winco 60706-229 ulpss20b2w-a opm
PACKAGED STANDBY SYSTEM
INSTALLATION AND OPERATORS' MANUAL
ULPSS20B2W/A

12270-00



60706-229

SAVE THESE INSTRUCTIONS PROPER USE AND

This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. Read and understand all instructions in the manual before starting and operating the generator set.
USING THE MANUAL
Congratulations on your choice of a Winco generator set. You have selected a high-quality, precision engineered generator set designed and tested to give you years of satisfactory service.

INSTALLATION
You must be sure your new engine generator set is: * Properly serviced before starting. * Operated in a well ventilated area. * Properly exhausted and gases safely dispersed. * Wired by a qualified electrician. * Operated only for its designed purposes. * Used only by operators who understand its operation. * Properly maintained.

To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.

COPY YOUR MODEL AND SERIAL NUMBER HERE

Should you experience a problem, please follow the "Troubleshooting Tables" near the end of this manual. The warranty listed in the manual describes what you can expect from WINCO should you need service assistance in the future.

No other WINCO generator has the same serial number as yours. It is important that you record the number and other vital information here. If you should ever need to contact us on this unit it will help us to respond to your needs faster.

TABLE OF CONTENTS

INTRODUCTION

2

GUIDE TO PRODUCT SAFETY

3

BASIC INFORMATION

Description

4

Specifications

5

PREPARING THE UNIT

Unpacking the Unit

5

ENGINE GENERATOR INSTALLATION

Installation

5

Fuel Installation

6,7

Vapor Fuel Pressure Tables

8

Fuel Conversions

8

Battery Installation

9

Connecting Battery Charger11

TRANSFER SWITCH INSTALLATION

AC Electrical Connections

11,12

DC Electrical Connections13

INITIAL START UP

13,15,16

DSE 3110 ENGINE CONTROL14

ASCO 185 SEQUENCE OF OPERATION18

FRONT PANEL CONFIGURATION19

DSE 3110 FAULT CODES

20

MAINTENANCE

21

GENERATOR SET OUTLINE

22

GENERATOR SET PAD LAYOUT

23

TROUBLESHOOTING TABLES

24

AC & DC SCHEMATIC

25

AC SCHEMATICS

26,27

12 MONTH WARRANTY

28

MODEL__________________________________ SERIAL NUMBER_________________________ PURCHASE DATE_________________________ DEALER_________________________________ DEALER PHONE # ________________________

12270-00



60706-229

SAFETY INFORMATION
This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
ANSI SAFETY DEFINITIONS
***********************************************************
DANGER:
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations. ***********************************************************
***********************************************************
WARNING:
WARNING indIcates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ***********************************************************
***********************************************************
CAUTION:
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. ***********************************************************
NOTE:
CAUTION is also used on the unit labels and in this manual to indicate a situation that could result in serious damage or destruction of the equipment and possible personal injury.
1. ELECTRICAL SHOCK The output voltage present in this equipment can cause fatal electric shock. This equipment must be operated by a responsible person.

2. FIRE HAZARD Natural gas and L.P. present a hazard of possible explosion and/or fire.
a. Keep fuel containers out of reach of children. b. Do not smoke or use open flame near the gen-
erator set or fuel tank. c. Keep a fire extinguisher nearby and know its
proper use. Fire extinguishers rated ABC by NFPA are appropriate. d. Store fuel only in an approved container, and only in a well ventilated area. e. Follow local codes for closeness to combustible material.
3. DEADLY EXHAUST GAS Exhaust fumes from any gasoline engine contain carbon monoxide, an invisible, odorless and deadly gas that must be mixed with fresh air.
a. Operate only in well ventilated areas. b. Never operate indoors. c. Never operate the unit in such a way as to
allow exhaust gases to seep back into closed rooms (i.e. through windows, walls, floors).
4. NOISE HAZARD Excessive noise is not only tiring, but continual exposure can lead to loss of hearing.
a. Use hearing protection when working around this equipment for long periods of time.
b. Keep your neighbors in mind when permanently installing this equipment.
5. CLEANLINESS Keep the generator and surrounding area clean.
a. Remove all grease, ice, snow or materials that create slippery conditions around the unit.
b. Remove any rags or other materials that could create a potential fire hazard.
c. Carefully clean up any gas or oil spills before starting the unit.
6. SERVICING EQUIPMENT All service, including the installation or replacement of service parts, should be preformed only by a qualified technician.

a. Do not allow anyone to operate the generator without proper instruction.
b. Guard against electric shock. c. Avoid contact with live terminals or receptacles. d. Use extreme care if operating this unit in rain
or snow. e. Use only three-pronged grounded receptacles
and extension cords. f. Be sure the unit is properly grounded to an
external ground rod driven into the earth.

a. Use only factory approved repair parts. b. Do not work on this equipment when fatigued. c. Never remove the protective guards, covers, or
receptacle panels while the engine is running. d. Use extreme caution when working on electri-
cal components. High output voltage from this equipment can cause serious injury or death.

12270-00



60706-229

e. Always avoid hot mufflers, exhaust manifolds, and engine parts. They can cause severe burns instantly.
f. Installing a generator set is not a "Do-it-yourself" project. Consult a qualified, licensed electrician or contractor. The installation must comply with all national, state, and local codes.
TESTING POLICY
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current and frequency are carefully checked.
Rated output of generator is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of the applicable engines.
INTRODUCTION AND DESCRIPTION
The package standby system is designed to automatically provide standby power to unattended loads during electrical outages. Upon interruption of normal electrical service, the packaged standby system electrical control circuits will automatically start the engine. The generator will produce electrical power and the Automatic Transfer Switch (ATS) will automatically transfer the electrical loads to the engine-generator set. Upon restoration of normal electrical service the emergency transfer switch will sense return of the normal commercial power. The Automatic Transfer Switch will transfer the load back to the normal commercial power source. The engine control circuits will begin a cool-down cycle, after which the fuel supply will be shut off and the engine ignition system disabled.

These packaged standby systems consist of two major components:

1. AUTOMATIC TRANSFER SWITCH

A wall mounted ASCO 185 Automatic Transfer Switch (ATS) designed for inside or outside installation. The transfer switch is UL1008 approved. A seven day electronic exerciser circuit is installed in the ATS as standard equipment. The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set. The transfer switch is also equipped standard with a 3 second start delay, and a 10 second transfer delay to allow the engine to warm up before transferring the load to the generator. When the line power is restored the ATS has a 5 minute transfer delay to allow the incoming utility to stabilize before transferring back to line power and then an additional 2 minute engine cool down delay before the engine shuts down. Read and understand the ATS owners manual before installing, servicing or operating the transfer switch.

UL Automatic Transfer Switch Sizes

UNIT

LINE SIDE GENERATOR

CONTACTOR SIDE CONTACTOR

ULPSS15B2W 100 AMPS100 AMPS

200 AMPS 200 AMPS

Both the 100 amp and the 200 amp UL Switches are available in single phase only.

2. ENGINE / GENERATOR
The engine generator set consists of a Briggs and Stratton, twin cylinder, four cycle air cooled engine, model 613277-0161-B1. The engine is factory equipped to run on LP or NG fuel. The engine operates at 3600 rpm and frequency regulation is maintained by the engine governor within 4 cycles variation (62.5 Hz - 58.5 Hz) from no load to rated load. The generator is a brushless, single bearing, direct drive, rotating field design. The generator is connected to the engine's tapered (quill) crankshaft extension. The engine generator is mounted in a drip-proof enclosure for outside installation. Connection boxes and terminal blocks are provided for all customer connections (both AC output and DC control). A customer supplied 12 volt 500 CCA (BCI group 26) battery is required to complete the installation.

** NOTICE **

This unit will automatically transfer if a power outage occurs while running in an exercise mode.

12270-00



60706-229

SPECIFICATIONS

GENERATOR

FUEL LP NG

WATTS* VOLTS AMPS HZ PH RPM 17000 120/240 70.8 60 1 3600 15000 120/240 62.5 60 1 3600

* Continuous Rating. * Derate 3.5% per 1000 feet elevation above sea level.

"Concealed Damage" is understood to mean damage to the contents of a package which is not evident at the time of delivery by the carrier, but which is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in transit. The title to goods rests with the consignee when generators are shipped F.O.B. factory, and only the consignee can legally file a claim. Please note, most carriers have a time limit for filing concealed damage claims.
**** CAUTION ****

FUEL CONSUMPTION

NATURAL GAS 1000 BTU/CU FT

CF/HR*

328

BTU/HR*

328,000

GAL/HR*

N/A

LP VAPOR 2520 BTU/CU FT
130.5 329,000
3.61

* Based on full load operation.

LP TANK SIZING
Required LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit (Celsius).

TANK TEMPERATURE 60° F (16° C) 32° F (0° C) 0° F (18° C) -20° F (-29° C)

TANK SIZE 150 GALLON 250 GALLON 500 GALLON 1000 GALLON

These units are shipped with oil. Be sure to check oil levels before operating. See engine manufacturer's instruction manual for recommended oil requirements before initial starting.
UNPACKING
1. Carefully remove the carton. 2. After inspecting the engine-generator and trans-
fer switch for external physical damage, check for the following items packed inside the carton. a. Owner's manual. b. Engine manufacturer's instruction manual. 3. Remove main frame hold down bolts. (4) 4. Unit can now be lifted from shipping pallet.
INSTALLATION
General Information
****************** ***** WARNING *****
****************** Before proceeding with the installation be sure the operation selector switch is in the stop position.

ENGINE SPECIFICATIONS
Refer to engine operating and maintenance instructions.
** NOTICE **
When unpacking the generator set, be sure to inspect it carefully for freight loss or damage. If loss or damage is noted at the time of delivery, require that the person making the delivery make note of the loss or damage on the freight bill, or affix his signature under the consignor's memo of the loss or damage. Contact the carrier for claim procedures.
When loss or damage is noted after delivery, segregate the damaged material, and contact the carrier for claim procedures. Be sure to retain the packaging material for carrier inspection.

These engine generator sets are designed to be mounted on a concrete pad outdoors only. As an option, a prefab pad may be used as long as proper attention is paid to site preparation to ensure the unit will not move after installation. The transfer switch is mounted next to your electrical entrance or distribution panel inside or outside the building. Consult a qualified, licensed electrician or contractor to install and wire the transfer switch. The installation must comply with all national, state and local codes.
Before beginning the installation process check the rating of the generator set and its transfer switch rating. Be certain they can handle the intended load and are compatible with the entrance voltage, phase and current ratings. Plans for installation should be prepared with proper attention to mechanical and electrical engineering detail to assure a satisfactory system installation. The information in this manual is offered only as a guide to finalizing your installation plans.

12270-00



60706-229

ENGINE GENERATOR SET MOUNTING
WARNING - Personal Injury
The enclosures on these units can become very hot adjacent to the exhaust areas. Special care must be taken when installing these units to insure that the risk of contact by people is minimized.
The unit's main frame should be bolted to a four to six inch thick cement pad. The engine-generator is mounted on a sub-frame which is isolated with special shock mounts on the main frame. This allows the engine-generator to vibrate without affecting the control panel on the main frame. (See page 23).
Do not install any shock mounts between the base frame and the concrete pad. Engine vibration will be transmitted to the control panel causing erroneous start/stop cycles and premature control failure.

These fuel pressures are critical; failure to provide the proper pressure can cause many problems ranging from a unit that will not start to causing damage to the fuel system.
These units are normally tested on Natural Gas and will have a tag hanging on the fuel hose indicating on what fuel your unit was factory tested. If you are running on LP or have to change fuel types at any time, see information on page 8 on NG/LP CONVERSION.
INSTALLING THE FUEL LINE
** NOTICE ** The engine generator sets are properly adjusted before they leave the factory. A tag is attached to the unit that specifies the fuel, natural gas (NG) or propane vapor (LP) that the unit was set up and tested on.

These units should be mounted a minimum of 24" from a structure. This will allow for ample room to maintain and work on the generator set. Units must be installed in accordance with all local, state, and national codes. Consult your local agency having jurisdiction for specific requirements.
FUEL INSTALLATION

NATURAL GAS or LP VAPOR PIPE SIZE
Size of pipe normally required for generators operating on NATURAL GAS or LP VAPOR.
Unit location will determine the size of fuel line that is required to supply the engine with a constant fuel pressure and volume.

The fuel supply should be as close as possible to the engine. This will reduce the installation cost of fuel runs. The information in this manual is offered to assist you in providing the proper fuel for your engine. However, this information is only provided to inform you of the engine's requirements and assist in making you aware of the decisions you must make. In no case should the instructions and information provided be interpreted to conflict with any local, state or national codes. If in doubt, always consult your local fire marshal, gas supplier or building inspector.
****************** ***** WARNING *****
******************
FIRE HAZARD - All fuel runs should be installed by a licensed fuel supplier.
To connect the fuel line to the generator set you will connect your incoming fuel line to the 3/4 inch NPT fitting located on the left side of the engine-generator set. This fitting is shipped with a plastic plug installed to insure the fuel system stays clean.
For all vapor fuel systems the delivery pressure of the fuel to the fuel solenoid on the unit must be four to six ounces psi (per square inch) or 7 to 11 inches W.C. (water column).

LIQUID PROPANE VAPOR (LP)
Refer to the tables on the following pages for fuel line size and recommended tank size. For distances of 100 feet or over, a two regulator fuel system is recommended. This is accomplished by installing a primary regulator at the tank which will reduce the tank pressure down to 10 to 15 lbs.
A low pressure regulator is installed to further reduce the fuel pressure to the required four (4) to six (6) oz. operating pressure. This low pressure regulator must be at least 10 feet from the engine generator set; any closer installation will require a larger line be installed to provide a fuel reservoir. This is also true for the single low pressure regulator, it should also be a minimum of 10 feet from the unit. If this is not done, the demand regulator on the unit and the pressure regulator in the fuel line will interfere with each other. When the two (2) regulator system is used on LP, a fuel line size of 1/2 to 5/8 inch is generally adequate for distances up to 300 feet from the primary to the low pressure regulator. (Consult you local fuel supplier for your exact requirements). The appropriate line size from the table below is then installed from the low pressure regulator to the generator set.

12270-00



60706-229

FEET up to 25 FT* 25 - 100 FT* over 100 FT*

SIZE OF PIPE 3/4 " Pipe 1" Pipe
Use a two regulator system.

* Allow an additional 3 feet for each standard elbow. Do not use `street ells' (restrictive).

NATURAL GAS (NG)

The primary regulator (fuel meter) on the building should deliver the correct volume and pressure to the generator set. This regulator must be sized to deliver the required BTU's to the generator set and all other appliances in the building. If the primary regulator (fuel meter) is a high pressure regulator, then a low pressure regulator must be installed to bring the pressure down to 4-6 oz. (7-11 inches water column) of pressure. This low pressure regulator must be at least 10 feet from the engine generator set; any closer installation will require a larger line be installed to provide a fuel reservoir. If this is not done, the demand regulator on the unit and the pressure regulator in the fuel line will interfere with each other. This regulator must be sized to accommodate the demand of the generator set and any other appliance connected to it. See table below for the correct size of pipe to be installed.

FUEL PRESSURE
LP & NG VAPOR FUEL Correct fuel pressure cannot be stressed enough. The most common cause for inoperative systems is an inadequate or incorrect fuel pressure. Performance of the engine is in direct relation to the correctness of the fuel system. Shown below is a diagram of a typical LP vapor fuel installation. Notice the following tables give two (2) different units of measuring fuel pressure. The first and most accurate is the use of a simple water manometer. A manometer is calibrated in inches of water column. The second is with a pressure gauge calibrated in ounces per square inch.
Reference numbers 1 through 3 in the diagrams above are system parts supplied by the customer.

FEET up to 25 FT* 25 - 100 FT* over 100 FT*

SIZE OF PIPE 3/4 " Pipe 1" Pipe
Consult Factory

Reference number 4 is on the generator.

* Allow an additional 3 feet for each standard elbow. Do not use `street ells' (restrictive).

****************** ***** WARNING *****
****************** PERSONAL DANGER - Do not use galvanized pipe in fuel line runs. The galvanized coating can become eroded and flake off, causing possible obstructions in the regulator or fuel valve. The results could range from inoperative engine to hazardous fuel leaks.

**** CAUTION ****

Be careful when sealing gas joints. Excessive sealing compound can be drawn into the solenoid, regulator or carburetor causing an engine malfunction.

12270-00



60706-229

Shown below is a diagram of a natural gas (NG) installation.

LP TANK SIZING
Required LP tank size for LP Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit (Celsius).

TANK TEMPERATURE 60° F (16° C) 32° F (0° C) 0° F (18° C) -20° F (-29° C)

TANK SIZE 150 GALLON 250 GALLON 500 GALLON 1000 GALLON

Reference numbers 2 through 4 in the diagram above are system parts supplied by the customer. Reference number 4 is on the generator.

Below are tables of the fuel pressure readings at each reference in the system.

FUEL PRESSURE TABLES

Single Low Pressure Regulator (LP Vapor only)

REF #

1

3

4

UNIT OFF LINE PSI

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

STARTING LINE PSI

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

NO LOAD LINE PSI

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

FULL LOAD

LINE PSI

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

NG/LP FUEL CONVERSION
These generator sets are factory tested on Natural Gas and will require no modifications for normal operation on Natural Gas. The carburetion system has been preset and anti-tamper plugs have been installed in the carburetor as required by the EPA.
To make a fuel conversion you will have to first remove the left side door. Looking down to your left you will see a decal and a plug. Remove the plastic plug with a screwdriver. Using a 5mm or 3/16" hex allen wrench turn LEFT about 1/4 turn until you feel a click and it will stop turning.
No other modifications to the unit are necessary. To switch from LP to NG you turn the selector to the right (NG) position.

Two (2) Regulator System (LP Vapor only)

REF #

1

2

3

4

UNIT OFF

LINE PSI

10-15 LBS

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

START- LINE PSI 10-15

ING

LBS

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

NO LINE PSI 10-15

LOAD

LBS

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

FULL LINE PSI 10-15

LOAD

LBS

7-11 IN 4-6 OZ

7-11 IN 4-6 OZ

Natural Gas REF #
UNIT OFF
STARTING
NO LOAD
FULL LOAD

2 2 PSI 2 PSI 2 PSI 2 PSI

3
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ

4
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ
7-11 IN 4-6 OZ

12270-00



60706-229

INSTALLING THE BATTERY

**** CAUTION ****

In the following battery installation procedure, check to be sure the selector switch remains in the "off" position. This should be your last step before initial start-up.

A customer supplied twelve-volt battery is required to complete the installation. Installation of the highest CCA rated battery, within the correct BCI group (size), will increase cold weather starting performance. Gel batteries should not be used with the battery tender installed in the generator enclosure.

Model

Voltage BCI Group MINIMUM

CCA Rating

ULPSS20B2W 12

26

500

Installation and servicing of batteries must be performed or supervised only by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When installing or replacing batteries, use the proper group/size starting battery. The battery should be a Maintenance Free lead acid design. Deep cycle batteries will not work for this application.

WARNING - The electrolyte is a diluted sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following precautions must always be taken.
* Always wear full eye protection and protective clothing.
* Where electrolyte contacts the skin, wash off immediately with water.
* If electrolyte contacts the eyes, flush thoroughly and immediately with water and seek immediate medical attention.
* Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of one pound of bicarbonate of soda (baking soda) to one gallon of water. The bicarbonate of soda solution is to be added until the evidence of reaction, foaming, has ceased. The resulting liquid is to be flushed with water and the area dried.
DANGER - Explosive Fire Risk
* Never smoke when near batteries. * Do not cause a flame or spark in the battery area. * Always discharge static electricity from your body
before touching batteries by first touching a grounded metal surface.

CAUTION - PERSONAL DANGER

SERVICING BATTERIES

CAUTION - NEVER dispose of a battery in a fire. The battery is capable of exploding.
CAUTION - DO NOT open or mutilate the battery. Released electrolyte is known to be harmful to the skin and eyes and to be very toxic.
These generator sets are all NEGATIVE ground. Be very careful not to connect the battery in reverse polarity, as this may short circuit the battery charging system on the engine.

Batteries used on these units may over time lose water. This is especially true if you are using a trickle charger to maintain your battery. When refilling the battery with water, use only distilled water. Tap water will shorten the service life of the battery.
Never fill the battery above the fill line. Over filling above the upper level line may cause the electrolyte to overflow, resulting in corrosion to the engine or nearby parts. Immediately wash off any spilled electrolyte following the procedure above.

CAUTION - A battery presents a risk of electrical shock and high short circuit current. The following precautions must be observed when working with batteries.
1. Remove watches, rings and other metal objects. 2. Use tools with insulated handles. 3. Check both the battery cable ends and the bat-
tery posts to be sure they are free of corrosion. 4. Always connect the battery positive cable first
and then connect the battery negative cable. When removing the battery cables from the battery, reverse the procedure and disconnect the negative cable first and then the positive cable. 5. Be sure all connections are tight and coat the terminals and cable ends with dielectric grease.

BATTERY CHARGING
Units equipped with electric start have a small flywheel charger built into the engine flywheel assembly for recharging the starting battery. This flywheel charger generates a small AC current that passes through a rectifier/regulator assembly on the engine to produce a DC charging current. This circuit is not designed to be used as a battery charging circuit to recharge dead batteries.

12270-00



60706-229

12270-00

10

60706-229

**** CAUTION ****
EQUIPMENT DAMAGE - Always connect the positive cable first and the negative cable last. When disconnecting, remove the negative cable first and the positive cable last. Failure to connect and disconnect in the proper sequence can cause equipment damage.
Observe polarities: connect the positive (+) battery terminal to the (+) cable from the engine starter; the negative (-) battery terminal is connected to the negative cable (ground) from the engine generator assembly. All connections must be clean and tight. Check the electrolyte (fluid) in the battery periodically to be sure it is above the plates. Never allow the battery to remain in a discharged condition.
**** CAUTION ****
EQUIPMENT DAMAGE - NEVER JUMP START these units. Doing so will destroy the engine control module, rendering the unit non-operational. Remove and fully recharge the battery before attempting to start.
CONNECTING THE BATTERY CHARGER
A two-stage battery tender is provided on all PSS series generators. This battery tender charges at a rate of 750 mA until the battery is fully charged and then automatically switches to a 13.2 VDC float charger. The charger has an indicator light on it. Red indicates it is charging, and green indicates it is in the storage mode (float charge). This charger is mounted on the generator set which is located behind an access cover in the rear of the unit.
The battery tender receptacle is to be powered by a GFCI circuit and installed in accordance with the United States National Electric Code. These AC wires can be run in the same conduit as the other AC leads from the generator. It is suggested that this circuit be fused for 15 amps. Terminal block connections have been provided in the customer connection area of the engine generator set. See Page 10 for diagram.
** NOTICE **
The battery tender is not intended to recharge a battery which has become completely discharged. It is designed to produce enough current to recharge a slightly low battery and maintain a fully charged battery.

MOUNTING THE AUTOMATIC TRANSFER SWITCH (ATS)
****************** ***** WARNING *****
****************** EQUIPMENT DAMAGE - Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the switch. Contactors returned for warranty consideration with foreign materials inside of them will not be warranted.
Before installing the ATS you must first ensure that the transfer switch is large enough to handle your complete distribution panel. If you are installing a 100 amp transfer switch, the main line circuit breaker must not be larger than 100 amps. If you have a 125, 150, 200 amp or larger system and want to use a 100 amp transfer switch, you will not be able to transfer the complete electrical system. In this case it will be necessary to install a secondary emergency distribution panel.

AC ELECTRICAL CONNECTIONS

NOTICE - CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A CLASS 2 CIRCUIT.

****************** ***** WARNING *****
******************

A main line circuit breaker has been provided inside the generator housing. During all wiring installation, make sure the breaker is in the off position and the generator operators switch is in the off position.

Note: This symbol ground where used.

always indicates

GENERATOR CONNECTIONS

Minimum conductor sizes between the generator and the ATS. Based on wire type and temperature rating. Wire has been derated for 40° C ambient temperatures.

12270-00

11

60706-229

WIRE TEMPERATURE RATING
CU Connector

AL Connector

The ground leads from all locations are connected to the grounded terminal lugs also located on the side wall. This set of terminals is labeled "GROUND".

75° C 90° C

# 2 AWG # 3 AWG

# 1/0 AWG # 2 AWG

To gain access to the customer connections, remove the end door panel opposite the muffler. All AC and DC connections to the ATS, 120 Volt power connection for battery charger, and battery installation are made behind this panel. See pages 22 and 23 for generator set and pad layout.

Two (2) hot leads, one (1) neutral and (1) ground lead are required between the generator and the ATS or distribution panel. The two power leads from the generator are marked G1 and G3. Next install two leads, one neutral and one ground, from the generator set to the ATS or distribution panel.

In addition to the power leads, install a three wire 120 volt, 15 amp circuit from your distribution panel to the generator. This circuit will be used to power the battery charger, optional block heater and optional battery heater.

The last two wires you will install are the DC control leads (14 or 16 gauge) for the start circuit in the ATS. These connections will be discussed later in more detail.

WINCO UL ATS (ASCO 185)

See the ASCO installation manual for additional details on proper wiring of the Automatic Transfer Switch.

INSTALLATION NOTES
The load current carrying wires (L) and (T) must be sized to handle the maximum load current without excessive voltage drop. By code, the wire must be heavy enough to handle the full current rating of the main line circuit breaker (or fuse) in the entrance (or sub-panel) protecting the contactor switch.
All wires should be installed in rigid or flexible conduit. Because of the many different types of service, feeder, and distribution equipment, no specific wiring instructions can be provided. It is, however, recommended that copper wire be used. In all cases it is essential that while the load is connected to the generator, there can be absolutely no feedback from the generator to the power line or the power line to the generator. When properly installed, the normal ATS control and safety systems will eliminate all paths for feedback. Check with your local electrical inspector on applicable local, state and federal codes.
****************** ***** WARNING *****
******************
A service disconnect must be installed in front of the ATS panel as the ATS is not service entrance rated. This will allow you to test the generator under load. Should you ever have to work on the switch, you will be able to disconnect the power and work on the switch cold without having the power company pull your meter.

The standby generator terminals in the ATS are marked "ALTERNATE L2 & L6". The "hot" leads G1 and G3 from the generator are connected to the terminals L2 & L6.
The normal line power terminals in the ATS are marked "PREFERRED - L1 & L5". The "hot" line power leads are L1 and L3 from the utility power supply. They are connected to terminals L1 and L5.
The load terminals in the ATS are marked "LOAD - L3 & L7". The leads to the load distribution panel are connected to terminals L3 & L7.
The neutral leads from all three locations are connected to the isolated terminal lugs on the sidewall of the cabinet. This terminal block is labeled "NEUTRAL" and the terminal lugs are mounted on red isolation standoffs.

To wire the automatic transfer switch into the existing wiring, first determine which circuits will be on the emergency load circuit. If the entire load is to be transferred, the transfer switch can be wired in directly after the watt-hour meter and the service entrance, providing the service entrance ampere rating is within the transfer switch's rated capability.
If only specific circuits are to be powered under emergency power failure conditions, an additional distribution panel designated "emergency distribution panel" must be installed.
All selected emergency circuits are removed from main distribution panels and reinstalled in the emergency distribution panel. Suggested circuits: freezer, refrigerator, furnace, emergency lights, sump pump, emergency outlet circuits, etc. Total running load must not exceed generator rating.

12270-00

12

60706-229

DC ELECTRICAL INTERCONNECTION
**** CAUTION ****
Never run the AC and DC wiring in the same conduit.
ASCO 185 UL SWITCH
Your DC connection points in the ASCO 185 UL ATS are on the terminal block on the bottom of the controller in the lower left hand corner of the ATS panel. The terminal block (TB7) is numbered 1 through 9. These terminals will accept # 22 - # 14 AWG stranded wire. It is recommended that you use # 16 AWG for distances up to 200 feet. You need to run two (2) wires from the engine generator set to the transfer switch. You will be using terminals 4 and 5, wire Start # 23 will connect to terminal # 5 and wire Battery Negative # 1 will connect to terminal # 4. See table and illustration below.

WIRE #
# 23 # 1

PURPOSE
Start Battery Negative

RECOMMENDED COLOR
Black
White

INITIAL START UP
****************** ***** WARNING *****
****************** DO NOT jump start these engine generator sets. Starting these units on a low battery of jump starting them will cause damage to the engine control module.
Use the following checklist to verify correct installaion before starting the engine:
 Engine oil.* Check level & fill as required with proper grade/quantity.
 Unit mounting base properly bolted down.  Clearance for service and maintenance on all
sides.  Proper fuel line material and size.  All fuel line connections tight.  Fuel line protected and a moisture trap in
stalled (may be required for NG).  LP/NG pressure OK. 4-6 oz. (7-11 in. WC).  Battery connections clean and tight.  Battery fully charged.  All AC and DC wiring installed and properly
protected. * Refer to engine owners manual for proper
levels and types.

After completing the above checklist, the engine generator set is ready for the initial start-up test.

12270-00

225 S. CORDOVA AVE. LECENTER, MN 56057 507-357-6821 SERVICE DEPT. 507-357-6831
13

60706-229

DSE 3110 CONTROL

STOP/RESET (Red Button) This button places the module into its "Stop/ Reset" mode. This will clear any alarm conditions for which the triggering criteria have been removed. The fuel supply de-energizes and the engine comes to a standstill. Should a remote start signal be present while operating in this mode, a remote start WILL NOT occur.

AUTO (White Button) This button places the module into its "Automatic" mode. This mode allows the module to control the function of the generator automatically. The module will monitor the remote start input and once a start request is made, the set will be automatically started and placed on load. The module will then wait until the next start event.

START (Green button) Pressing this button from STOP/RESET will start the engine and run off load.

2270-00

PAGE Pressing this button scrolls the display to show the various instruments.

4

60706-229

START UP PROCEDURE
Engine Generator Set only

With the engine running smoothly, check the no load voltage and frequency at wire # 1 and # 4 (L2 and

The engine control module (ECM) is manufactured by Deep Sea Electronics. Model 3110 is used on this engine generator set. See picture below. Additional information on the DSE 3110 is on pages 14, 19-21.

L6 in the ASCO ATS) on the generator terminal block in the ATS. The voltage should be 240 volts plus or minus nominal. The frequency should be between 61.5 to 62 hertz (Hz). The voltage should also be checked between the hot terminals (L2 and L6) and the neutral to be certain of a balanced voltage output

Manual Operation Press and release the red Stop/Reset button. Then press and release the green Start Engine button.

and a solid neutral connection. The voltage should be about one half of the line to line voltage. See picture below for frequency adjustments.

The engine generator will crank and start automatically. If the engine fails to start see Fault Codes on page 20 to correct the problem before proceeding.

** NOTICE ** If for any reason during the check out procedures the voltage and frequency are not correct, press the

red Stop/Reset button and correct the trouble before

proceeding.

After verifying the voltage and frequency are correct, press the Stop/Reset button. This will shut off the engine immediately.

BEND THIS TAB TO CHANGE THE ENGINE SPEED (FREQUENCY). STRETCHING SPRING INCREASES THE FREQUENCY (INCREASES ENGINE SPEED). RELAXING SPRING DECREASES THE FREQUENCY (DECREASES ENGINE SPEED).

12270-00

15

60706-229

Transfer Switch & Engine Generator

DESCRIPTION

Automatic (remote) Operation This procedure checks the electrical operation of the automatic transfer switch. If the actual operation does not follow this procedure, consult the troubleshooting section in the transfer switch manual.
1. Turn on the preferred source (utility) circuit breaker. The Utility Acceptable Light should now come on, as well as the Load On Utility Light. If these lights fail to come on, recheck your incoming power to insure you have 240 volts nominal. If not, troubleshoot your utility source before continuing.

The digital controller provides sensing, timing, and control functions for the ATS. This micro-processorbased controller includes built-in control buttons and status lights for control of the ATS and the generator.
PUSH BUTTONS
On the front control display are three push buttons that control the operation of the generator and the ATS.
**** CAUTION ****

2. Press and release the Auto button on the engine control module (ECM). The auto mode icon will appear on the screen. The unit is now ready to be operated from the Automatic Transfer Switch.
3. Turn on the alternate source (generator) circuit breaker.
****************** ***** WARNING *****
******************
PERSONAL INJURY HAZARD - Install front cover in transfer switch before operation. An electrical system fault could cause a flash and severe personal injury.
ASCO 185 DIGITAL CONTROLLER

Before using the transfer test button, be sure that conditions are safe for running the generator and for load transfer
TRANSFER TEST Use this button to test the system. This operation starts the generator and transfers the load. The controller is shipped with a load transfer set by default. Changing the exercise without a load will be discussed later. Be sure that conditions are safe to do this operation.
BYPASS TIME DELAY Use this button to cancel the active time delay or exercise period (stops the generator after cooldown).
SET ENGINE EXERCISER Use this button to set the automatic exerciser.
INDICATOR LIGHTS

On the front control display are five lights that indicate the status of the sources and the ATS.

UTILITY ACCEPTABLE This light indicates that the utility voltage is acceptable for connection to the load.

GENERATOR ACCEPTABLE This light indicates that the generator voltage and frequency is acceptable for connection to the load.

LOAD ON UTILITY This light indicates that the generator voltage is acceptable for connection to the load.

LOAD ON GENERATOR This light indicates that the generator voltage and frequency is acceptable for connection to the load.

12270-00

16

60706-229

AUTOMATIC GENERATOR EXERCISER

SETTING THE EXERCISER CIRCUIT

This light indicates the status of the generator exer- Press and hold (5 seconds) the Set Engine Exer-

ciser:

ciser button. The exercise period occurs immedi-

ately and at the same time weekly thereafter. The

- Blinks during the exercise period (including cool status light below the button blinks during the exer-

down).

cise period (including the cooldown). The light stays

- stays on when the exerciser has been set.

on to indicate that the exerciser has been set. If the

light is off, the exerciser has not been set.

- is off when the exerciser has not been set.

CANCELLING AN ACTIVE EXERCISE PERIOD

GENERATOR STARTING CONTACTS

Press the Bypass Time Delay button to stop an

Disconnect the generator battery. Connect the

exercising generator. If exercise with load is set, the

generator starting wires # 1 (battery -) to terminal 4 ATS retransfers the load to the utility, then stops the

and wire # 23 (start) to terminal 5 of the TB7 terminal generator after cooldown.

block. This is removable for convenient connections.

******************

***** WARNING *****

******************

WITH A TOTAL POWER FAILURE (UTILITY POWER FAILS AND THE GENERATOR FAILS TO START AND RUN) THE EXERCISER MUST BE RESET AFTER THE POWER IS RESTORED.

SETTINGS

GENERATOR EXERCISER CIRCUIT
The automatic generator exerciser is configured to automatically exercise the generator for 20 minutes once every week.
In order to set and test the exercise circuit the AUTO button on the generator control panel must be on.
EXERCISE WITH OR WITHOUT LOAD

The ASCO 185 has settings that can be changed for various applications. The dipswitch options are explained in the ASCO 185 Operator's Manual.
SEE THE FOLLOWING PAGE FOR SEQUENCE OF OPERATION.
This completes your installation and unit testing. ALWAYS leave the system in automatic mode unless servicing the unit. For automatic operation, the auto mode icon must be displayed on the engine control module display.

The transfer switch can be set up to exercise the generator with or without a load transfer. Normally Winco generators exercise without a load transfer. This is because you may not wish to have a momentary interruption of power. Turn the exerciser dipswitch on. Then set the "with load" or "without load" dipswitch. See table below.

Function clock battery

Factory Setting
off

exerciser

off

with load or without load

without load

DIP Switch
S2
S1
S1

DIP Actuator
10
7
8

Actuator Position
on (up) off (down)
on (up) off (down)
with (up) without (down)

12270-00

17

60706-229

12270-00

18

60706-229

FRONT PANEL CONFIGURATION
This configuration mode allows the operator limited customizing of the way the module operates. Use the module's navigation buttons to traverse the menu and make value changes to the parameters.
1

2

4

3

. ACCEPT button.

2. NEXT PAGE button.

3. DECREASE VALUE / NEXT ITEM

4. INCREASE VALUE / NEXT ITEM

ACCESSING THE FRONT PANEL

Press  (accept) and 2 (next page) simultaneously (at the same time). This display

shows the configuration icon:

The first parameter is also displayed.

EDITING A PARAMETER

Enter the editor as described above.

* Press 2 to select the required `page' as detailed below.

* Press 4 to select the next parameter or 3 to select the previous parameter within the

current page.

* When viewing the parameter to be changed, press the  button. The value begins to

flash.

* Press 4 or 3 to adjust the value to the requested setting.

* Press  to save the current value. The value stops flashing.

* Press and hold the  button to exit the editor, the configuration icon

is removed

from the display.

NOTE: Values representing pressure will be displayed in Bar. Values representing temperature are displayed in degrees Celsius. NOTE: When adjusting values in the front panel editor, a "press and hold" of the increment button will cover the full range of the item being adjusted (min to max) in under 20 seconds. NOTE: When the editor is visible, it is exited after 5 minutes of inactivity for security.

2270-00

9

60706-229

DSE 3110 CONTROL FAULT CODES

DESCRIPTION
AUXILIARY INPUTS
FAIL TO START

Auxiliary inputs can be user configured and will display the message as written by the user.
The engine has not fired after the preset number of start attempts.

FAIL TO STOP

The module has detected a condition that indicates that the engine is running when it has been instructed to stop.
NOTE:- `Fail to Stop' could indicate a faulty oil pressure sensor - If engine is at rest, check oil sensor wiring and configuration.

The module detects that the engine oil pressure has fallen

LOW OIL PRESSURE below the low oil pressure pre-alarm setting level after the

C

Safety On timer has expired.

ENGINE HIGH OIL TEMPERATURE D

The module detects that the engine oil temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired.

UNDERSPEED
OVERSPEED
BATTERY UNDER VOLTAGE / BATTERY OVER VOLTAGE GENERATOR UNDER VOLTAGE
GENERATOR OVER VOLTAGE
GENERATOR UNDER FREQUENCY

The engine speed has fallen below the underspeed pre alarm setting
The engine speed has risen above the overspeed pre alarm setting
The DC supply has fallen below or risen above the low/ high volts setting level.
The generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On timer has expired.
The generator output voltage has risen above the pre-set pre-alarm setting.
The generator output frequency has fallen below the pre-set pre-alarm setting after the Safety On timer has expired.

GENERATOR OVER FREQUENCY

The generator output frequency has risen above the preset pre-alarm setting.

12270-00

20

60706-229

DSE 3110 ENGINE CONTROL
PROTECTIONS
When an alarm is present, the Common alarm LED (if configured) will illuminate. The LCD display will show an icon to indicate the failure.
WARNINGS Warnings are non-critical alarm conditions and do not affect the operation of the generator system; they serve to draw the operators attention to an undesirable condition. Warning alarms are self-resetting when the fault condition is removed. The icon will appear steady in the display.
SHUTDOWNS Shutdowns are critical alarm conditions that stop the engine and draw the operator's attention to an undesirable condition. Shutdown alarms are latching. The fault must be removed and the STOP/RESET button pressed to reset the module. The icon will appear flashing in the display.
MODULE DISPLAY
TIMER ICON When the module is controlling the engine (starting and stopping), an animated timer icon will be displayed in the icon area to indicate that a timer is active. For example, cranking time, crank rest, etc.
STOPPED ICON When there are no alarms present, an icon will be displayed to indicate the engine is stopped and what mode the unit is in.

PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and Automatic Transfer Switch.
***************** ***** WARNING *****
*****************
When performing any type of maintenance on this equipment, make sure the selector switch on the engine generator is in the off position. If you are working in the Automatic Transfer Switch, confirm with a reliable meter that all power has been disconnected.
AUTOMATIC TRANSFER SWITCH
Clean and inspect the switch once a year. De-energize all power sources, both line and engine generator set, then brush and vacuum away any excessive dust or dirt accumulation. At this time, with the contactor de-energized, you can remove the contact covers and check the contacts. Make sure contacts are clean and not burned or pitted.
ENGINE GENERATOR SET
Service the engine in accordance with the engine manufacturer's manual provided with your new equipment. Routinely remove debris and dirt from around the inside generator enclosure. Insure that the air intakes are free from leaves and other debris at all times.

Stop Mode

Auto Mode

Manual Mode

Clean and inspect battery terminals a least twice a year. Also Check the battery water level at least twice a year.

RUNNING ICON When there are no alarms present, an animated icon is displayed to indicate the engine is running.

Other than keeping the generator clean and free of debris, there is no other routine or preventative maintenance required as long as the generator is run biweekly to keep it dry and in good working order.

USB ICON When a USB connection is made to the module the USB icon is displayed.
MEMORY CORRUPTION If either the config file or engine file becomes corrupted, the unit will display the following icon.

COLD WEATHER OPERATION
Extreme cold weather operation requires special considerations. Higher CCA batteries are required for cold weather starting; 650 CCA or larger are recommended. In addition you should consider installing an oil heater kit and a battery warmer for reliable starting during cold weather.

12270-00

21

60706-229

ENGINE GENERATOR SET LAYOUT ULPSS20B2W/A

12270-00

22

60706-229

12270-00

ENGINE GENERATOR SET PAD LAYOUT

23

60706-229

TROUBLESHOOTING TABLES
******************** ****** WARNING ******
********************
NEVER JUMP START THESE UNITS. JUMP STARTING THESE UNITS WITH LOW OR BAD BATTERIES WILL CAUSE PERMANENT DAMAGE TO THE ENGINE CONTROL MODULE.
UNIT WILL NOT CRANK WHEN THE POWER FAILS
1. Engine control module not in the "Auto" mode. 2. Transfer switch control board not closing the
contacts. 3. Low or dead battery, must hold 12 volts during
cranking. 4. Incorrect wiring between transfer switch and
generator. 5. Loose or dirty battery terminals. 6. Defective engine control module (ECM). 7. Defective starter. 8. Defective start solenoid. 9. Defective start/stop control in the transfer
switch. 10. ATS panel in fault from previous run cycle. 11. Blown 2 amp fuse on generator control
panel. 12. Blown 10 amp fuse on generator control
panel. 13. Defective starter/fuel solenoid relay(s).
ENGINE WILL NOT CRANK USING START BUTTON ON THE GENERATOR
1. Low or dead battery, must hold 12 volts during cranking.
2. Blown 2 amp fuse on generator control panel.
3. Blown 10 amp fuse on generator control panel. 4. Loose or dirty battery terminals. 5. Defective engine control module (ECM). 6. Defective starter. 7. Defective start solenoid. 8. Locked up engine generator set. 9. Defective starter/fuel solenoid relay(s).

ENGINE CRANKS BUT WILL NOT START
1. Improper fuel pressure being delivered to unit. 2. Fuel supply shut off. 3. Fuel supply empty. 4. Defective spark plug. 5. Defective engine ignition module. 6. Dirty air cleaner filter. 7. Defective fuel solenoid valve. 8. Low voltage from battery to fuel solenoid, must
hold 12 volts during cranking. 9. Oil in the bottom of air cleaner from crankcase
breather. 10. Defective starter/fuel solenoid relay(s).
ENGINE STARTS AND THEN STOPS AND FAULT ICON COMES ON
1. Engine is low on oil. 2. No AC output from generator to engage stop
crank circuit.
ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS
1. Insufficient fuel volume getting to the unit. a. Fuel line too small. b. Low fuel pressure.
2. AC short circuit. 3. Wiring to the ATS panel crossed or shorted. 4. Unit is overloaded. Check load amperage.
ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY (GENERATOR)
1. No AC generator output from generator. 2. See Automatic Transfer Switch Manual.
ATS PANEL WILL NOT PULL IN ON NORMAL POWER
See Automatic Transfer Switch Manual
NO AC OUTPUT FROM GENERATOR
1. Defective Diodes. 2. Defective Voltage Regulator. 3. Defective rotor. 4. Defective stator. 5. Defective exciter rotor. 6. Defective exciter stator. 7. AC short in the output leads. 6. Defective / Open Circuit Breaker 7. Wiring error.

12270-00

24

60706-229

12270-00

AC AND DC GENERATOR SCHEMATIC

25

60706-229

AC WIRING SCHEMATICS

ULPSS20-17/A

ULPSS20-3/A

12270-00

26

60706-229

AC WIRING SCHEMATICS

ULPSS20-18/A

ULPSS20-4/A

12270-00

27

60706-229

12 MONTH LIMITED WARRANTY
WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours, which ever occurs first, that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions.
WINCO's sole liability, and Purchaser's sole remedy for a failure under this warranty, shall be limited to the repair of the product. At WINCO's option, material found to be defective in material or workmanship under normal use and service will be repaired or replaced. For warranty service, return the product within 12 months or 1000 hours, which ever occurs first from the date of purchase, transportation charges prepaid, to your nearest WINCO Authorized Service Center or to WINCO, Inc. at LeCenter Minnesota.
THERE IS NO OTHER EXPRESS WARRANTY.
To the extent permitted by law, any and all warranties, including those of merchantability and fitness for a particular purpose, are limited to 12 months or 1000 hours, which ever occurs first from date of purchase. In no event is WINCO liable for incidental or consequential damages.
Note: Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply in every instance. This warranty gives you specific legal rights which may vary from state to state.
WINCO reserves the right to change or improve its products without incurring any obligations to make such changes or improvements on products purchased previously.
EXCLUSIONS:
WINCO does not warrant Engines. Engines are covered exclusively by the warranties of their respective manufacturers, see enclosed warranties.
WINCO does not warrant Batteries, or Other Component Parts that are warranted by their respective manufacturers.
WINCO does not warrant modifications or alterations which were not made by WINCO Inc.
WINCO does not warrant products which have been subjected to misuse and/or negligence or have been involved in an accident.

12270-00

28

60706-229


Adobe PDF Library 7.0 Adobe InDesign CS2 (4.0)

Related Documents

Preview WINCO ULPSS12H4W/E Packaged Standby System Installation and Operators Manual
Comprehensive installation and operators manual for the WINCO ULPSS12H4W/E Packaged Standby System. Covers safety instructions, product description, specifications, installation procedures for fuel, battery, and electrical connections, initial startup, testing, preventive maintenance, troubleshooting, and warranty information.
Preview WINCO ULPSS12H4W/E Packaged Standby System Installation and Operators Manual
Comprehensive installation and operators manual for the WINCO ULPSS12H4W/E Packaged Standby System. Covers safety, proper use, installation, specifications, fuel, battery, wiring, startup, maintenance, troubleshooting, warranty, schematics, and layout for this generator set.
Preview WINCO PSS60/C, PSS90/C, DSE7310 Installation and Operations Manual
Comprehensive installation and operations manual for WINCO PSS60/C, PSS90/C, and DSE7310 package standby generator systems. Covers safety, setup, operation, troubleshooting, and warranty.
Preview Winco PSS60/B, PSS90/B, DSE7110 Standby Generator Installation and Operations Manual
Comprehensive installation and operations manual for Winco PSS60/B, PSS90/B, and DSE7110 standby generator sets. Covers safety precautions, system description, installation procedures, starting procedures, troubleshooting, and warranty information.
Preview WINCO 27.6kW-36kW PTO Generators: Installation and Operators Manual
Comprehensive installation and operators manual for WINCO 27.6kW to 36kW PTO generators, covering safety, specifications, installation, operation, maintenance, and troubleshooting.
Preview WINCO W6010DE/J Generator Parts List and Diagrams
Comprehensive parts list and assembly diagrams for the WINCO W6010DE/J portable generator. Includes detailed breakdowns of the engine, generator end, cradle assembly, fuel system, electrical receptacles, and decals, with part numbers and quantities.
Preview WINCO HPS12000HE-03/B Parts List and Diagrams
Comprehensive parts list and assembly diagrams for the WINCO HPS12000HE-03/B portable generator, including engine, fuel system, and receptacle components.
Preview Winco SPECTRUM Gas Stock Pot Stove Operating Instruction Manual
Comprehensive operating instructions, safety precautions, installation, conversion, and maintenance guide for Winco SPECTRUM Gas Stock Pot Stoves (Models NGSP-1 and NGSP-2).