB Power Distribution Modules, designed for up to four outputs. It is indicated as "Used on PTC Models" when applicable.

Fig. 3: PD8/PD8CB Power Distribution Module

This diagram illustrates the PD8 and PD8CB Power Distribution Modules, supporting up to eight outputs. It is indicated as "Used on PTC Models" when applicable.

Fig. 4: PD16W/PD16WCB Power Distribution Module

This diagram depicts the PD16W and PD16WCB Power Distribution Modules, designed for up to sixteen outputs. It is indicated as "Used on PTC Models" when applicable.

Enclosure Dimensions

BC300 Enclosure

Dimensions: 13.5" x 13" x 3.25" (342.9mm x 330.2mm x 82.6mm).

This enclosure accommodates up to two (2) 12VDC/7AH batteries.

Note: An enclosure accommodating up to two (2) 12VDC/12AH batteries is also available upon request (contact Altronix).

Diagram Description: The diagram shows a rectangular enclosure with mounting hole patterns. It provides detailed measurements for the overall dimensions, depth, and placement of mounting holes, including offsets and diameters.

BC400 Enclosure

Dimensions: 15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm).

This enclosure accommodates up to two (2) 12VDC/12AH batteries.

Diagram Description: The diagram shows a rectangular enclosure with mounting hole patterns. It provides detailed measurements for the overall dimensions, depth, and placement of mounting holes, including offsets and diameters.

Models: SMP7CTX220 Series, Power Supply-Chargers, SMP7CTX220 Series Power Supply-Chargers, Supply-Chargers, Chargers

File Info : application/pdf, 8 Pages, 850.35KB

PDF preview unavailable. Download the PDF instead.

Altronix SMP7PMP8CB220 Power Supply Charger Installation Instructions

References

Adobe PDF Library 16.0 Adobe InDesign 16.4 (Macintosh)

Related Documents

Preview Altronix AL125ULB Two Output Switching Power Supply/Charger Datasheet
Technical specifications and overview for the Altronix AL125ULB, a two-output switching power supply and charger with PTC protected 12VDC/24VDC outputs, battery backup, and supervision features.
Preview Altronix OLS75 Off-Line Power Supply/Charger Installation Guide
Installation guide for the Altronix OLS75 Off-Line Power Supply/Charger, detailing specifications, features, and installation instructions for 12VDC/24VDC selectable output with 2.5A continuous current.
Preview Altronix OLS120 Power Supply Charger Installation Guide | Technical Specifications
Detailed installation guide and technical specifications for the Altronix OLS120 Off-Line Power Supply/Charger, covering overview, input/output, battery backup, supervision, and terminal identification.
Preview Altronix DPS5: Versatile 6/12/24VDC Power Supply & Charger Installation Guide
This guide provides installation instructions and specifications for the Altronix DPS5, a versatile power supply and charger offering selectable 6VDC, 12VDC, or 24VDC output at 4A. Ideal for access control, security, and CCTV systems.
Preview Altronix/Lenel-S2 Trove Kits Installation Guide
Installation guide for Altronix/Lenel-S2 (S2 Security Platform) Trove Kits, including T3SSK75F28 (Fused Outputs) and T3SSK75F28D (PTC Outputs) models. Details kit contents, configuration, and installation steps.
Preview Altronix AL400ULB UL Recognized Power Supply/Charger - Specifications and Installation
Detailed specifications, installation guide, and maintenance information for the Altronix AL400ULB UL Recognized power supply and charger, featuring 12VDC/24VDC selectable output and battery backup.
Preview Altronix AL624 Power Supply/Charger: Specifications and Overview
Comprehensive details on the Altronix AL624 Power Supply/Charger, covering its overview, technical specifications, input/output voltage selection, installation instructions, LED diagnostics, and terminal identification for access control, security, and CCTV systems.
Preview Altronix Trove2/Mercury Kits with Fused Outputs Installation Guide
Installation guide for Altronix Trove2/Mercury kits, detailing various fused output models, configuration options, and assembly instructions for access control systems. Includes overview, configuration charts, installation steps, and enclosure dimensions.