R. STAHL IS1 Relay Digital Output Module 9477/12-08-12 for Zone 1 Ex d e
Article No. 162627
Overview
The R. STAHL 9477/12-08-12 digital output relay module for Zone 1 offers 8 channels for solenoid valve operation not requiring intrinsic safety, with a high switching capacity. The outputs are available as potential-free relay contacts (make contacts) in Ex e or with Conduit connection technology. Combined operation with Ex i I/O modules is permitted.
- Up to 8 potential-free relay contacts
- Ex e outputs with high switching capacity up to 100 VA
- Zone 1 module can be hot-swapped
Technical Data
Explosion Protection
Application (zones) | 1, 2 |
---|---|
Interface Ex zone | 1, 2 |
IECEx gas certification | IECEx PTB 06.0001X |
IECEx protection against gas explosions | Ex d e [ia, ib] IIC T4 |
ATEX gas certification | PTB 01 ATEX2187 |
ATEX protection against gas explosions | II 2 G Ex d e [ia, ib] IIC T4 |
FM certification | FM17US0332X |
cFM certification | FM16CA0134X |
cFM marking | XP; Class I, Div. 1, Groups A,B,C,D; Class I, Zone 1, IIC; T4 at Ta = 65 °C; See Doc. 9477 6 031 001 1 |
Certifications | ABS, BVIS, EU RO MR (DNV), KR, LR |
Installation | Zone 1/Division 1 |
Further specifications | See operating manual and certifications |
Electrical Data
Number of channels | 8 Ex e outputs | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Terminal connection Ex e/conduit | 2.5 mm² | |||||||||
Auxiliary power connection | BusRail types 9494 | |||||||||
Auxiliary power supply unit model | Intrinsic safety Ex ia via BusRail | |||||||||
Behavior on undervoltage | All outputs "OFF" | |||||||||
Current consumption | 200 mA | |||||||||
Maximum power consumption | 4.8 W | |||||||||
Maximum dissipated energy outputs | 4.8 W | |||||||||
Undervoltage monitoring | Output = OFF | |||||||||
Galvanic separation | Complies with EN 60079-11 | |||||||||
Auxiliary supply/System component voltage | 1500 V AC | |||||||||
I/O Module - I/O Module voltage | 500 V AC | |||||||||
I/O Channels - System component voltage | 375 V AC | |||||||||
I/O Channels - I/O Channels voltage | 250 V AC | |||||||||
Output contact model | NA contact | |||||||||
Maximum switching voltage | 65 V AC | |||||||||
Minimum switching voltage | 5 V AC/DC | |||||||||
Maximum switching current | 2 A | |||||||||
Minimum switching current | 2 mA | |||||||||
Switching capacity |
| |||||||||
Service life | Electrical at max. 2 A | |||||||||
CA 1 - Load | ≥ 0.6 x 10⁶ switching cycles | |||||||||
DC 1 - Load condition (ohmic load) | ≥ 100 x 10³ switching cycles | |||||||||
Max. contact load without damaging gold plating | Up to 24 V / 1.5 W | |||||||||
Safe contact in case of damaged gold plating | From 12 V / 1.5 W | |||||||||
Connections | 2.5 mm² flexible | |||||||||
Maximum signal delay from internal bus to output | 10 ms |
Device Specific Data
Diagnostic messaging module | CON |
---|---|
Output error proportion | DESC |
Accessible parameters | Conserve last value |
Condition LED | CON |
Module status and alarms | DESC |
Diagnostic | |
Collective error LED | LED "ERR", red |
Ambient conditions | |
Ambient temperature | -20°C ... +65°C (-4°F ... +149°F) |
Storage temperature | -40°C ... +70°C (-40°F ... +158°F) |
Maximum altitude | < 2000 m |
Max. relative humidity | 95% (non-condensing) |
Shock (semisinusoidal) | 15 g (3 shocks per axis and direction) (IEC EN 60068-2-27) |
Vibration (sinusoidal) | Frequency range 2 - 13.2 Hz: Amplitude 1.0 mm (max value); Frequency range 13.2 - 100 Hz: Acceleration amplitude 0.7 g (IEC EN 60068-2-6) |
Electromagnetic compatibility | Complies with standards and regulations: EN 61326-1 (2006), IEC 61000-4-1...6, NAMUR NE 21 |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP20 |
---|---|
Module housing | Polyamide 6 GF |
Fire resistance (UL 94) | HB |
Emission category | Corresponds to G3 |
Width | 96.5 mm (3.8 in) |
Depth | 170 mm (6.70 in) |
Length | 208 mm (8.19 in) |
Installed depth | 169 mm (6.69 in) |
Contacts | NA contact |
Weight | 2.57 kg (5.67 lb) |
Mounting / Installation | |
Mounting position | Vertical / Horizontal |
Dimensions
Diagrams showing module dimensions are available. All measurements are in millimeters (inches).
Relay module of digital output with base for Division 1
Relay module of digital output for Zone 1
Accessories
Accessory | Article No. |
---|---|
Base for relay module of digital output | |
Zone 1, connection via Ex e terminals for digital output relay modules 9477/12, 8 channels | 162703 |
Division 1, connection via Conduit for digital output relay modules 9477/12, 8 channels | 162712 |
Anti-vibration mounting kit | 271919 |
For installations with extreme vibrations (> 0.7 g and max. 4 g), the anti-vibration mounts 9490 can be used as an additional measure and ensure the mechanical stability of the individual modules. For mounting: DOMR 9477/12 module for Zone 1. Number of mounts in the set: 1. Screws (Art. No. 275516) must be ordered separately! | |
Screw set | 275516 |
Screw set M5 x 14 (threadable) for anti-vibration mounts 9490. Number of screws in the set: 25 |
R. STAHL reserves the right to modify technical data, dimensions, weights, designs, and delivery options.