This manual uses specific symbols to emphasize information:
Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
Identifies an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction.
For residential (domestic) installation only. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:
The unit can be hung from joists or ceiling using included brackets or optional chains and spring kit (part no. V61239, sold separately). Bathroom fans and range hoods can exhaust stale air. For multi-level homes, one exhaust register at the highest level is recommended. A standard 3-prong electrical outlet must be available within 3 feet of the unit.
There are three installation methods for houses:
Stale air from registers at the highest level is exhausted outdoors. Fresh air from outdoors is filtered and supplied by registers at the lowest liveable level. Multi-level homes require at least one exhaust register at the highest level. This system is primarily for homes with radiant hot water or electric baseboard heating. (Diagram shows a house with ducts connecting to various rooms, exhausting stale air from upper levels and supplying fresh air to lower levels.)
Stale air from registers at the highest level is exhausted outdoors. Fresh air from outdoors is filtered and supplied to the return (plenum) or supply duct of the forced air unit. It is not essential for the forced air system blower to run when the unit is in operation, but it is recommended. Homes with multiple forced air systems should have one unit on each system. (Diagram shows a house with ducts connecting to a central forced air system, exhausting stale air from upper levels and supplying fresh air to the return/supply plenum.)
Stale air is exhausted outdoors. Fresh air from outdoors is filtered and supplied to the return (plenum) or supply duct of the forced air unit. To avoid cross-contamination and achieve highest efficiencies, the forced air system blower must always be ON. Homes with multiple forced air systems should have one unit on each system. (Diagram shows a house with ducts connecting to a central forced air system, similar to central draw point but emphasizing continuous blower operation.)
Stale air from registers in bathrooms and kitchen is exhausted outdoors. Fresh air from outdoors is filtered and supplied by registers in bedrooms and living room. (Diagram shows a high-rise dwelling layout with ducts exhausting from kitchen/bathrooms and supplying to bedrooms/living room.)
Stale air from registers in bathrooms and kitchen is exhausted outdoors. Fresh air from outdoors is filtered and supplied to the supply duct of the fan-coil system unit. It is not essential for the fan-coil system blower to run when the unit is in operation, but it is recommended. (Diagram shows a high-rise dwelling layout with ducts connecting to a fan-coil system, exhausting from kitchen/bathrooms and supplying to the fan-coil unit.)
All units have 2 ports with integrated balancing dampers (Fresh air to building and Exhaust air to outdoors ports). Before installation, ensure these ports are in wide open position. If not:
When loosening or tightening the damper lever locking screw, never use an electric screwdriver or drill, use a standard screwdriver.
(Diagram shows a damper lever and a screw, indicating how to adjust the damper.)
Choose an appropriate location:
Never handle the unit using its ports; hold the unit by its sides.
Hang the unit using 2 included brackets. (Diagram shows a unit being held by its sides.)
To ensure occupants safety, ensure the brackets are mounted to solid surface (e.g.: concrete ceiling, joists).
The included screws are for wood joist only; do not use them to secure brackets to concrete ceiling or metal joists.
Ensure the unit is completely held by the brackets before continuing the installation.
NOTE: The unit can also be hung using 4 hooks (shaded part in illustration), chains, springs and screws (kit sold separately, part no. V61239). (Diagram shows the unit with four hooks for alternative hanging.)
Make sure the unit is level.
Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas furnace, a gas water heater or a fireplace.
Stale air exhaust ductwork:
Fresh air distribution ductwork:
Stale air exhaust ductwork: Same as for Fully Ducted System.
Fresh air distribution ductwork:
When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety regulations. Please refer to your local building code.
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the ERV. Also, use a steel duct.
Supply side connection:
(Diagram shows a steel duct connecting the ERV to the furnace supply duct, with a minimum 18" distance from the furnace/air handler.)
When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety regulations. Please refer to your local building code.
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the ERV. Also, use a steel duct. For a Return-Return installation, the furnace blower must be in operation when the ERV is in operation.
Supply-return connection:
Stale air intake:
Fresh air distribution: Same instructions as Supply side connection, Section 2.6.2.
NOTE: It is not essential to synchronize the furnace blower operation with the unit operation, but we recommend it.
(Diagram shows a steel duct connecting the ERV to both the furnace supply and return ducts, with minimum distances specified.)
NOTE: All unit ports are designed for minimum 5" diameter ducts, but can connect to bigger sizes using appropriate transitions.
Insulated flexible ducts:
Make sure the balancing dampers are set to wide open position before connecting ducts. Ductwork connecting Fresh air to building and Exhaust air to outdoors ports with exterior hood(s) must be made of insulated ducts, all way long.
All units have Fresh air to building and Exhaust air to outdoors ports equipped with integrated balancing dampers. Ensure these are wide open before installing insulated flexible ducts (See Section 2.2).
If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts.
Procedure for connecting insulated flexible ducts to the unit ports (Exhaust air to outdoors and Fresh air from outdoors ports):
Make sure the vapor barrier on the insulated ducts does not tear during installation to avoid condensation within the ducts.
(Four diagrams illustrate the steps of connecting flexible ducts: 1. Insulation pulled back, 2. Duct attached with tie wrap, 3. Insulation pulled over joint, 4. Duct tape applied.)
Rigid ducts:
Do not use screws to connect the rigid ducts to the ports.
Use a small length (6" length) of flexible duct to connect the rigid duct to the ports to avoid vibration transmissions. Use tie-wraps for connections, then seal with duct tape.
Choose appropriate location for exterior hoods:
Make sure the intake hood is at least 6 feet away from any of the following: Dryer exhaust, high efficiency furnace vent, central vacuum vent, Gas meter exhaust, gas barbecue-grill, any exhaust from a combustion source, garbage bin and any other source of contamination.
Refer to figure for connecting insulated ducts to exterior hoods. An "Anti-gust intake hood" should be installed in regions with a lot of snow. (Diagram shows exterior hoods on a wall, indicating minimum distances between intake and exhaust hoods, and from the ground. It also shows duct connections with tape and tie.)
If using a Tandem Transition, a backdraft damper must be installed on the stale air to outdoors duct. If this causes an interruption in the duct insulation, insulation must be added around the backdraft damper to avoid condensation.
If desired, a Tandem transition kit can be used instead of 2 exterior hoods.
*Patented.
(Diagrams show two types of Tandem Transition kits: VTYIK1 and V14695.)
The ERV100S unit has an integrated control located under the unit, in front of the electrical compartment. Plug in the unit. (Diagram shows the front of the ERV100S unit with an integrated control panel, highlighting an LED (1) and a push button (2).)
The unit booting sequence is similar to a personal computer. Each time the unit is plugged in or after a power failure, it performs a booting sequence before operating.
During booting, the integrated control LED (1) will light up and remain GREEN or AMBER for 3 seconds, then shut off (booting done). Or it will light up in the color of the previous mode if controlled by its integrated control. No command is taken until the unit is fully booted.
If a problem occurs or the unit enters Protection Mode, its LED (1) will blink. The color and pattern depend on the error type or Protection Mode. Refer to the sticker on the unit and Section 9 Troubleshooting for details.
Use the push button (2) to control the unit. The LED (1) indicates the unit's mode:
LED COLOR | RESULTS |
---|---|
AMBER | UNIT IS ON LOW SPEED |
GREEN | UNIT IS ON HIGH SPEED |
NO LIGHT | UNIT IS OFF OR CONTROLLED BY A MAIN CONTROL |
NOTE: When using main control, the integrated control must be turned off.
Units are factory set to normal defrost. For cold regions (outdoor temperature -17°F and lower), extended defrost may be necessary. During the first 3 seconds of booting, the integrated control LED shows the current defrost mode:
LED COLOR | DEFROST MODE |
---|---|
GREEN | NORMAL |
AMBER | EXTENDED |
Within the first 3 seconds of booting, press the push button until the LED blinks, then release. The LED will blink AMBER 5 times, then shut off, then turn RED (unit returns to booting sequence).
The ERV100S unit can be controlled using an optional main control.
NOTES: 1. The integrated control must be turned OFF to use an optional main control. 2. If an optional auxiliary control is used, if activated, this auxiliary control will override the optional main control operation.
Always disconnect the unit before making any connections. Failure in disconnecting power could result in electric shock or damage of the wall control or electronic module inside the unit.
Never install more than one main wall control per unit. Make sure that the wires do not short-circuit between themselves or by touching any other components on the wall control. Avoid poor wiring connections. To reduce electrical interference (noise) potential, do not run wall control wiring next to control contactors or near light dimming circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.
Open the unit door. Insert the terminal connector (included in the installation kit) under the unit, on the electrical compartment front face. Use this terminal connector for electrical connection for main and optional wall controls, then secure the cable(s) with a tie wrap. (Diagram shows the terminal connector being inserted and secured with a tie wrap.)
Check if all wires are correctly inserted in their corresponding holes in the terminal block. A wire is correctly inserted when its orange receptacle is lower than another one without wire. Splice back the end of the cable to access the 4 wires. Strip the end of each wire. Connect each wire to its corresponding terminal: YELLOW wire to "Y", RED wire to "R", GREEN wire to "G" and BLACK wire to "B". Connect the auxiliary control cable, if installed. (Diagram shows a terminal block with wires inserted, illustrating correct and incorrect insertion.)
(Diagram shows wiring connections for the VT7W main wall control to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals.)
(Diagram shows wiring connections for the VT4W main wall control to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals and rear view of VT4W.)
(Diagram shows wiring connections for the VT6W main wall control to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals.)
NOTE: If an optional auxiliary wall control is activated, this control will override the main wall control commands. (Diagram shows wiring connections for VBATHW or VB20W auxiliary wall controls to the unit's terminal block, indicating NO, C, NC, I, OC, OL, Y, R, G, B terminals.)
Once wall control(s) connections are made and checked, close the unit door.
NOTE: For information about the operation of the wall controls, refer to the Main and auxiliary wall controls user guide.
Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control.
On some older thermostats, energizing the “R” and “G” terminals at the furnace also energizes “Y” at the thermostat, turning on the cooling system. If this occurs, use the ALTERNATE FURNACE INTERLOCK WIRING.
STANDARD FURNACE INTERLOCK WIRING: Connects the unit to the furnace's 24-volt thermostat terminals (R, G, W, Y) and the unit terminal connector (NO, C, NC, I, OC, OL, Y, R, G, B). (Diagram shows wiring for standard furnace interlock with 4 wires for heating/cooling and 2 wires for heating only.)
ALTERNATE FURNACE INTERLOCK WIRING: Connects the unit to the furnace's 24-volt thermostat terminal (R, G, W, Y) and the unit terminal connector (NO, C, NC, I, OC, OL, Y, R, G, B) using wiring nuts for NO and NC connections. (Diagram shows wiring for alternate furnace interlock with 4 wires for heating/cooling and 2 wires for heating only.)
The factory set high speed is 100 CFM, and low speed is approximately 50 CFM. To change these values, the transformer wire taps connections must be changed (see table and illustration below).
Speed | Connection | JU1 Jumper | |
---|---|---|---|
High Speed | 100 CFM | BL-BL | H (1-2) |
85 CFM | BN-BL | M (2-3) | |
Low Speed | 65 CFM | GY-R | |
50 CFM | R-R |
(Diagram shows the internal electronic assembly with transformer taps (BK, BL, BN, GY, R) and JU1 jumper, illustrating connections for different CFM settings. A color code table for wires is also present: BK-BLACK, BL-BLUE, BN-BROWN, G-GREEN, GY-GREY, O-ORANGE, R-RED, W-WHITE, Y-YELLOW, NC-NO CONNECTION.)
A detailed wiring diagram (ref: 24600_REV-A) is provided in the manual for qualified personnel, showing connections for motors, capacitors, transformer, controls, and the CPU. It includes notes on UL/CSA certification, wire replacement, compliance with codes, and class 2 circuits. (The original document contains a complex wiring diagram with various components and connections, which is not transcribed here due to complexity and length constraints.)
(Diagram shows a magnehelic gauge with two tubes.)
Make sure the unit is not running in defrost mode while balancing.
Defrost mode can activate below 32°F, preventing balancing. To cancel defrost, use the auxiliary control or jump OC-OL on unit terminal block for 20 minutes of high speed ventilation. Remove jumper after 20 minutes. Another way is to wait 10 minutes after plugging in the unit. Both units start in defrost mode within the first minute of operation.
When loosening or tightening the damper lever locking screw, never use an electric screwdriver or drill, use a standard screwdriver.
(Diagram shows a hand using a screwdriver to adjust a damper lever.)
Make sure to turn the damper lever to the right direction (opposite to its stopper). Securing the lever in wrong position may cause freezing into the unit.
(Diagrams show correct and incorrect positions for the damper lever.)
NOTE: The unit is considered balanced even if there is a difference of ±10 cfm between the two air flows.
To ensure good working condition, use only Broan-NuTone LLC genuine replacement parts. These parts are designed to comply with certification standards and maintain safety. Third-party parts may cause damage or reduce performance. Broan-NuTone LLC recommends contacting a certified service depot for all replacement parts and repairs.
The manual provides a detailed list of service parts including: Installation Brackets Kit, Balancing and Backdraft Damper Port Kit, Metal Port Kits, Adjustable Port Kit, Door Metal Keepers and Latches Kit, Blower Kits (Cold Side, Warm Side), Thermistors, Transformer Kit, Capacitors, Electronic Board Kit, Magnet with Bracket Kit, Door Assembly, Filter Kits (Standard and Optional MERV 8), ERV Core, Core Locking Device Kit, Terminal Connector, and Optional Hardware Kit. (The original document contains an exploded view diagram of the ERV100S unit with numbered parts and a corresponding table listing part numbers and descriptions. This table is summarized here.)
If the unit does not work properly, reset it by unplugging for one minute and then replugging. If issues persist, refer to the table below.
If the unit's LED is flashing, its sensors have detected a problem. The table indicates where the problem occurs:
LED SIGNAL | ERROR TYPE | ACTION (Summary) | UNIT STATUS (Summary) |
---|---|---|---|
LED flashes GREEN (double blink every 2 seconds) | Outdoor thermistor error | Check J12 connector, replace thermistor | Unit works but defrosts frequently |
LED flashes GREEN (2 blinks per second; faster blink) | Building side thermistor error | Check J20 connector, replace thermistor | Unit does not work |
LED flashes RED (one blink every 2 seconds) | Cold side motor error, open door or magnetic switch bad contact | Jump J11, diagnose motor | Unit does not work |
LED flashes RED (2 blinks per second; faster blink) | Unit is on protection mode or in error for abnormal time | Check outdoor temperature, reset unit, diagnose error type | Unit exhausts air without fresh air for 2 hours, then resumes previous mode. If LED continues to flash RED, unit is in error. |
Risk of electric shocks. Electronic board connections must be checked by qualified personnel only.
Common problems and solutions:
PROBLEMS (Summary) | POSSIBLE CAUSES (Summary) | YOU SHOULD TRY THIS (Summary) |
---|---|---|
The error code E1 is displayed on VT8W or VT7W wall control screen. | Incompatible control, reverse/misconnected/broken wires. | Check control compatibility (page 2), ensure correct wire connections, inspect/replace damaged wires. |
No outdoor temperature displayed on VT8W wall control screen. | Unit in error, damaged/misconnected RED wire. | Check unit LED for flashing, ensure RED wire is connected. |
VT8W or VT7W wall control screen alternates between normal display and E3. | Defective VT8W or VT7W wall control. | Replace the VT8W or VT7W wall control. |
The main wall control does not work. | Integrated control set to low/high speed, incompatible control, reverse/misconnected/broken wires, defective wall control. | Press integrated push button until LED turns off, check control compatibility (page 2), ensure correct wire connections, inspect/replace damaged wires, replace wall control. |
Unit does not work (LED not lit on power up). | Unit unplugged, no power, defective fuse, unplugged connectors (J10, J9, J8), defective transformer/PCB. | Plug in unit, test outlet, check fuse F1, check connectors, check transformer voltage, test PCB. |
The auxiliary control does not work. | Reverse/misconnected/broken wires, defective auxiliary control. | Ensure correct wire connections, inspect/replace damaged wires, test/replace auxiliary control. |
A. The supply motor does not work, but exhaust motor works. B. The LED flashes RED. | Defective supply motor/capacitor/PCB. | Swap motor connections (J5/J4), check capacitor validity, check PCB. |
The exhaust motor does not work. | Defective exhaust motor/capacitor, bad transformer wire connection, defective transformer/PCB. | Swap motor connections (J4/J5), check capacitor validity, check transformer/PCB, adjust JU1 jumper. |
Unit shows protection mode error (different than being in protection mode). | Wrong defrost cycle selection, defective motor/damper, choked airflow (filters/outdoor port clogged), low inside temperature. | Refer to Section 3.2/3.4, inspect unit (motors, damper), inspect ducting, clean filters, balance unit, ensure room temperature is above 64°F. |
File Info : application/pdf, 20 Pages, 6.70MB
DocumentDocument![]() |
Broan ERV100S Energy Recovery Ventilator Installation Guide Comprehensive installation guide for the BROAN ERV100S Energy Recovery Ventilator, covering setup, electrical connections, ductwork planning, controls, balancing, and troubleshooting for residential applications. Optimize your home's air quality and energy efficiency with this essential manual. |
![]() |
Broan ERV100S Energy Recovery Ventilator Installation Guide Comprehensive installation guide for the Broan ERV100S Energy Recovery Ventilator, covering unit preparation, ductwork installation, electrical connections, controls, balancing procedures, and troubleshooting for residential applications. Optimize your home's air quality with proper ERV setup. |
![]() |
Broan ERV100S and ERV100SP Energy Recovery Ventilator Installation Guide Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators, covering setup, controls, electrical connections, speed selection, balancing, service parts, and troubleshooting for residential use. |
![]() |
Broan ERV100S and ERV100SP Energy Recovery Ventilator Installation Guide Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators, covering typical installations, unit preparation, ductwork, electrical connections, controls, balancing, service parts, and troubleshooting for residential use. |
![]() |
Broan ERVS100S Energy Recovery Ventilator: Features, Specifications, and Installation Guide Comprehensive guide to the Broan ERVS100S Energy Recovery Ventilator (ERV), detailing its balanced ventilation capabilities, integrated humidity sensing, energy efficiency, technical specifications, performance data, installation options, and control features for improved indoor air quality. |
![]() |
Broan ERV100S ERV100SP Energy Recovery Ventilator Installation Guide Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators. Learn about typical installations, unit preparation, ductwork planning, electrical connections, speed selection, and troubleshooting for residential use. |
![]() |
Broan ERV/HRV Residential Ventilation Unit Installation Guide Comprehensive installation guide for Broan ERV70S, ERV70T, HRV80S, HRV90S, HRV80T, and HRV90T ventilation units. This manual provides detailed instructions for residential installation, electrical connections, ductwork planning, unit balancing, and troubleshooting, ensuring optimal performance and energy efficiency. |
![]() |
Broan HRV150S, HRV190S, and ERV180S Installer Manual Installer manual for Broan HRV150S, HRV190S, and ERV180S residential ventilation units, covering installation, technical data, controls, balancing, service parts, and troubleshooting. |