R. STAHL Remote I/O IS1+ Digital Output Module for Zone 1 Ex i

Art. No. 9475/32-04-12

Product Overview

The R. STAHL 9475/32-04 digital output modules for Zone 1 are designed for controlling Ex i solenoid valves or indicator lamps. They feature four channels for Ex i solenoid valves up to 40 mA and an additional Ex i control input for safe shutdown up to SIL 2. All outputs are short-circuit proof, galvanically separated from the system, and individually monitored for wire breakage/short-circuiting.

Key features include:

Technical Data

Explosion Protection

Application range (zones) 1, 2
Ex interface zone 0, 1, 2, 20, 21, 22
IECEX gas certificate IECEX DEK 12.0070X
IECEx gas explosion protection Ex ia [ia Ga] IIC T4 Gb
IECEx dust certificate IECEX DEK 12.0070X
IECEx dust explosion protection [Ex ia Da] IIIC
ATEX gas certificate DEKRA 12 ATEX0232X
ATEX gas explosion protection II 2 (1) G Ex ia [ia Ga] IIC T4 Gb
ATEX dust certificate DEKRA 12 ATEX0232X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
FMus certificate FM17US0332X
CFM certificate FM16CA0134X
Marking cFMus IS, Class I, Div. 1, Groups A,B,C,D; Class I, Zone 1, AEx/Ex ia [ia] IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; T4 at Ta = 75°C
Certificates ATEX (DEK), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (DEK), India (PESO), Korea (KTL), SIL (exida), USA (FM)
Ship approval ABS, BVIS, EU RO MR (DNV), KR, LR
Declaration of conformity ATEX (EUK), China (CCC)
Installation Zone 1, Zone 2 and safe areas

Safety Data

Max. voltage U<0xE2><0x82><0x98> 19.7 V
Max. current I<0xE2><0x82><0x98> (Ex ia) 142 mA
Max. power P<0xE2><0x82><0x98> (Ex ia) 698 mW
Max. current I<0xE2><0x82><0x99> (Ex ib) 53.8 mA
Max. power P<0xE2><0x82><0x99> (Ex ib) 617 mW
Internal inductance Negligible
Max. internal capacitance C<0xE2><0x82><0x98> 11 nF

Output ia

L<0xE2><0x82><0x98> [mH] C<0xE2><0x82><0x98> [nF]
IIC 1.3, 1.1, 0.5, 0.2, 0.1, 0.05 99, 109, 119, 149, 189, 220
IIB/IIIC 7.5, 5.0, 2.0, 0.5, 0.2, 0.1, 0.05 669, 879, 889, 889, 989, 1189, 1439

Output ib

L<0xE2><0x82><0x98> [mH] C<0xE2><0x82><0x98> [nF]
IIC 3.1, 2.0, 0.6, 0.5, 0.2, 0.1, 0.05 109, 109, 119, 119, 149, 189, 220
IIB/IIIC 27, 20, 10, 5.0, 0.2, 0.1, 0.05 499, 609, 869, 899, 1089, 1189, 1439

Ex i control input "Plant STOP"

Connection terminals X3 1, 2 (without galvanic separation, compatible with 9575/22) X3 3, 4 (with galvanic separation, switchable in parallel)
Type of protection Ex ia Ex ia
Max. voltage U<0xE2><0x82><0x98> 5.1 V --
Max. current I<0xE2><0x82><0x98> 0.44 mA --
Max. power P<0xE2><0x82><0x98> 0.5 mW --
Max. connectable inductance L/capacitance C<0xE2><0x82><0x98> IIC: L<0xE2><0x82><0x98> [mH] 100, 10, 2, 1, 0.2, 0.01; C<0xE2><0x82><0x98> [nF] 2.195, 2.595, 3.295, 3.695, 5.495, 15.995 IIC: L<0xE2><0x82><0x98> [mH] --; C<0xE2><0x82><0x98> [nF] --
IIB/IIIC: L<0xE2><0x82><0x98> [mH] 100, 10, 2, 1, 0.2, 0.01; C<0xE2><0x82><0x98> [nF] 9.995, 12.995, 16.995, 19.995, 31.995 IIB/IIIC: L<0xE2><0x82><0x98> [mH] --; C<0xE2><0x82><0x98> [nF] --
Max. voltage U<0xE2><0x82><0x98> -- 30 V
Max. internal resistance R<0xE2><0x82><0x98> -- 4040 Ω

Electrical Data

Number of channels: 4 Ex i outputs

Connection Ex i field signals: Pluggable, blue terminals, 16-pin, 2.5 mm², screw type or cage clamp version with lock

Connection Ex i Steuereingang: Pluggable, blue terminals, 2-pin, 2.5 mm², screw type version with lock

Device Specific Data

Output behaviour in case of error Keep last value, ON, OFF
Retrievable parameters Hardware revision, Manufacturer, Serial number, Software revision, Type
LED module requires maintenance "M/S" LED, blue
LED operating conditions "RUN" LED, green
LED channel error LED for each channel, red
LED channel status LED per channel, yellow
"Plant STOP" LED "Plant STOP" LED, yellow (all outputs are high-impedance)
Signal status bit "1" = Output supplied with power, "0" = High-impedance output
Wire breakage output > 10 kΩ (when the test current is deactivated, can only be detected if the output is switched on)
Short circuit output < 30 Ω (response range 30 to 60 Ω) (can be detected only if the output is switched on)
Diagnostics LED group error: "ERR" LED, red

Ambient Conditions

Ambient temperature -40°C ... +75°C (-40°F ... +167°F)
Storage temperature -40°C ... +80°C (-40°F ... +176°F)
Max. operating altitude < 2000 m
Max. relative humidity 95% (without condensation)
Shock (semi-sinusoidal) 15 g (3 shocks per axis and direction) (IEC EN 60068-2-27)
Vibration (sinusoidal) Frequency range 2 to 13.2 Hz Amplitude 1 mm (peak value); Frequency range 13.2 to 100 Hz Acceleration amplitude 0.7 g (IEC EN 60068-2-6)
Electromagnetic compatibility Tested to the following standards and regulations: EN 61326-1 (2006) IEC 61000-4-1 to 61000-4-6, NAMUR NE 21 (observe operating instructions)

Mechanical Data

Degree of protection (IP) (IEC 60529) IP20
Module enclosure Polyamide 6GF
Fire resistance (UL 94) V2
Pollutant class Corresponds to G3
Width 96.5 mm (3.8 in)
Height 67 mm
Length 128 mm (5.04 in)
Mounting depth in inches 2.64 in
Weight 275 g (0.61 lb)
Mounting type on NS 35/15 DIN rail (DIN EN 60715)
Mounting orientation Horizontal, Vertical

Accessories

Pluggable terminal 2.5 mm² with lock, 16-pin, screw connector, blue, for connecting the field signals to I/O modules, for intrinsically safe field circuits. Labelling: 1 to 16. Note: A second terminal is additionally required for I/O module Series 9470 and 9482. Labelling: 17 to 32. Art. No. 162702
2.5 mm² with lock, 16-pin, spring clamp connection, blue, for connecting the field signals to I/O modules, for intrinsically safe field circuits, incl. test jacks. Labelling: 1 to 16. Note: A second terminal is additionally required for I/O module Series 9470 and 9482. Labelling: 17 to 32. Art. No. 162695
Electronic relay The 9174 electronic relay module makes it possible to switch Ex e loads using an intrinsically safe control system. Input: Ex i; output: 31.2 V/2 A DC, Ex e. Art. No. 212340
Electronic relay The electronic relay modules are used to switch Ex e loads using an intrinsically safe (Ex i) or non-intrinsically safe (Ex e) control system. Coil circuit: Ex i or non-Ex i (Ex e)*. Contact circuit: Non-Ex i (Ex e). *It is possible to switch between Ex i and non-Ex i circuits, or vice versa, at any time without restriction. Note: Cannot be used with 9475/32-04-12, 9475/32-08-52, 9475/33-08-50 Art. No. 282457
Ex i/Ex e relay module for Zone 1 The Ex i/Ex e relay module is used for the galvanically isolated switching of intrinsically safe (Ex i) and non-Ex i (Ex e) electrical circuits. Coil circuit: Ex i or non-Ex i (Ex e). Contact circuit: Ex i or non-Ex i (Ex e). Thanks to the integrated safeguarding for the contact and coil circuit, additional safeguarding is not necessary. Note: Not usable with 9475/32-04-12, 9475/32-08-52, 9475/33-08-50 Art. No. 273000
Partition For mounting between intrinsically safe and non-intrinsically safe connections between I/O modules to maintain a tight string length of 50 mm. Art. No. 220101
Resistor error message suppression The resistors are used to suppress error messages for unused I/O channels. Resistance value: 5K6/0.5 W. Suitable for: AIM 9468; UMH 9469; DIOM 9470; DIOM 9471; DIOM 9472; DOM 9475. For intrinsically safe circuits (simple apparatus according to EN 60079-11). Art. No. 244911
Warning label "Clean modules only with a damp cloth." Art. No. 162796
DIN A4 sheet For label plate on I/O modules; 6 plates per sheet; IS Wizard printout; packaging unit = 20 sheets. Art. No. 162832
Labelling strips "FB Addr Mod No ..." for pluggable terminal, 26 pieces on the sheet. Art. No. 162788

Spare Parts

Vibration bracket set When installed in environments with extreme vibration (> 0.7 g and max. 4 g), the 9490 vibration brackets may be used as an additional measure and provide mechanical stability for the individual modules. For mounting: All I/O modules, except 9477/12 and 9478. Number of brackets in a set: 8. Screws (item no. 275516) must be ordered separately. Art. No. 271920
Set of screws Set of M5 x 14 screws (self-tapping) for 9490 vibration brackets. Number of screws in a set: 25. Art. No. 275516
Ex i LED indicator lamp 8010/3-02 LED indicator lamp for intrinsically safe circuits, Ex i. Art. No. 237972
LED indicator lamp for front installation for Ex i front installation. Art. No. 240901

Technical Drawings

Output characteristic: A graph shows the relationship between voltage (U) and current (I) for the 9475/32-04-12 output.

Dimensional Drawings: Detailed dimensions in mm [inches] are provided for the module.

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-remote-i-o-is1 -digital-output-module-for-zone-1-ex-i-9475-32-04-12-210651-en-gb-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL Remote I/O IS1+ Digital Output Module for Zone 1 Ex i (9475/32-04-12)
Technical data sheet for the R. STAHL Remote I/O IS1+ Digital Output Module (Art. Nr. 210651), designed for Zone 1 Ex i applications. Details include explosion protection, technical specifications, electrical data, environmental conditions, and accessories.
Preview R. STAHL IS1+ Digital Output Module for Zone 1 Ex i (9475/32-04-12)
Technical data sheet for the R. STAHL IS1+ digital output module (9475/32-04-12), designed for Zone 1 Ex i applications. Details safety, technical specifications, environmental conditions, and accessories.
Preview R. STAHL IS1+ Digital Output Module for Zone 1 Ex i (9475/32-04-12)
Technical data and specifications for the R. STAHL IS1+ digital output module (9475/32-04-12), designed for Zone 1 Ex i applications. This module features 4 Ex i logic outputs with line and error monitoring, LED status indication, and hot-swap capability for Zone 1 replacement. It includes detailed safety values, electrical characteristics, environmental conditions, and mechanical specifications.
Preview R. STAHL Remote I/O IS1+ Zone 2 Power Module 9445/35-12 Technical Data
Technical specifications and features of the R. STAHL 9445/35-12 Remote I/O IS1+ Zone 2 power module, including explosion protection, electrical data, ambient conditions, and mechanical details.
Preview R. STAHL IS1+ Remote Digital I/O Module for Zone 2 Ex i (9470/33-16-10)
Technical specifications and details for the R. STAHL IS1+ remote digital input/output module (9470/33-16-10), designed for Zone 2 Ex i applications. Includes safety data, electrical characteristics, environmental conditions, and accessories.
Preview R. STAHL Remote I/O IS1 Ethernet CPU Module for Zone 1 (9441/12-00-00)
Technical data and specifications for the R. STAHL Remote I/O IS1 Ethernet CPU module (Art. No. 211045), designed for Zone 1 hazardous areas. Includes explosion protection details, technical data, electrical specifications, ambient conditions, mechanical data, and accessories.
Preview R. STAHL Remote I/O IS1 CPU and Power Module for Zone 1 (9440/22-01-11-C1455)
Technical specifications and accessories for the R. STAHL Remote I/O IS1 CPU and Power Module (9440/22-01-11-C1455), designed for Zone 1 hazardous areas. Details include explosion protection, electrical and safety data, mechanical specifications, and compatible accessories.
Preview R. STAHL IS1 Relay Digital Output Module 9477/12-08-12 for Zone 1 Ex d e
Technical specifications and accessories for the R. STAHL IS1 Relay Digital Output Module 9477/12-08-12, designed for Zone 1 Ex d e applications. This module features 8 digital relay outputs with high switching capacity and ATEX/IECEx certifications.