INSTALLATION GUIDE FOR BROAN ERV100S

ABOUT THIS MANUAL

This manual uses specific symbols to emphasize information:

WARNING

Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.

CAUTION

Identifies an instruction which, if not followed, may severely damage the unit and/or its components.

NOTE: Indicates supplementary information needed to fully complete an instruction.

ABOUT THESE UNITS

LIMITATION

For residential (domestic) installation only. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.

WARNING

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:

  1. Use this unit only in the manner intended by the manufacturer. For questions, contact the manufacturer at the address or telephone number listed in the warranty.
  2. Before servicing or cleaning the unit, disconnect power cord from electrical outlet.
  3. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
  4. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
  5. Do not use this unit with any solid-state speed control device other than VT7W, VT4W, VT6W (Main Control) and VB20W, VBATHW (Auxiliary Controls).
  6. This unit must be grounded. The power supply cord has a 3-prong grounding plug for personal safety. It must be plugged into a mating 3-prong grounding receptacle, grounded in accordance with national electrical code and local codes and ordinances. Do not remove the ground prong. Do not use an extension cord.
  7. Do not install in a cooking area or connect directly to any appliances.
  8. Do not use to exhaust hazardous or explosive materials and vapors.
  9. When performing installation, servicing or cleaning these units, it is recommended to wear safety glasses and gloves.
  10. When applicable local regulation comprises more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his expenses.

CAUTION

  1. To avoid premature clogged filters, turn OFF the unit during construction or renovation.
  2. Please read specification label on product for further information and requirements.
  3. Be sure to duct air outdoor - Do not intake/exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage.
  4. Intended for residential installation only in accordance with the requirements of NFPA 90B.
  5. Do not run any air ducts directly above or closer than 2 ft to any furnace or its supply plenum, boiler, or other heat producing appliance. If a duct has to be connected to the furnace return plenum, it must be connected not closer than 9' 10" from this plenum connection to the furnace.
  6. The ductwork is intended to be installed in compliance with all local and national codes that are applicable.
  7. When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit operates adequately.
  8. If the ductwork passes through an unconditioned space (e.g.: attic), the unit must operate continuously except when performing maintenance and/or repair. Also, the ambient temperature of the house should never drop below 65°F.
  9. Do not make excessive use of fragrance appliances or chemicals since some may damage the unit components material.

1. TYPICAL INSTALLATIONS

The unit can be hung from joists or ceiling using included brackets or optional chains and spring kit (part no. V61239, sold separately). Bathroom fans and range hoods can exhaust stale air. For multi-level homes, one exhaust register at the highest level is recommended. A standard 3-prong electrical outlet must be available within 3 feet of the unit.

1.1 FOR HOUSE

There are three installation methods for houses:

1.1.1 FULLY DUCTED SYSTEM

Stale air from registers at the highest level is exhausted outdoors. Fresh air from outdoors is filtered and supplied by registers at the lowest liveable level. Multi-level homes require at least one exhaust register at the highest level. This system is primarily for homes with radiant hot water or electric baseboard heating. (Diagram shows a house with ducts connecting to various rooms, exhausting stale air from upper levels and supplying fresh air to lower levels.)

1.1.2 CENTRAL DRAW POINT (CONNECTION TO A FORCED AIR SYSTEM)

Stale air from registers at the highest level is exhausted outdoors. Fresh air from outdoors is filtered and supplied to the return (plenum) or supply duct of the forced air unit. It is not essential for the forced air system blower to run when the unit is in operation, but it is recommended. Homes with multiple forced air systems should have one unit on each system. (Diagram shows a house with ducts connecting to a central forced air system, exhausting stale air from upper levels and supplying fresh air to the return/supply plenum.)

1.1.3 SIMPLIFIED INSTALLATION (CONNECTION TO A FORCED AIR SYSTEM)

Stale air is exhausted outdoors. Fresh air from outdoors is filtered and supplied to the return (plenum) or supply duct of the forced air unit. To avoid cross-contamination and achieve highest efficiencies, the forced air system blower must always be ON. Homes with multiple forced air systems should have one unit on each system. (Diagram shows a house with ducts connecting to a central forced air system, similar to central draw point but emphasizing continuous blower operation.)

1.2 FOR HIGH-RISE DWELLING

1.2.1 FULLY DUCTED SYSTEM (PRIMARILY FOR HOMES WITH RADIANT HOT WATER OR ELECTRIC BASEBOARD HEATING)

Stale air from registers in bathrooms and kitchen is exhausted outdoors. Fresh air from outdoors is filtered and supplied by registers in bedrooms and living room. (Diagram shows a high-rise dwelling layout with ducts exhausting from kitchen/bathrooms and supplying to bedrooms/living room.)

1.2.2 CENTRAL DRAW POINT (CONNECTION TO A FAN-COIL SYSTEM)

Stale air from registers in bathrooms and kitchen is exhausted outdoors. Fresh air from outdoors is filtered and supplied to the supply duct of the fan-coil system unit. It is not essential for the fan-coil system blower to run when the unit is in operation, but it is recommended. (Diagram shows a high-rise dwelling layout with ducts connecting to a fan-coil system, exhausting from kitchen/bathrooms and supplying to the fan-coil unit.)

2. INSTALLATION

2.1 INSPECT THE CONTENTS OF THE BOX

2.2 UNIT PREPARATION

All units have 2 ports with integrated balancing dampers (Fresh air to building and Exhaust air to outdoors ports). Before installation, ensure these ports are in wide open position. If not:

  1. Loosen the damper lever locking screw.
  2. Use the damper lever to open the damper.
  3. Lock the damper in position by tightening the locking screw.

CAUTION

When loosening or tightening the damper lever locking screw, never use an electric screwdriver or drill, use a standard screwdriver.

(Diagram shows a damper lever and a screw, indicating how to adjust the damper.)

2.3 LOCATING THE UNIT

Choose an appropriate location:

2.4 HOW TO HANG THE UNIT

WARNING

Never handle the unit using its ports; hold the unit by its sides.

Hang the unit using 2 included brackets. (Diagram shows a unit being held by its sides.)

WARNING

To ensure occupants safety, ensure the brackets are mounted to solid surface (e.g.: concrete ceiling, joists).

CAUTION

The included screws are for wood joist only; do not use them to secure brackets to concrete ceiling or metal joists.

  1. Mount brackets to ceiling or joists. Use the template printed on the cardboard filler located in the unit box to ease location. Align bracket notches with cardboard filler tabs. Use at least 2 end screws (A) (or nails) per bracket; the center one is optional. (Diagram shows brackets being mounted to joists, with a cardboard filler template for alignment.)
  2. Bend 90° integrated hooks (2 places) on the unit. (Diagram shows bending hooks on the unit.)
  3. Hang the hooks onto the brackets. (Diagram shows the unit being hung onto the brackets.)
  4. Clip the other side of unit onto the brackets (2 places). (Diagram shows the unit fully clipped onto the brackets.)

WARNING

Ensure the unit is completely held by the brackets before continuing the installation.

NOTE: The unit can also be hung using 4 hooks (shaded part in illustration), chains, springs and screws (kit sold separately, part no. V61239). (Diagram shows the unit with four hooks for alternative hanging.)

CAUTION

Make sure the unit is level.

2.5 PLANNING OF THE DUCTWORK

2.6 INSTALLING THE DUCTWORK AND REGISTERS

WARNING

Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas furnace, a gas water heater or a fireplace.

2.6.1 FULLY DUCTED SYSTEM

Stale air exhaust ductwork:

Fresh air distribution ductwork:

2.6.2 CENTRAL DRAW POINT SYSTEM

Stale air exhaust ductwork: Same as for Fully Ducted System.

Fresh air distribution ductwork:

WARNING

When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety regulations. Please refer to your local building code.

CAUTION

When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the ERV. Also, use a steel duct.

Supply side connection:

(Diagram shows a steel duct connecting the ERV to the furnace supply duct, with a minimum 18" distance from the furnace/air handler.)

2.6.3 SIMPLIFIED INSTALLATION

WARNING

When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety regulations. Please refer to your local building code.

CAUTION

When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the ERV. Also, use a steel duct. For a Return-Return installation, the furnace blower must be in operation when the ERV is in operation.

Supply-return connection:

Stale air intake:

Fresh air distribution: Same instructions as Supply side connection, Section 2.6.2.

NOTE: It is not essential to synchronize the furnace blower operation with the unit operation, but we recommend it.

(Diagram shows a steel duct connecting the ERV to both the furnace supply and return ducts, with minimum distances specified.)

2.7 CONNECTING THE DUCTS TO THE UNIT

NOTE: All unit ports are designed for minimum 5" diameter ducts, but can connect to bigger sizes using appropriate transitions.

Insulated flexible ducts:

CAUTION

Make sure the balancing dampers are set to wide open position before connecting ducts. Ductwork connecting Fresh air to building and Exhaust air to outdoors ports with exterior hood(s) must be made of insulated ducts, all way long.

All units have Fresh air to building and Exhaust air to outdoors ports equipped with integrated balancing dampers. Ensure these are wide open before installing insulated flexible ducts (See Section 2.2).

CAUTION

If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts.

Procedure for connecting insulated flexible ducts to the unit ports (Exhaust air to outdoors and Fresh air from outdoors ports):

  1. Pull back the insulation to expose the flexible duct.
  2. Attach the flexible duct to the port using a tie wrap.
  3. Pull the insulation over the joint and tuck in between the inner and outer rings of the double collar, then pull down the vapor barrier (shaded part in illustrations below) over the insulation and tuck in between the inner and outer rings.
  4. Apply duct tape to the joint (outer ring and vapor barrier) making an airtight seal. Avoid compressing insulation.

CAUTION

Make sure the vapor barrier on the insulated ducts does not tear during installation to avoid condensation within the ducts.

(Four diagrams illustrate the steps of connecting flexible ducts: 1. Insulation pulled back, 2. Duct attached with tie wrap, 3. Insulation pulled over joint, 4. Duct tape applied.)

Rigid ducts:

CAUTION

Do not use screws to connect the rigid ducts to the ports.

Use a small length (6" length) of flexible duct to connect the rigid duct to the ports to avoid vibration transmissions. Use tie-wraps for connections, then seal with duct tape.

2.8 INSTALLING 2 EXTERIOR HOODS

Choose appropriate location for exterior hoods:

WARNING

Make sure the intake hood is at least 6 feet away from any of the following: Dryer exhaust, high efficiency furnace vent, central vacuum vent, Gas meter exhaust, gas barbecue-grill, any exhaust from a combustion source, garbage bin and any other source of contamination.

Refer to figure for connecting insulated ducts to exterior hoods. An "Anti-gust intake hood" should be installed in regions with a lot of snow. (Diagram shows exterior hoods on a wall, indicating minimum distances between intake and exhaust hoods, and from the ground. It also shows duct connections with tape and tie.)

2.9 INSTALLING A TANDEM® TRANSITION* KIT

CAUTION

If using a Tandem Transition, a backdraft damper must be installed on the stale air to outdoors duct. If this causes an interruption in the duct insulation, insulation must be added around the backdraft damper to avoid condensation.

If desired, a Tandem transition kit can be used instead of 2 exterior hoods.

*Patented.

(Diagrams show two types of Tandem Transition kits: VTYIK1 and V14695.)

3. CONTROLS

The ERV100S unit has an integrated control located under the unit, in front of the electrical compartment. Plug in the unit. (Diagram shows the front of the ERV100S unit with an integrated control panel, highlighting an LED (1) and a push button (2).)

3.1 BOOTING SEQUENCE

The unit booting sequence is similar to a personal computer. Each time the unit is plugged in or after a power failure, it performs a booting sequence before operating.

During booting, the integrated control LED (1) will light up and remain GREEN or AMBER for 3 seconds, then shut off (booting done). Or it will light up in the color of the previous mode if controlled by its integrated control. No command is taken until the unit is fully booted.

If a problem occurs or the unit enters Protection Mode, its LED (1) will blink. The color and pattern depend on the error type or Protection Mode. Refer to the sticker on the unit and Section 9 Troubleshooting for details.

3.2 INTEGRATED CONTROL

Use the push button (2) to control the unit. The LED (1) indicates the unit's mode:

LED COLORRESULTS
AMBERUNIT IS ON LOW SPEED
GREENUNIT IS ON HIGH SPEED
NO LIGHTUNIT IS OFF OR CONTROLLED BY A MAIN CONTROL

NOTE: When using main control, the integrated control must be turned off.

3.3 SETTING EXTENDED DEFROST

Units are factory set to normal defrost. For cold regions (outdoor temperature -17°F and lower), extended defrost may be necessary. During the first 3 seconds of booting, the integrated control LED shows the current defrost mode:

LED COLORDEFROST MODE
GREENNORMAL
AMBEREXTENDED

Within the first 3 seconds of booting, press the push button until the LED blinks, then release. The LED will blink AMBER 5 times, then shut off, then turn RED (unit returns to booting sequence).

3.4 ELECTRICAL CONNECTION TO WALL CONTROLS

The ERV100S unit can be controlled using an optional main control.

NOTES: 1. The integrated control must be turned OFF to use an optional main control. 2. If an optional auxiliary control is used, if activated, this auxiliary control will override the optional main control operation.

WARNING

Always disconnect the unit before making any connections. Failure in disconnecting power could result in electric shock or damage of the wall control or electronic module inside the unit.

CAUTION

Never install more than one main wall control per unit. Make sure that the wires do not short-circuit between themselves or by touching any other components on the wall control. Avoid poor wiring connections. To reduce electrical interference (noise) potential, do not run wall control wiring next to control contactors or near light dimming circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.

Open the unit door. Insert the terminal connector (included in the installation kit) under the unit, on the electrical compartment front face. Use this terminal connector for electrical connection for main and optional wall controls, then secure the cable(s) with a tie wrap. (Diagram shows the terminal connector being inserted and secured with a tie wrap.)

Check if all wires are correctly inserted in their corresponding holes in the terminal block. A wire is correctly inserted when its orange receptacle is lower than another one without wire. Splice back the end of the cable to access the 4 wires. Strip the end of each wire. Connect each wire to its corresponding terminal: YELLOW wire to "Y", RED wire to "R", GREEN wire to "G" and BLACK wire to "B". Connect the auxiliary control cable, if installed. (Diagram shows a terminal block with wires inserted, illustrating correct and incorrect insertion.)

3.4.1 ELECTRICAL CONNECTION TO VT7W MAIN WALL CONTROL

(Diagram shows wiring connections for the VT7W main wall control to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals.)

3.4.2 ELECTRICAL CONNECTION TO VT4W MAIN WALL CONTROL

(Diagram shows wiring connections for the VT4W main wall control to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals and rear view of VT4W.)

3.4.3 ELECTRICAL CONNECTION TO VT6W MAIN WALL CONTROL

(Diagram shows wiring connections for the VT6W main wall control to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals.)

3.4.4 ELECTRICAL CONNECTION TO OPTIONAL AUXILIARY WALL CONTROLS (VBATHW AND VB20W)

NOTE: If an optional auxiliary wall control is activated, this control will override the main wall control commands. (Diagram shows wiring connections for VBATHW or VB20W auxiliary wall controls to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals.)

Once wall control(s) connections are made and checked, close the unit door.

NOTE: For information about the operation of the wall controls, refer to the Main and auxiliary wall controls user guide.

4. ELECTRICAL CONNECTION TO THE FURNACE

WARNING

Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control.

For a furnace connected to a cooling system:

On some older thermostats, energizing the “R” and “G” terminals at the furnace also energizes “Y” at the thermostat, turning on the cooling system. If this occurs, use the ALTERNATE FURNACE INTERLOCK WIRING.

STANDARD FURNACE INTERLOCK WIRING: Connects the unit to the furnace's 24-volt thermostat terminals (R, G, W, Y) and the unit terminal connector (NO, C, NC, I, OC, OL, Y, R, G, B). (Diagram shows wiring for standard furnace interlock with 4 wires for heating/cooling and 2 wires for heating only.)

ALTERNATE FURNACE INTERLOCK WIRING: Connects the unit to the furnace's 24-volt thermostat terminal (R, G, W, Y) and the unit terminal connector (NO, C, NC, I, OC, OL, Y, R, G, B) using wiring nuts for NO and NC connections. (Diagram shows wiring for alternate furnace interlock with 4 wires for heating/cooling and 2 wires for heating only.)

5. SPEED SELECTION

The factory set high speed is 100 CFM, and low speed is approximately 50 CFM. To change these values, the transformer wire taps connections must be changed (see table and illustration below).

SpeedConnectionJU1 Jumper
High Speed100 CFMBL-BLH (1-2)
85 CFMBN-BLM (2-3)
Low Speed65 CFMGY-R
50 CFMR-R

(Diagram shows the internal electronic assembly with transformer taps (BK, BL, BN, GY, R) and JU1 jumper, illustrating connections for different CFM settings. A color code table for wires is also present: BK-BLACK, BL-BLUE, BN-BROWN, G-GREEN, GY-GREY, O-ORANGE, R-RED, W-WHITE, Y-YELLOW, NC-NO CONNECTION.)

6. WIRING DIAGRAM

WARNING

  • Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
  • This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit situation. If the fuse blows, unplug the product from the outlet. Discontinue using the unit and contact technical support.

A detailed wiring diagram (ref: 24600_REV-A) is provided in the manual for qualified personnel, showing connections for motors, capacitors, transformer, controls, and the CPU. It includes notes on UL/CSA certification, wire replacement, compliance with codes, and class 2 circuits. (The original document contains a complex wiring diagram with various components and connections, which is not transcribed here due to complexity and length constraints.)

7. BALANCING THE UNIT

7.1 WHAT YOU NEED TO BALANCE THE UNIT

(Diagram shows a magnehelic gauge with two tubes.)

7.2 PRELIMINARY STAGES TO BALANCE THE UNIT

Make sure the unit is not running in defrost mode while balancing.

Defrost mode can activate below 32°F, preventing balancing. To cancel defrost, use the auxiliary control or jump OC-OL on unit terminal block for 20 minutes of high speed ventilation. Remove jumper after 20 minutes. Another way is to wait 10 minutes after plugging in the unit. Both units start in defrost mode within the first minute of operation.

7.3 BALANCING PROCEDURE

  1. Set the unit to high speed. Make sure the furnace/air handler blower is ON if connected to cold air return ductwork; otherwise, leave it OFF.
  2. Place the magnehelic gauge on a level surface and adjust to zero.
  3. Connect tubing from gauge to exhaust air flow pressure taps and fresh airflow pressure taps. Connect tubes to appropriate high/low fittings. If gauge drops below zero, reverse connections. (Diagram shows airflow paths for FRESH AIRFLOW (HIGH/LOW) and EXHAUST AIRFLOW (HIGH/LOW) with pressure taps for measurement.)
  4. Measure both flows; adjust higher flow to equal the lower one using the balancing damper lever.

CAUTION

When loosening or tightening the damper lever locking screw, never use an electric screwdriver or drill, use a standard screwdriver.

(Diagram shows a hand using a screwdriver to adjust a damper lever.)

CAUTION

Make sure to turn the damper lever to the right direction (opposite to its stopper). Securing the lever in wrong position may cause freezing into the unit.

(Diagrams show correct and incorrect positions for the damper lever.)

  1. Secure both damper levers in place using their locking screw, then shut all pressure taps with small plastic plugs.
  2. Write required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, your name, phone number and business address).

NOTE: The unit is considered balanced even if there is a difference of ±10 cfm between the two air flows.

8. SERVICE PARTS

To ensure good working condition, use only Broan-NuTone LLC genuine replacement parts. These parts are designed to comply with certification standards and maintain safety. Third-party parts may cause damage or reduce performance. Broan-NuTone LLC recommends contacting a certified service depot for all replacement parts and repairs.

The manual provides a detailed list of service parts including: Installation Brackets Kit, Balancing and Backdraft Damper Port Kit, Metal Port Kits, Adjustable Port Kit, Door Metal Keepers and Latches Kit, Blower Kits (Cold Side, Warm Side), Thermistors, Transformer Kit, Capacitors, Electronic Board Kit, Magnet with Bracket Kit, Door Assembly, Filter Kits (Standard and Optional MERV 8), ERV Core, Core Locking Device Kit, Terminal Connector, and Optional Hardware Kit. (The original document contains an exploded view diagram of the ERV100S unit with numbered parts and a corresponding table listing part numbers and descriptions. This table is summarized here.)

9. TROUBLESHOOTING

If the unit does not work properly, reset it by unplugging for one minute and then replugging. If issues persist, refer to the table below.

If the unit's LED is flashing, its sensors have detected a problem. The table indicates where the problem occurs:

LED SIGNALERROR TYPEACTION (Summary)UNIT STATUS (Summary)
LED flashes GREEN (double blink every 2 seconds)Outdoor thermistor errorCheck J12 connector, replace thermistorUnit works but defrosts frequently
LED flashes GREEN (2 blinks per second; faster blink)Building side thermistor errorCheck J20 connector, replace thermistorUnit does not work
LED flashes RED (one blink every 2 seconds)Cold side motor error, open door or magnetic switch bad contactJump J11, diagnose motorUnit does not work
LED flashes RED (2 blinks per second; faster blink)Unit is on protection mode or in error for abnormal timeCheck outdoor temperature, reset unit, diagnose error typeUnit exhausts air without fresh air for 2 hours, then resumes previous mode. If LED continues to flash RED, unit is in error.

WARNING

Risk of electric shocks. Electronic board connections must be checked by qualified personnel only.

Common problems and solutions:

PROBLEMS (Summary)POSSIBLE CAUSES (Summary)YOU SHOULD TRY THIS (Summary)
The error code E1 is displayed on VT8W or VT7W wall control screen.Incompatible control, reverse/misconnected/broken wires.Check control compatibility (page 2), ensure correct wire connections, inspect/replace damaged wires.
No outdoor temperature displayed on VT8W wall control screen.Unit in error, damaged/misconnected RED wire.Check unit LED for flashing, ensure RED wire is connected.
VT8W or VT7W wall control screen alternates between normal display and E3.Defective VT8W or VT7W wall control.Replace the VT8W or VT7W wall control.
The main wall control does not work.Integrated control set to low/high speed, incompatible control, reverse/misconnected/broken wires, defective wall control.Press integrated push button until LED turns off, check control compatibility (page 2), ensure correct wire connections, inspect/replace damaged wires, replace wall control.
Unit does not work (LED not lit on power up).Unit unplugged, no power, defective fuse, unplugged connectors (J10, J9, J8), defective transformer/PCB.Plug in unit, test outlet, check fuse F1, check connectors, check transformer voltage, test PCB.
The auxiliary control does not work.Reverse/misconnected/broken wires, defective auxiliary control.Ensure correct wire connections, inspect/replace damaged wires, test/replace auxiliary control.
A. The supply motor does not work, but exhaust motor works. B. The LED flashes RED.Defective supply motor/capacitor/PCB.Swap motor connections (J5/J4), check capacitor validity, check PCB.
The exhaust motor does not work.Defective exhaust motor/capacitor, bad transformer wire connection, defective transformer/PCB.Swap motor connections (J4/J5), check capacitor validity, check transformer/PCB, adjust JU1 jumper.
Unit shows protection mode error (different than being in protection mode).Wrong defrost cycle selection, defective motor/damper, choked airflow (filters/outdoor port clogged), low inside temperature.Refer to Section 3.2/3.4, inspect unit (motors, damper), inspect ducting, clean filters, balance unit, ensure room temperature is above 64°F.
Models: ERV100S, ERV100S Energy Recovery Ventilator, Energy Recovery Ventilator, Recovery Ventilator, Ventilator

File Info : application/pdf, 20 Pages, 6.70MB

PDF preview unavailable. Download the PDF instead.

installation-guide-broan-erv100s-sky-series-ceiling-mounted-erv

References

BeaulieuD Acrobat Distiller 22.0 (Windows)

Related Documents

Preview Broan ERV100S Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for the BROAN ERV100S Energy Recovery Ventilator, covering setup, electrical connections, ductwork planning, controls, balancing, and troubleshooting for residential applications. Optimize your home's air quality and energy efficiency with this essential manual.
Preview Broan ERV100S Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for the Broan ERV100S Energy Recovery Ventilator, covering unit preparation, ductwork installation, electrical connections, controls, balancing procedures, and troubleshooting for residential applications. Optimize your home's air quality with proper ERV setup.
Preview Broan ERV100S and ERV100SP Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators, covering setup, controls, electrical connections, speed selection, balancing, service parts, and troubleshooting for residential use.
Preview Broan ERV100S and ERV100SP Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators, covering typical installations, unit preparation, ductwork, electrical connections, controls, balancing, service parts, and troubleshooting for residential use.
Preview Broan ERVS100S Energy Recovery Ventilator: Features, Specifications, and Installation Guide
Comprehensive guide to the Broan ERVS100S Energy Recovery Ventilator (ERV), detailing its balanced ventilation capabilities, integrated humidity sensing, energy efficiency, technical specifications, performance data, installation options, and control features for improved indoor air quality.
Preview Broan ERV100S ERV100SP Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators. Learn about typical installations, unit preparation, ductwork planning, electrical connections, speed selection, and troubleshooting for residential use.
Preview Broan ERV/HRV Residential Ventilation Unit Installation Guide
Comprehensive installation guide for Broan ERV70S, ERV70T, HRV80S, HRV90S, HRV80T, and HRV90T ventilation units. This manual provides detailed instructions for residential installation, electrical connections, ductwork planning, unit balancing, and troubleshooting, ensuring optimal performance and energy efficiency.
Preview Broan HRV150S, HRV190S, and ERV180S Installer Manual
Installer manual for Broan HRV150S, HRV190S, and ERV180S residential ventilation units, covering installation, technical data, controls, balancing, service parts, and troubleshooting.