FNV 25 / FNV 50 / FNV 100 VOICE EVACUATION INTERFACE SYSTEM INSTALLATION INSTRUCTIONS

System Overview

The FNV 25, FNV 50, and FNV 100 are self-contained amplifier, tone generator, digital message repeater, and supervisory interface units. They are designed for use with a UL-listed Fire Alarm Control Panel (FACP) to provide a Listed Voice Evacuation Alarm System.

The FACP provides initiating circuitry and a signaling circuit to the FNV units. The FNV series provides its own internal supervision and supervision for its speaker lines. Any fault is reported back to the FACP. In normal standby, the supervisory circuit from the panel connects to a matching EOLR. If the FNV unit experiences an internal failure or a fault on the speaker line, a contact opens, and the FACP reports it as an open fault.

These units are powered by 120 VAC at 60 Hz. The FNV 25 provides 25W to the speaker circuit, the FNV 50 provides 50W, and the FNV 100 provides 100W. Speakers can be 25 or 70 VRMS (jumper selectable; 25V is factory set).

Installation

Installers must ensure all wiring and devices comply with the following standards:

  • National Electrical Code (NFPA 70)
  • NFPA Standard 72
  • Life Safety Code (NFPA 101)

Install equipment in a clean, dry environment, avoiding areas subject to vibration. Remove electronic assemblies from the enclosure before drilling or punching. Make cable entries from the rear or sides where possible. Ensure modifications do not interfere with assemblies or batteries.

Wiring

Refer to wiring and terminal designation diagrams for detailed connections:

  1. Connect speaker lines to TB1 - 5(+) & 6(-), observing polarity. Ensure all speakers are connected with the same polarity. For Class "A" (Style "Z"), use returns TB1 - 7(-) & 8(+).
  2. Ensure the microphone is attached to connector P2. If no microphone is installed, set switch SN2 - 8 to the OFF position.
  3. Attach the appropriate EOLR for the FACP to TB3 - 3 & 4 and TB3 - 5 & 6. The TB3 term 5 & 6 value must also be placed at the end of the speaker line. Use the EOLR value specified in the FACP manufacturer's installation instructions for the indicating appliance circuit. If EVX-4Z zone splitters are used, the FACP EOLR is relocated per EVX-4Z installation instructions (P/N 1-5010 Rev C).
  4. Connect the FACP signaling circuit to TB1 - 3(+) & 4(-), observing alarm polarity.
  5. Connect 120 VAC, 60 Hz power to the transformer's primary pigtail leads (black and white). Secure the ground lead to the grounding stud in the cabinet.
  6. Once power is on, connect the battery wiring harness (Red (+) / Black (-)), observing polarity. Minimum battery size is 24V 7AHr. Maximum battery size is 18Ahr for FNV 25/50 and 24Ahr for FNV 100 (use two 12V batteries in series). If the unit relies on an external power supply with battery backup, ensure switch SN2 - 7 is in the OFF position. Battery wiring is Non Power-Limited and must maintain a minimum 1/4" spacing from any Power-Limited wiring. If batteries are in a separate enclosure, use separate conduit for battery wiring.

Once all power and circuits are connected, the Green LED should remain on, indicating the FNV unit is fully operational and all circuits are nominal.

Terminal Designations

TB1:

  • TER 1 & 2: Power Input 24-32V AC/DC (NOTE 1, 4)
  • TER 3 & 4: FACP Signal Circuit Input - 10mA max. (Alarm Polarity shown) (NOTE 1, 4)
  • TER 5 & 6: 25/70 VRMS Speaker Loop Style Y/Z (Class "A"/"B" start) (NOTE 2)

TB3:

  • TER 1 & 2: Optional FACP Supervisory Circuit (See installation instructions page 5 diagram 2 for details, 32V - 0.4A max.). Factory set for none - J1 (installed).
  • TER 3 & 4: FACP Signal/Supervisory Circuit EOLR
  • TER 5 & 6: Matching EOLR for speaker supervisory circuit
  • TER 7: General purpose output (pulls to circuit negative on fault condition, 32V - 0.2A max). Not for Fire Protective Signaling use.

TB2:

  • TER 1: Circuit Neg
  • TER 2: Aux Audio Input (0.5V nominal) (1VRMS - 1mA max.)
  • TER 3: PreAmp In/Out (600 Ohm 0dBm)
  • TER 4: Master - Programmable +24VDC Active; Slave - +24VDC Input
  • TER 5: Signal Active Master - Out / Slave - In
  • TER 6: Aux Audio Enable (+24V)(32V - 5mA max.)
  • TER 7: Aux Signal Activate (+24V) (32V - 5mA max.)
  • TER 8: Alarm Voltage +24V when unit is in alarm condition (0.1A)
  • TER 9: Int V+ (+24V) disconnected in alarm condition (0.1A)
  • TER 10: V+ (+24V 0.1A)
  • TER 11: Mic PTT (+24V 0.1A)

NOTES:

  1. Intended for connection to Listed Class 2 / Class 3 (Power Limited) sources only.
  2. Power Limited
  3. Non-Supervised
  4. Supervised
  5. Terminating equipment must be installed in the same room as the unit.

FACTORY DEFAULT SWITCH / JUMPER SETTINGS:

  • SN1: 1=OFF (8 sec. initial delay), 2=ON, 3=OFF, 4=ON (8 sec. repeat delay), 5=OFF, 6=ON (Message On), 7=OFF (3 Repeats), 8=ON.
  • SN2: 1=OFF (Temporal Whoop Signal), 2=OFF, 3=OFF, 4=OFF (Fault Code Lock default), 5=X Do not use (default up (off)), 6=AC Fault Delay, 7=ON (Battery connected), 8=ON (Mic connected).
  • J1 A/B: 1-2 = SHORT
  • J2: 25 VRMS 2-3 = SHORT; 70 VRMS 1-2 = SHORT. To change output voltage, move shorting block.
  • J5: 1+2 SHORT = Ground Fault Enable.

Options

AUX +24VDC OUTPUT (TB2-4, 8, 9 & 10): These terminals provide a maximum of 200 mA regulated 24VDC power for auxiliary functions. Do not exceed a 200 mA load combined on these terminals. For connection to Listed General Signal devices only (Non-Fire Protective Signaling applications). Terminal 4 activation is programmed in the U6 ePROM chip and is typically active under conditions like Aux Signal Active, Aux Audio Enable, Bell Circuit Active, or RSI Active. Reprogramming requires factory intervention.

CONNECTION OF AN AUX AUDIO SOURCE (TB2-1 & 2): An auxiliary audio source from additional paging equipment can be connected to augment an existing paging system. It is not intended for continuous signal input but can be used for paging applications. For such operation, the Aux Audio Enable input (TB2-6) must be powered from Int V+ (TB2-9) to prevent the aux audio from overriding the evacuation signal during an alarm.

OPTIONAL SUPERVISORY CIRCUIT (TB3-1 & 2): An alternate method for normal supervision via the signaling circuit can be employed using any supervisory circuit from the FACP. Connection is made to TB3, Ter. 1 and 2. This provides a normally closed connection to the EOLR on Ter. 3 and 4. The relay contact opens upon any trouble condition, reporting an open circuit trouble to the FACP. Jumper shorting blocks A and B must be removed from J1 for this connection.

Operation

Standby: The Green LED remains on.

Alarm Condition: The Red LED remains on, and the Green LED also remains on. The alarm sequence typically involves alternating alarm tones and digital messages until the alarm condition is cleared. Keying the microphone overrides tones and messages for direct broadcast, resetting the digital message sequence.

LED Indicators: The Green LED dims with broadcast audio levels. The Yellow LED remains on during a fault condition. The Green LED flashes to indicate fault codes. A fault condition opens the contact connecting the FACP signal circuit to the EOLR, notifying the FACP. Yellow LED 4 illuminates during a ground fault condition.

Specifications

FeatureFNV 25FNV 50FNV 100
Input Voltage120 VAC at 60 Hz120 VAC at 60 Hz120 VAC at 60 Hz
Input Current (@ 120 VAC)1.4 A0.8 A1.2 A
Input Current (Battery) Standby0.18 A0.13 A0.18 A
Input Current (Battery) Alarm1.0 A1.0 A2.60 A
Standby w/Aux Load0.31 A0.26 A1.20 A
Output Power25 Watt50 Watt100 Watt
Freq. Response800 - 2800 Hz400 - 4000 Hz400 - 4000 Hz
Output Voltage25/70 VRMS Selectable25/70 VRMS Selectable25/70 VRMS Selectable
*Optional 24 VDC input0.6 A Standby, 1.0 A Alarm0.6 A Standby, 1.0 A Alarm0.18 A Standby, 2.50 A Alarm
Output ProtectionPower Limited, Open and Short Circuit protected (100 watt MODELS)

Model Configurations

The FNV-100 is a complete Voice Evacuation Module (no transformer/cabinet). The FNV 100 is a complete Voice Evacuation Panel (with transformer/cabinet). The FNV-100E is a slave amplifier. Different model numbers combine these amplifiers:

  • FNV 100: 1x FNV-100, 1x Speaker Circuit
  • FNV 150: 1x FNV-100, 1x FNV-50E, 2x Speaker Circuits
  • FNV 200: 1x FNV-100, 1x FNV-100E, 2x Speaker Circuits
  • FNV 100E: 1x FNV-100E, 1x Speaker Circuit
  • FNV 150E: 1x FNV-100E, 1x FNV-50E, 2x Speaker Circuits
  • FNV 200E: 2x FNV-100E, 2x Speaker Circuits

*Input current measurements are determined by test conditions under UL 1711. Sine is a continuous non-distorted sine wave. Alarm is the average current during an alarm signal. Standby is the current draw with normal power on. Battery Standby is current draw from batteries on power loss.

Wiring Diagrams

Wiring Diagram 1: Typical Installation illustrates the connection of the Fire Alarm Control Panel (FACP) signal circuit, input power, and speaker lines to the FNV unit. It details field wiring connections for various wire gauges and notes that input power is Non-Power Limited, requiring separation from Power Limited wiring.

Wiring Diagram 2: Optional Supervisory Circuit Application shows how to connect an optional supervisory circuit from the FACP to TB3-1 & 2 for an alternative supervision method. It requires removing jumper shorting blocks on J1.

Wiring Diagram 3: Addressable System Application demonstrates connecting the FNV unit to an addressable system using an addressable control module or monitor module. It also requires removing jumper shorting blocks on J1.

Wiring Diagram 4: Multiple Unit Connection Detail illustrates cascading multiple FNV units (up to 15). It shows connections between units using a 14-pin ribbon cable or hardwired connections, with all power, supervisory, and speaker connections remaining unchanged.

Wiring Diagram 5: Aux Audio Enable Connection Detail shows the connection for enabling auxiliary audio input, typically via a customer-provided dry contact.

Switch Settings

The FNV 25/50/100 units feature switch networks SN1 and SN2 for configuration:

SN2 Default: 0/0/0/0/0/0/1/1

  • SW 1/2/3: Sets the evacuation tone (Temporal slow whoop, Hi Lo, Horn, Bell, Empty, Chime, None, 1kHz Sine).
  • SW 4: Sets diagnostics mode (Off or On).
  • SW 5: Not Applicable (NA).
  • SW 6: Sets AC power failure report delay (No delay or 6 hour delay).
  • SW 7: Battery status (Not connected or Connected).
  • SW 8: Microphone status (Not connected or Connected).

SN1 Default: 0/1/0/1/0/1/0/1

  • SW 1/2/3: Sets the initial delay before the message plays (No delay, 4, 8, 12, 16, 20, 24, or 28 second delay). Tone sounds during delays.
  • SW 4/5: Sets the delay between message repeats (4, 8, 12, or 16 second delay).
  • SW 6: Sets message play (Message off or Message on).
  • SW 7/8: Sets the number of times the message plays (1, 2, or 3 plays).

Switch Network Detail: UP = 0, DOWN = 1.

Trouble Codes

When a unit enters a Trouble Condition, the Yellow LED remains on. The Green LED flashes a code indicating the trouble type. Codes repeat after a pause. Multiple troubles may result in combined codes.

CodeTroubleCodeTrouble
1Power Failure8Amplifier Trouble
2Open Speaker Circuit16Microphone Trouble
4Shorted Speaker Circuit32Battery Trouble

* 6 flashes typically indicate "External Trouble" (e.g., EVX-RM). If LED 4 is on, 6 flashes indicate a ground fault. Simultaneous ground fault and external trouble do not combine for 12 flashes.

End of Line Resistors

R1: End-of-line resistor for the FACP Signal Circuit. If the FACP requires a 4.7K EOLR, R1 must be 4.7K. Normally connected through a closed Trouble contact; this contact opens when the FNV unit goes into trouble, signaling an "Open" circuit to the FACP.

R2 & R3: R2 sets the value for the speaker circuit EOLR (R3). R2 and R3 must match. If a speaker EOLR (R3) already exists, match its value for R2.

Field wiring connections: Use appropriate wire gauges (#6-32 screw: 14-18 AWG; #8-32 screw: 12-18 AWG; Horizontal entry terminal: 18-26 AWG). Wire gauge is determined by circuit load.

Models: FNV 25, FNV 50, FNV 100, FNV 100 Voice Evacuation Interface System, Voice Evacuation Interface System, Evacuation Interface System, Interface System

File Info : application/pdf, 8 Pages, 797.81KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676769026

References

Corel PDF Engine Version 10.427

Related Documents

Preview Hochiki FireNET Graphix: Installation and Programming Manual
A comprehensive guide to installing, configuring, and programming the Hochiki FireNET graphix fire alarm system graphics software. Covers system overview, hardware installation, software setup, running the application, design tools, and utilities.
Preview Hochiki FireNET PLUS Operating Instructions for FN-1127 Control Panel and FN-LCD-S Annunciators
Comprehensive operating instructions for the Hochiki FireNET PLUS FN-1127 control panel and FN-LCD-S annunciators, detailing fire and trouble conditions, button functions, fuse replacement, battery maintenance, and SOM-R releasing function.
Preview Hochiki DCP-SOM-AI/DCP-SOM-A Class A Supervised Output Module Installation Instructions
Detailed installation guide for Hochiki America's DCP-SOM-AI and DCP-SOM-A Class A Supervised Output Modules, covering general description, mounting, wiring, specifications, and SCI operation.
Preview Hochiki FireNET L@titude Analog Addressable Fire Alarm Control Panel Specifications
Comprehensive technical specifications, features, and optional peripherals for the Hochiki FireNET L@titude analog addressable fire alarm control panel. Includes product details, electrical specs, and model configuration.
Preview Hochiki Product Guide ISS30:MAR24 - Fire Detection Systems & Solutions
Comprehensive product guide from Hochiki, detailing their advanced range of fire detection systems, including addressable, conventional, wireless, and air sampling technologies. Learn about Hochiki's commitment to fire safety innovation.
Preview HOCHIKI ACE-V Analog Multi-Criteria Detector - Technical Specifications and Features
Detailed information on the HOCHIKI ACE-V Analog Multi-Criteria Detector, including its applications, standard features, operation, technical specifications, and product listings. Designed for effective smoke and heat detection.
Preview Hochiki HFP AP Single/Two Loop Control Panel Range Product Manual
Comprehensive product manual for the Hochiki HFP AP Single/Two Loop Control Panel Range, detailing installation, operation, and programming. Covers technical specifications, safety guidelines, cabling, front panel controls, and configuration options.
Preview HOCHIKI HCVR-3 Conventional Releasing Fire Alarm Control Panel Datasheet
Detailed specifications and features of the HOCHIKI HCVR-3 Conventional Releasing Fire Alarm Control Panel, including product listings, compatible devices, and technical data. UL Listed and FM Approved.