Altronix Trove2/Mercury Kits with Fused Outputs
Installation Guide
Overview
Altronix Trove Mercury kits are pre-assembled and consist of a Trove2 enclosure/backplane with factory-installed Altronix power supply/charger(s) and sub-assemblies. These kits accommodate various combinations of Mercury boards for up to sixteen (16) doors in a single enclosure.
Kit Models
4 Door Kits
- T2MK3F4: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane, (1) eFlow6NB - Power Supply/Charger, (1) ACM4 - Fused Access Power Controller, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
- T2MK3F4Q: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane, (1) eFlow6NB - Power Supply/Charger, (1) LINQ2 - Network Communications Module, (1) ACM4 - Fused Access Power Controller, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
8 Door Kits
- T2MK3F8: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane, (1) eFlow6NB - Power Supply/Charger, (1) ACM8 - Fused Access Power Controller, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
- T2MK3F8Q: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane, (1) eFlow6NB - Power Supply/Charger, (1) LINQ2 - Network Communications Module, (1) ACM8 - Fused Access Power Controller, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
- T2MK7F8: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane, (1) eFlow104NB - Power Supply/Charger, (1) ACM8 - Fused Access Power Controller, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
- T2MK7F8Q: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane, (1) eFlow104NB - Power Supply/Charger, (1) LINQ2 - Network Communications Module, (1) ACM8 - Fused Access Power Controller, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
16 Door Kits
- T2MK75F16: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane, (1) eFlow104NB and (1) eFlow102NB - Power Supply/Chargers, (2) ACM8 - Fused Access Power Controllers, (1) PD16W - Power Distribution Module.
- T2MK75F16Q: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane, (1) eFlow104NB and (1) eFlow102NB - Power Supply/Chargers, (1) LINQ2 - Network Communications Module, (2) ACM8 - Fused Access Power Controllers, (1) PD16W - Power Distribution Module.
- T2MK77F16: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane, (2) eFlow104NB - Power Supply/Chargers, (2) ACM8 - Fused Access Power Controllers, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
- T2MK77F16Q: Fully assembled kit includes: Trove2 enclosure with TM2 Altronix/Mercury backplane and TMV2 door backplane, (2) eFlow104NB - Power Supply/Chargers, (1) LINQ2 - Network Communications Module, (2) ACM8 - Fused Access Power Controllers, (1) VR6 - Voltage Regulator, (1) PDS8 - Dual Input Power Distribution Module.
All components of these Trove kits are UL Listed sub-assemblies. Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
Configuration Chart
Altronix Model Number | Networkable 120VAC 60Hz | Input Current (A) | Power Supply Board Input Fuse Rating | Power Supply Board Battery Fuse Rating | Output Range (VDC) [DC] | Output Range (VDC) [Aux] | Output Range (VDC) [DC] | Output Range (VDC) [Aux] | Maximum Supply Current for Main and Aux. Outputs on Power Supply board and ACM4/ACM8 Access Power Controller's outputs | Fail-Safe/Fail-Secure or Dry Form "C" Outputs | Current Per ACM4/ACM8 Output (A) | ACM4/ACM8 Board Input Fuse Rating | ACM4/ACM8 Board Output Fuse Rating | PDS8 Board Input Fuse Rating | PDS8 Board Output Fuse Rating | PD8UL/PD16W Board Output Fuse Rating |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
T2MK3F4 | ✓ | 3.5 | 5A/ 250V | 10A/ 32V | 20.19-26.4 | 20.19-26.4 | - | - | 24VDC @ 5.8A | 4 | 2.5 | 10A/ 250V | 3A/ 250V | 10A/ 250V | 3A/ 250V | - |
T2MK3F4Q | ✓ | 3.5 | 5A/ 250V | 10A/ 32V | 20.19-26.4 | 20.19-26.4 | - | - | 24VDC @ 5.8A | 4 | 2.5 | 10A/ 250V | 3A/ 250V | 10A/ 250V | 3A/ 250V | - |
T2MK3F8 | ✓ | 3.5 | 5A/ 250V | 10A/ 32V | 20.19-26.4 | 20.19-26.4 | - | - | 24VDC @ 5.8A | 8 | 2.5 | 10A/ 250V | 2.5A/ 250V | 10A/ 250V | 3A/ 250V | - |
T2MK3F8Q | ✓ | 3.5 | 5A/ 250V | 10A/ 32V | 20.19-26.4 | 20.19-26.4 | - | - | 24VDC @ 5.8A | 8 | 2.5 | 10A/ 250V | 2.5A/ 250V | 10A/ 250V | 3A/ 250V | - |
T2MK7F8 | 4.5 | 6.3A/ 250V | 15A/ 32V | 20.17-26.4 | 20.28-26.4 | - | - | 24VDC @ 9.2A | 8 | 2.5 | 10A/ 250V | 2.5A/ 250V | 10A/ 250V | 3A/ 250V | - | |
T2MK7F8Q | 4.5 | 6.3A/ 250V | 15A/ 32V | 20.17-26.4 | 20.28-26.4 | - | - | 24VDC @ 9.2A | 8 | 2.5 | 10A/ 250V | 2.5A/ 250V | 10A/ 250V | 3A/ 250V | - | |
T2MK75F16 | ✓ | 8 | 6.3A/ 250V | 15A/ 32V | 20.17-26.4 | 20.28-26.4 | 9.7-13.2 | 10.03-13.2 | 12VDC @ 9.3A 24VDC @ 9.2A |
16 | 2.5 | 10A/ 250V | 2.5A/ 250V | - | 3.5A/ 250V | - |
T2MK75F16Q | ✓ | 8 | 6.3A/ 250V | 15A/ 32V | 20.17-26.4 | 20.28-26.4 | 9.7-13.2 | 10.03-13.2 | 12VDC @ 9.3A 24VDC @ 9.2A |
16 | 2.5 | 10A/ 250V | 2.5A/ 250V | - | 3.5A/ 250V | - |
T2MK77F16 | ✓ | 9 | 6.3A/ 250V | 15A/ 32V | 20.17-26.4 | 20.28-26.4 | 20.17-26.4 | 20.28-26.4 | 24VDC @ 9.2A | 16 | 2.5 | 10A/ 250V | 2.5A/ 250V | 10A/ 250V | 3A/ 250V | - |
T2MK77F16Q | ✓ | 9 | 6.3A/ 250V | 15A/ 32V | 20.17-26.4 | 20.28-26.4 | 20.17-26.4 | 20.28-26.4 | 24VDC @ 9.2A | 16 | 2.5 | 10A/ 250V | 2.5A/ 250V | 10A/ 250V | 3A/ 250V | - |
Installation Instructions
- Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
- Remove backplane(s) from enclosure. Do not discard hardware.
- Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure's upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
- Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2" from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
- Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB, eFlow102NB, eFlow104NB and Sub-Assembly Installation Guide for the following models: ACM4, ACM8, LINQ2, PDS8, VR6 for further installation instructions.
- Fasten snap on spacers onto metal pems configuration of backplane depending on the Mercury access controller (Fig. 2-5, pg. 3-6).
- Position Mercury access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2-5, pg. 3-6).
- Mount backplane to enclosure with hardware.
Diagram Descriptions
Figure 1: Tamper Switch Mounting
Illustrates the mounting location of the included UL Listed tamper switch (Altronix Model TS112 or equivalent) on the enclosure edge, approximately 2 inches from the right side. It shows the connection points to an Access Control Panel or UL Listed reporting device.
Figure 2 & 2a: T2MK3F4, T2MK3F4Q, T2MK3F8, T2MK3F8Q - Mercury Board Configuration
Shows the backplane layout for T2MK3F4, T2MK3F4Q, T2MK3F8, and T2MK3F8Q kits. It details the placement of Altronix LINQ2 Module (for Q models), eFlow6NB Power Supply/Charger, ACM4 (for T2MK3F4/Q) or ACM8 (for T2MK3F8/Q) Access Power Controllers, and PDS8 Power Distribution Module. Altronix VR6 is mounted under the PDS8. Figure 2a illustrates how snap-on spacers are fastened to metal pems (labeled A, B, C, D) on the backplane, and how the Mercury board is positioned and secured onto these spacers.
Figure 3 & 3a: T2MK7F8, T2MK7F8Q - Mercury Board Configuration
Details the backplane layout for T2MK7F8 and T2MK7F8Q kits. It shows the placement of Altronix LINQ2 Module (for Q models), eFlow104NB Power Supply/Charger, ACM8 Access Power Controller, and PDS8 Power Distribution Module. Altronix VR6 is mounted under the PDS8. Figure 3a illustrates the mounting of Mercury boards using snap-on spacers on pems (labeled A, B, C, D) on the backplane.
Figure 4 & 4a: T2MK75F16, T2MK75F16Q - Mercury Board Configuration
Illustrates the backplane configuration for T2MK75F16 and T2MK75F16Q kits. It shows the placement of Altronix LINQ2 Module (for Q models), two Altronix power supplies (eFlow102NB and eFlow104NB), two Altronix ACM8 Access Power Controllers, and the PD16W Power Distribution Module. Figure 4a shows the mounting of Mercury boards using snap-on spacers on pems (labeled A, B, C, D) on the backplane.
Figure 5 & 5a: T2MK77F16, T2MK77F16Q - Mercury Board Configuration
Details the backplane layout for T2MK77F16 and T2MK77F16Q kits. It shows the placement of Altronix LINQ2 Module (for Q models), two Altronix eFlow104NB Power Supply/Chargers, two Altronix ACM8 Access Power Controllers, and the PDS8 Power Distribution Module. Altronix VR6 is mounted under the PDS8. Figure 5a illustrates the mounting of Mercury boards using snap-on spacers on pems (labeled A, B, C, D) on the backplane.
Figure 6 & 6a: TMV2 (T2MK75F16, T2MK75F16Q, T2MK77F16, T2MK77F16Q) - Mercury and/or Altronix Board Configuration
Describes the configuration of Mercury and Altronix boards for TMV2 enclosures. It shows the placement of Mercury Access Controllers on pems (labeled A, B) and Altronix Sub-Assemblies/Adapters (like ACM4, MOM5, PD4UL, PD8UL, PDS8, VR6, GB1) on pems (labeled C). Figure 6a illustrates the use of nylon spacers and pems for mounting.
Enclosure Dimensions
The enclosure dimensions are approximately: Height 27.25 inches (692.2mm), Width 21.5 inches (552.5mm), Depth 6.5 inches (165.1mm). Detailed measurements for mounting points and knockouts are provided in the original document's diagram.