Installation Guide for Altronix models including: OLS120, Off-Line Power Supply-Charger, Power Supply-Charger, Supply-Charger
Altronix OLS120 Power Supply Charger - Fire and Safety Plus
Altronix OLS120 | Power Supply Charger, Single Output, 12/24
File Info : application/pdf, 2 Pages, 480.20KB
DocumentDocumentOLS120 Off-Line Power Supply/Charger Installation Guide Overview: Altronix OLS120 power supply/charger converts 115VAC, 60Hz or 230VAC, 50Hz input into a 12VDC or 24VDC at 4A of continuous supply current (see specifications). This general purpose power supply has a wide range of applications for access control and security system accessories that require additional power. Specifications: Agency Listings: · UL Recognized component for Information Technology Equipment (UL 60950-1). · CE European Conformity. Input: · Universal input 115VAC, 60Hz, 0.95A or 230VAC, 50Hz, 0.6A. Output: · 12VDC or 24VDC selectable output. · 4A continuous supply current. · Filtered and electronically regulated output. · Short circuit and thermal overload protection. Battery Backup: · Built-in charger for sealed lead acid or gel type batteries. Battery Backup (cont'd): · Automatic switch over to stand-by battery when AC fails. · Maximum charge current 0.7A. Supervision: · AC fail supervision (form "C" contacts). · Low battery supervision (form "C" contacts). Visual Indicators: · AC input and DC output LED indicators. Features: · Power ON/OFF switch. · Includes battery leads. Board Dimensions (L x W x H approx.): 7.25" x 4.5" x 1.75" (184.1mm x 114.3mm x 44.5mm). Installation Instructions: OLS120 should be installed in accordance with The National Electrical Code and all applicable Local Regulations. 1. Mount the OLS120 in the desired location/enclosure (mounting hardware included). 2. Slide [Power ON/OFF] switch to OFF position. 3. Set the OLS120 to the desired DC output voltage via SW1 (Voltage Output Selection Table). Keep power-limited wiring separate from non power-limited wiring (115VAC/230VAC 50/60Hz Input, Battery Wires). Minimum 0.25" spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts on unit. Refer installation and servicing to qualified service personnel. 4. Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G]. Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting). 5. Slide [Power ON/OFF] switch to ON position. 6. Measure output voltage before connecting devices. This helps avoiding potential damage. 7. Slide [Power ON/OFF] switch to OFF position. 8. Connect devices to be powered to the terminals marked [ DC +]. 9. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to the terminals marked [ BAT +] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. 10. When batteries are not used, a loss of AC will result in the loss of output voltage. 11. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory relay outputs marked [NC, C, NO]. 12. Slide [Power ON/OFF] switch to ON position. Voltage Output Selection Table: Output VDC Switch Position Max. Load DC 12VDC SW1 - ON 4A 24VDC SW1 - OFF 4A Red (DC) ON ON OFF OFF Green (AC) ON OFF ON OFF LED Diagnostics: Power Supply Status Normal operating condition. Loss of AC. Stand-by battery is supplying power. No DC output. Short circuit or thermal overload condition. No DC output. Loss of AC. Discharged or no battery present. Terminal Legend L, G, N DC + AC FAIL NC, C, NO Low Battery NC, C, NO BAT + Terminal Identification: Function/Description Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral, G to ground. 12VDC / 24VDC @ 4A continuous supply current. Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 115VAC / 28VDC Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 115VAC / 28VDC. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC. 24VDC output threshold set @ approximately 21VDC. Stand-by battery connections. Maximum charge rate 0.7A. OFF - 24V ON - 12V LOW BAT ON OFF ON AC DC OLS120 5A 250V L G N AC FAIL NC C NO NC C NO --- BAT + --- DC + Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty IIOLS120 - Rev. 010704 H30U MEMBER