Overview

Altronix Trove Mercury kits are pre-assembled and consist of a Trove2 enclosure/backplane with factory-installed Altronix power supply/charger(s) and sub-assemblies. These kits accommodate various combinations of Mercury boards for up to sixteen (16) doors in a single enclosure.

Kit Models

4 Door Kits

8 Door Kits

16 Door Kits

All components of these Trove kits are UL Listed sub-assemblies. Please refer to the included corresponding Sub-Assembly Installation Guides for further information.

Configuration Chart

Altronix Model Number Networkable 120VAC 60Hz Input Current (A) Power Supply Board Input Fuse Rating Power Supply Board Battery Fuse Rating Output Range (VDC) [DC] Output Range (VDC) [Aux] Output Range (VDC) [DC] Output Range (VDC) [Aux] Maximum Supply Current for Main and Aux. Outputs on Power Supply board and ACM4/ACM8 Access Power Controller's outputs Fail-Safe/Fail-Secure or Dry Form "C" Outputs Current Per ACM4/ACM8 Output (A) ACM4/ACM8 Board Input Fuse Rating ACM4/ACM8 Board Output Fuse Rating PDS8 Board Input Fuse Rating PDS8 Board Output Fuse Rating PD8UL/PD16W Board Output Fuse Rating
T2MK3F4 3.5 5A/ 250V 10A/ 32V 20.19-26.4 20.19-26.4 - - 24VDC @ 5.8A 4 2.5 10A/ 250V 3A/ 250V 10A/ 250V 3A/ 250V -
T2MK3F4Q 3.5 5A/ 250V 10A/ 32V 20.19-26.4 20.19-26.4 - - 24VDC @ 5.8A 4 2.5 10A/ 250V 3A/ 250V 10A/ 250V 3A/ 250V -
T2MK3F8 3.5 5A/ 250V 10A/ 32V 20.19-26.4 20.19-26.4 - - 24VDC @ 5.8A 8 2.5 10A/ 250V 2.5A/ 250V 10A/ 250V 3A/ 250V -
T2MK3F8Q 3.5 5A/ 250V 10A/ 32V 20.19-26.4 20.19-26.4 - - 24VDC @ 5.8A 8 2.5 10A/ 250V 2.5A/ 250V 10A/ 250V 3A/ 250V -
T2MK7F8 4.5 6.3A/ 250V 15A/ 32V 20.17-26.4 20.28-26.4 - - 24VDC @ 9.2A 8 2.5 10A/ 250V 2.5A/ 250V 10A/ 250V 3A/ 250V -
T2MK7F8Q 4.5 6.3A/ 250V 15A/ 32V 20.17-26.4 20.28-26.4 - - 24VDC @ 9.2A 8 2.5 10A/ 250V 2.5A/ 250V 10A/ 250V 3A/ 250V -
T2MK75F16 8 6.3A/ 250V 15A/ 32V 20.17-26.4 20.28-26.4 9.7-13.2 10.03-13.2 12VDC @ 9.3A
24VDC @ 9.2A
16 2.5 10A/ 250V 2.5A/ 250V - 3.5A/ 250V -
T2MK75F16Q 8 6.3A/ 250V 15A/ 32V 20.17-26.4 20.28-26.4 9.7-13.2 10.03-13.2 12VDC @ 9.3A
24VDC @ 9.2A
16 2.5 10A/ 250V 2.5A/ 250V - 3.5A/ 250V -
T2MK77F16 9 6.3A/ 250V 15A/ 32V 20.17-26.4 20.28-26.4 20.17-26.4 20.28-26.4 24VDC @ 9.2A 16 2.5 10A/ 250V 2.5A/ 250V 10A/ 250V 3A/ 250V -
T2MK77F16Q 9 6.3A/ 250V 15A/ 32V 20.17-26.4 20.28-26.4 20.17-26.4 20.28-26.4 24VDC @ 9.2A 16 2.5 10A/ 250V 2.5A/ 250V 10A/ 250V 3A/ 250V -

Installation Instructions

  1. Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
  2. Remove backplane(s) from enclosure. Do not discard hardware.
  3. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure's upper keyholes over the three upper screws. Install the three lower screws and make sure to tighten all screws.
  4. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2" from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
  5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB, eFlow102NB, eFlow104NB and Sub-Assembly Installation Guide for the following models: ACM4, ACM8, LINQ2, PDS8, VR6 for further installation instructions.
  6. Fasten snap on spacers onto metal pems configuration of backplane depending on the Mercury access controller (Fig. 2-5, pg. 3-6).
  7. Position Mercury access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2-5, pg. 3-6).
  8. Mount backplane to enclosure with hardware.

Diagram Descriptions

Figure 1: Tamper Switch Mounting

Illustrates the mounting location of the included UL Listed tamper switch (Altronix Model TS112 or equivalent) on the enclosure edge, approximately 2 inches from the right side. It shows the connection points to an Access Control Panel or UL Listed reporting device.

Figure 2 & 2a: T2MK3F4, T2MK3F4Q, T2MK3F8, T2MK3F8Q - Mercury Board Configuration

Shows the backplane layout for T2MK3F4, T2MK3F4Q, T2MK3F8, and T2MK3F8Q kits. It details the placement of Altronix LINQ2 Module (for Q models), eFlow6NB Power Supply/Charger, ACM4 (for T2MK3F4/Q) or ACM8 (for T2MK3F8/Q) Access Power Controllers, and PDS8 Power Distribution Module. Altronix VR6 is mounted under the PDS8. Figure 2a illustrates how snap-on spacers are fastened to metal pems (labeled A, B, C, D) on the backplane, and how the Mercury board is positioned and secured onto these spacers.

Figure 3 & 3a: T2MK7F8, T2MK7F8Q - Mercury Board Configuration

Details the backplane layout for T2MK7F8 and T2MK7F8Q kits. It shows the placement of Altronix LINQ2 Module (for Q models), eFlow104NB Power Supply/Charger, ACM8 Access Power Controller, and PDS8 Power Distribution Module. Altronix VR6 is mounted under the PDS8. Figure 3a illustrates the mounting of Mercury boards using snap-on spacers on pems (labeled A, B, C, D) on the backplane.

Figure 4 & 4a: T2MK75F16, T2MK75F16Q - Mercury Board Configuration

Illustrates the backplane configuration for T2MK75F16 and T2MK75F16Q kits. It shows the placement of Altronix LINQ2 Module (for Q models), two Altronix power supplies (eFlow102NB and eFlow104NB), two Altronix ACM8 Access Power Controllers, and the PD16W Power Distribution Module. Figure 4a shows the mounting of Mercury boards using snap-on spacers on pems (labeled A, B, C, D) on the backplane.

Figure 5 & 5a: T2MK77F16, T2MK77F16Q - Mercury Board Configuration

Details the backplane layout for T2MK77F16 and T2MK77F16Q kits. It shows the placement of Altronix LINQ2 Module (for Q models), two Altronix eFlow104NB Power Supply/Chargers, two Altronix ACM8 Access Power Controllers, and the PDS8 Power Distribution Module. Altronix VR6 is mounted under the PDS8. Figure 5a illustrates the mounting of Mercury boards using snap-on spacers on pems (labeled A, B, C, D) on the backplane.

Figure 6 & 6a: TMV2 (T2MK75F16, T2MK75F16Q, T2MK77F16, T2MK77F16Q) - Mercury and/or Altronix Board Configuration

Describes the configuration of Mercury and Altronix boards for TMV2 enclosures. It shows the placement of Mercury Access Controllers on pems (labeled A, B) and Altronix Sub-Assemblies/Adapters (like ACM4, MOM5, PD4UL, PD8UL, PDS8, VR6, GB1) on pems (labeled C). Figure 6a illustrates the use of nylon spacers and pems for mounting.

Enclosure Dimensions

The enclosure dimensions are approximately: Height 27.25 inches (692.2mm), Width 21.5 inches (552.5mm), Depth 6.5 inches (165.1mm). Detailed measurements for mounting points and knockouts are provided in the original document's diagram.

Models: T2MK3F4, T2MK3F8, T2MK75F16, T2MK3F4Q, T2MK3F8Q, T2MK77F16Q, T2MK75F16Q, T2MK7F8, T2MK7F8Q, T2MK77F16, T2MK3F4 Trove2-Mercury Kits with Fused Outputs, T2MK3F4, Trove2-Mercury Kits with Fused Outputs, Trove2-Mercury Kits, Mercury Kits

File Info : application/pdf, 8 Pages, 1.09MB

PDF preview unavailable. Download the PDF instead.

TroveM kits Series

References

Adobe PDF Library 16.0.3 Adobe InDesign 17.0 (Macintosh)

Related Documents

Preview Altronix Trove1/Mercury Kits Installation Guide
Comprehensive installation guide for Altronix Trove1/Mercury Kits, detailing models T1MK14, T1MK14D, T1MK14S, and T1MK14SD, including product overview, configuration charts, installation steps, and enclosure dimensions.
Preview Altronix/DMP 734/734N Wiegand Kits Installation Guide
Comprehensive installation guide for Altronix/DMP 734/734N Wiegand Kits, including models T1DMK3F4, T1DMK3F4D, T2DMK7F8, and T2DMK7F8D. It covers kit overviews, component lists, a configuration chart, step-by-step installation procedures, hardware requirements, module mounting diagrams, enclosure dimensions, and information on the optional LINQ2 Network Communication Module. Essential for integrators and technicians setting up Altronix access control power solutions.
Preview Altronix MaximalFD Series PTC Access Power Controllers Installation Guide
Installation guide for Altronix MaximalFD Series Single Power Supply Access Power Controllers (PTC), including Maximal3FD, Maximal5FD, and Maximal7FD models. Covers features, installation, maintenance, wiring, and specifications.
Preview Altronix Trove Access & Power Integration Enclosure Installation Guide
Comprehensive installation guide for Altronix Trove1SA1 and Trove2SA2 enclosures with Altronix/SALTO backplanes, designed for integrating access control and power supply systems. Includes specifications, mounting instructions, and module configuration details.
Preview Altronix TM400 Compact Enclosure Installation Guide
Installation guide for the Altronix TM400 compact enclosure, detailing its features, specifications, and how to integrate Altronix power distribution and Mercury/LenelS2 access controllers.
Preview Altronix Trove1M1 Enclosure & TM1 Backplane: Access & Power Integration Solution
Detailed specifications and features of the Altronix Trove1M1 enclosure and TM1 backplane, designed for seamless integration of Mercury access control systems. Includes dimensions, compatibility, agency listings, and accessories.
Preview Altronix Trove2 Enclosure: Secure Access & Power Integration Solutions
Explore the Altronix Trove2, a robust enclosure designed for seamless integration of access control systems and power solutions. Features include durable construction, versatile knockout configurations, and compatibility with leading manufacturers.
Preview Altronix TROVE Series: Integrated Access Control Power and Distribution
Discover the Altronix TROVE Series, offering comprehensive solutions for access control power and integration. Explore enclosure options, pre-configured kits, power supplies, sub-assemblies, and accessories for efficient security system deployment.