Mircom MPS-800MP(U) Series Fire Alarm Manual Station
Mircom's MPS-800MP(U) Series Fire Alarm Manual Stations provide manual fire alarm activation.
This guide covers these models:
- MPS-810MP: Single Stage, Dual Action, MP Addressable Manual Station
- MPS-810MPU: Single Stage, Dual Action, MP Addressable Manual Station (US)
- MPS-810MPU-EN: Single Stage, Dual Action, MP Addressable Manual Station with Fire Bezel (US)
- MPS-802MP: Two Stage, Dual Action, MP Addressable Manual Station
- MPS-822MP: Two Stage, Dual Action, MP Addressable Manual Station with additional door contacts
Specifications & Dimensions
Compatible with FX-400 series and FleX-Net™ FX-4000 Fire Alarm Control Panels
Electrical Rating:
- Nominal Operating Voltage: 15-30 VDC
- Maximum alarm current: 3.3 mA
- Standby current: 2 mA
Electrical Rating for MPS-822MP maglock terminal:
- 1A at 30VDC
Dimensions:
139 mm H x 104 mm W x 34 mm D (5 1/2" H x 4 1/8" W x 1 3/8" D)
Notes
- Environment: Indoor, dry
- Do not change factory applied finishes.
- Wire as shown so that supervision of connections is maintained.
- Maximum wire size: 14 AWG
- ADA compliant.
- To be installed per ADA 4.27.1 to 4.27.4 inclusive.
- Wiring must be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32 and CAN/ULC-S524, Standard for Installation of Fire Alarm Systems.
- All manual fire alarm stations shall be installed as per the specific requirements outlined in the UL/ULC codes, as well as all other applicable national or local codes. Final acceptance is subject to the local authority having jurisdiction.
- These devices may be operated with a blunt hand (no use of fingers) and do not require a striking action, tight grasping, pinching, or twisting of the wrist. The force required to actuate the devices is less than 22 N (5 lbf).
Install the manual station
Contents of kit
- MPS-810MP, MPS-810MPU, MPS-810MPU-EN: 2 mounting screws, 2 reset keys (black)
- MPS-802MP, MPS-822MP: 2 mounting screws, 2 reset keys (black), 2 stage two keys
A. Open
- Insert the reset key into the reset keyhole and turn it.
- Pull the cover open.
B. Wire
Note: The maximum wire size is 14 AWG.
- Strip wires to 10 mm (25/64") maximum.
- Push the wire into the terminal.
Note: The terminals have a push-in lock. To remove the wire, push the terminal in with the screwdriver and pull out the wire at the same time. See Figure 3.
To remove wire:
- Place a small flathead screwdriver into the groove and push in.
- At the same time, pull the wire out of the terminal.
Wire as shown in Figure 4.
Figure 4: Wiring diagram showing connections. Terminals are labeled: FROM PREVIOUS DEVICE, TO MAGLOCK (MPS-822MP), TO NEXT DEVICE OR LEAVE IT EMPTY, with positive (+) and negative (-) indicators.C. Mount
- Flush mount indoor: Single-gang electrical box.
- Surface mount indoor: BB-800 backbox with or without STI-1230 (Deep Cover without Gasket)
Note: Mount the manual station with the Mircom logo on the bottom.
Figure 5: Back view of the manual station highlighting the mounting holes.D. Set the addressable module
CAUTION: To set the address on this device, disconnect it from the loop, or ensure that the loop to which it is connected is both disconnected from the panel and shorted across both pairs of + and - terminals at the device. Failing to take either of these steps may change the address programming of previously configured sensors on the same loop.
Follow the instructions in LT-6146, the MIX-4090 Device Programmer Installation Manual, available on http://www.mircom.com. If left at its factory setting, the panel will report this device as having no address.
The connector for the device programmer is inside the unit above the addressable module, as shown in Figure 6.
Figure 6: Diagram showing the location of the connector for the device programmer, situated inside the unit above the addressable module.Using the manual station
Activate the alarm
- Push in the push bar.
- Pull down the pull handle.
A qualified person must reset the station by opening it with the reset key. See Reset the manual station below.
Activate the stage two alarm (MPS-802MP and MPS-822MP)
- Insert the stage two key into the stage two keyhole, and then turn the key.
The stage two alarm activates immediately.
Note: The stage two alarm will activate automatically a certain amount of time after the handle has been pulled if no action is taken. This time is set in the Fire Alarm Control Panel.
Reset the manual station
Note: Resetting the station does not cancel the alarm at the panel.
- Insert the reset key into the reset keyhole and turn it.
- Pull the cover open. The switch is now reset.
- Close and lock the station with the reset key.
- Reset the Fire Alarm Control Panel to reset the alarm.