DESCRIPTION
The HCVR-3 is a 3 zone conventional releasing fire alarm control panel that is UL Listed and FM Approved for releasing.
The HCVR-3 can be configured to activate releasing by a single zone or combination of any two zones. The LCD display is used to show the countdown timer during activation of the releasing sequence.
The HCVR-3 is fully programmable using simple menu options. The panel is a single board construction which provides an easy replacement solution. It is also compatible with a wide range of devices.
STANDARD FEATURES · UL 864 Listed and FM Approved · Three detection zones · Any single zone or any combination of zones can be
configured to release · Fully programmable using simple menu options · Simple, single board construction · Installer friendly · Compatible with wide range of detection devices · Configurable first stage NAC delays · Configurable detection delays · Built-in Manual Release switch and separate circuit · Compatible with FirePro XtinguishTM · Compatible with various releasing valves · Configurable releasing delays up to 60 seconds in 5
second intervals · Configurable releasing duration up to 5 minutes in 5
second intervals · Releasing countdown timer displayed on the LCD · Supports up to seven HCVR-SDU or HCVR-AB · Built-in relays for Fire, Trouble, Stage 1, Stage 2,
Extract and Local Fire
S6468
PRODUCT LISTINGS
3046396
California State Fire Marshal 7165-0410:0206
Specifications subject to change without notice.
Hochiki America Corporation 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268 Phone: 714-522-2246 Fax: 714-522-2268 Technical Support: 714-670-3229 or technicalsupport@hochiki.com
Continued on second page. Find latest revision at www.hochiki.com
Page 1 of 2 F0154 Rev.01 10/2024
HCVR-3 - CONVENTIONAL RELEASING FIRE ALARM CONTROL PANEL
SPECIFICATIONS
Supply Voltage Power Supply DC Rating Mains Supply Fuse Dimensions Weight Color Material Max. Battery Size RS-485 Serial Bus Trouble Contact Rating Local Fire Contact Rating Fire Contact Rating 1st Stage Contact Rating 2nd Stage Contact Rating EXTRACT Output EXISTING Output Rating NAC Output Rating Detection Zone End of line resistor NAC Output Stand by Current Alarm Current Operating Humidity Operating Temperature
115VAC (50hz/60hz) or 230VAC (50hz/60hz) 24V 2 Amps 1.6 Amps 250V 14.5" (W) x 12.2" (H) x 3.5" (D) 12.3 lbs. w/o batteries Red or gray 1.2mm mild steel 7Ah 12V (2 per panel) Maximum line impedance 120 Ohms 30VDC 1 Amp 30VDC 1 Amp 30VDC 1 Amp 30VDC 1 Amp 30VDC 1 Amp 30VDC 1 Amp contacts for (NO) and (C) 18 to 28VDC 1 Amp max load for 5 minutes and voltage reversing DC 0.5 Amp per output 6K8 Ohms 5% resistor 10K Ohms 5% resistor 100 mA 620 mA 93% RH Non-Condensing -5°C to +49°C (23°F to 120°F)
MODEL PANEL ACCESSORIES HCVR-SDU HCVR-AB HCVR-SQA HCVR-DS DETECTORS SLR-24H SLR-835 SLR-835/-835W SLR-835-BH-2W SLV-24V/-24/-24N SOE-24V, SOE-24H SOC-24V / SOC-24VN SIJ-24 DCD-135 DCD-190 BASES NS6-220 NS4-220 PULL STATION/ABORT SWITCH HPS-DAK-SR HCVR-AS RELEASING VALVES HV2185328 8210G207 11601 11602 11592 11591 11596 11595 2823A-2NB-A4F6 EA45 (510006) K-45-8017 B6793-859 753-E Series 305350 Ci IS8B 305451 Ci IS8B
HOCHIKI AMERICA COMPATIBLE DEVICES
DESCRIPTION
Remote Status Display Unit Ancillary Board Sequential Activator Disconnect Switch
Photoelectric Smoke Detector w/heat Photoelectric 8-35V Smoke Detector Photoelectric 8-35V Smoke Detector Photoelectric 8-35V Smoke Detector w/heat Photoelectric Smoke Detector Photoelectric Smoke Detector Photoelectric Smoke Detector Ionization Smoke Detector 135° Fixed Temperature Rate of Rise Heat Detector 190° Fixed Temperature Rate of Rise Heat Detector
6" base, 93mA draw, 24V 4" base, 93mA draw, 24V
Conventional Manual Pull Station for Fire Suppression Release Abort Switch
ASCO Solenoid ASCO Solenoid Viking Solenoid Viking Solenoid Viking Solenoid Viking Solenoid Viking Solenoid Viking Solenoid Snap-tite Solenoid Sevo Systems Solenoid Kidde Solenoid (equivalent to 486500-01) Kidde Solenoid (equivalent to 81-100000-001) Victaulic Solenoid Fire Eater Solenoid Fire Eater Solenoid
MAX
7 7 20 1
20 per zone 20 per zone 20 per zone 20 per zone 20 per zone 20 per zone 20 per zone 20 per zone 20 per zone 20 per zone
20 20
1 (system design may require more) 1 (system design may require more)