Broan HRV150S, HRV190S, and ERV180S Installer Manual

Residential Heat Recovery Ventilators (HRV) and Energy Recovery Ventilators (ERV)

About This Manual

This manual covers multiple models (HRV150S, HRV190S, ERV180S); illustrations are typical. Pay attention to symbols:

⚠ WARNING: Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
⚠ CAUTION: Denotes an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction.

Broan-NuTone LLC welcomes suggestions regarding this manual or unit. Contact Broan-NuTone by phone at 1-800-558-1711.

About These Units

Limitation

For residential (domestic) installation only. Installation work and electrical wiring must be performed by qualified persons according to all applicable codes and standards, including fire-rated construction codes.

⚠ WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:
  1. Use this unit only as intended by the manufacturer. For questions, contact the manufacturer at the address or phone number in the warranty.
  2. Before servicing or cleaning, disconnect power cord from electrical outlet.
  3. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
  4. When cutting or drilling into walls or ceilings, avoid damaging electrical wiring and other hidden utilities.
  5. Do not use this unit with any solid-state speed control device other than those listed below:
UnitsOptional Main ControlsOptional Auxiliary Controls
HRV150SVT7W, VT4W or VT6WVB20W and 59W
HRV190S
ERV180S
  1. This unit must be grounded. The power supply cord has a 3-prong grounding plug for personal safety. It must be plugged into a mating 3-prong grounding receptacle, grounded in accordance with national electrical code and local codes and ordinances. Do not remove the ground prong. Do not use an extension cord.
  2. Do not install in a cooking area or connect directly to any appliances.
  3. Do not use to exhaust hazardous or explosive materials and vapors.
  4. When performing installation, servicing, or cleaning, wear safety glasses and gloves.
  5. Due to the unit's weight, two installers are recommended for installation.
  6. If local regulations are more restrictive, those requirements prevail. The installer agrees to conform to them at their expense.
⚠ CAUTION:
  1. To avoid prematurely clogged filters, turn OFF the unit during construction or renovation.
  2. Read the specification label on the product for further information and requirements.
  3. Duct air outside – Do not intake/exhaust air into spaces within walls, ceilings, attics, crawl spaces, or garages.
  4. Intended for residential installation only in accordance with NFPA 90B (for units installed in the USA).
  5. Do not run air ducts directly above or closer than 2 ft to any furnace or its supply plenum, boiler, or other heat producing appliance. If a duct must connect to the furnace return plenum, it must be connected not closer than 9' 10" from this plenum connection to the furnace.
  6. Ductwork must comply with all local and national codes.
  7. When leaving the house for a long period (more than two weeks), a responsible person should regularly check unit operation.
  8. If ductwork passes through an unconditioned space (e.g., attic), the unit must operate continuously except during maintenance/repair. The ambient temperature of the house should never drop below 65°F.

Technical Data

Air Distribution (Normal Operation)

Diagram showing air flow paths in normal operation: Fresh outdoor air (blue arrows) is drawn into the unit, passes through the heat/energy recovery core, and is supplied to the building. Stale indoor air (red arrows) is drawn from the building, passes through the core, and is exhausted outside. The two air streams exchange heat/energy without mixing.

Air Distribution (Defrost Mode)

Diagram showing air flow paths in defrost mode: During defrost, the outdoor air intake is temporarily closed. Indoor air (red arrows) is recirculated through the unit and the heat/energy recovery core to melt any ice buildup. Stale air from the building is still exhausted, and fresh air supply is temporarily paused or reduced.

Defrost Cycles Tables

HRV150S Unit

Outdoor Temperature Fahrenheit (°F)Defrost Cycles (Minutes) - DefrostingDefrost Cycles (Minutes) - Operation Time Between Each Defrost CyclesExtended Defrost Cycles - DefrostingExtended Defrost Cycles - Operation Time Between Each Defrost Cycles
237501030
57251020
-1710201015

ERV180S Unit

Outdoor Temperature Fahrenheit (°F)Defrost Cycles (Minutes) - DefrostingDefrost Cycles (Minutes) - Operation Time Between Each Defrost CyclesExtended Defrost Cycles - DefrostingExtended Defrost Cycles - Operation Time Between Each Defrost Cycles
2310601030
510301020
-1710201015

HRV190S Unit

Outdoor Temperature Fahrenheit (°F)Defrost Cycles (Minutes) - DefrostingDefrost Cycles (Minutes) - Operation Time Between Each Defrost CyclesExtended Defrost Cycles - DefrostingExtended Defrost Cycles - Operation Time Between Each Defrost Cycles
236501030
56251020
-1710201015
NOTE: HRV and ERV Performance Charts are on the specification sheets. Visit www.broan-nutone.com for documents.

Dimensions

HRV150S and HRV190S

Diagram showing dimensions for HRV150S and HRV190S units. The unit is rectangular, approximately 35" (891 mm) wide and 17" (432 mm) high. The main body is 30¼" (768 mm) deep. It features a motorized damper, terminal block location, door, blower assembly, and heat recovery core. Port diameter is 6" (152 mm). Power cord length is 36" (914 mm). Hooks for hanging chains are located on top.

ERV180S

Diagram showing dimensions for ERV180S unit. The unit is rectangular, approximately 39" (991 mm) wide and 17" (432 mm) high. The main body is 34" (864 mm) deep. It features a motorized damper, terminal block location, door, blower assembly, and energy recovery core. Port diameter is 6" (152 mm). Power cord length is 36" (914 mm). Hooks for hanging chains are located on top.

Specifications

MODELHRV150SHRV190SERV180S
WEIGHT65 LB.65 LB.76 LB.
PORT DIAMETER6"6"6"
DRAIN DIAMETER1/2"1/2"1/2"
INSTALLATIONCHAINS AND SPRINGS (PROVIDED WITH THE UNIT)
MOTOR SPEEDHIGH AND LOW SPEED FACTORY SET (OPTIONAL INCREASED LOW SPEED)
ELECTRICAL SUPPLY120 V, 60 Hz120 V, 60 Hz120 V, 60 Hz
POWER CONSUMPTION160 WATTS195 WATTS200 WATTS

Typical Installations

There are three common installation methods:

Fully Ducted System

Primarily for homes with radiant hot water or electric baseboard heating. Moist, stale air is exhausted from high humidity areas (bathrooms, kitchen, laundry room). Fresh air is supplied to bedrooms and main living areas. Bathroom fans and range hoods can supplement stale air exhaust. Homes with multiple levels require at least one exhaust register at the highest level.

Diagram illustrating a fully ducted system: The HRV/ERV unit is connected to a network of ducts. Exhaust ducts draw air from bathrooms, kitchen, and laundry. Supply ducts deliver fresh air to bedrooms and living areas. The system is independent of the furnace ductwork.

Exhaust Ducted System (Source Point Ventilation)

For homes with forced air heating. Moist, stale air is exhausted from high humidity areas. Fresh air is supplied to the cold air return or supply duct of the furnace. Bathroom fans and range hoods can supplement stale air exhaust. Homes with multiple levels require at least one exhaust register at the highest level.

NOTE: For this installation type, it is not essential for the furnace blower to run when the unit is operating, but it is recommended.

Diagram illustrating an exhaust ducted system: The HRV/ERV unit draws stale air from specific points (bathrooms, kitchen) via dedicated exhaust ducts. Fresh air from the unit is then supplied into the furnace's return or supply ductwork, allowing the furnace blower to distribute it throughout the house.

Simplified (Volume Ventilation)

For homes with forced air heating. Fresh air and exhaust air flow through the furnace ducts, simplifying installation. Bathroom fans and a range hood are suggested for exhausting stale air.

NOTE: For this installation type, the furnace blower must be running when the unit is operating.

Diagram illustrating a simplified (volume ventilation) system: The HRV/ERV unit is connected directly to the furnace's return and supply ducts. This allows the furnace blower to handle both fresh air distribution and stale air exhaust throughout the entire house.

Installation

⚠ WARNING: When applicable local regulation comprises more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses.
⚠ WARNING: When performing installation, servicing or cleaning the unit, it is recommended to wear safety glasses and gloves.

Inspect the Content of the Box

NOTE: Before installation, remove the shipping bracket by unscrewing its wing nut and loosening its two retaining screws. Diagram shows a wing nut and two retaining screws on a shipping bracket.

Locating and Mounting the Unit

Choose an appropriate location:

Hang the unit with the 4 chains and springs provided. Diagram shows the unit being hung from a ceiling using chains and springs, with connections for ductwork and a drain.

Planning of the Ductwork

  1. Follow Section 3.4 to determine appropriate duct diameters.
  2. Keep it simple: minimum bends and joints. Minimize insulated duct length.
  3. Do not use wall cavities as ducts. Do not use branch lines smaller than 4" Ø.
  4. Do not ventilate crawl spaces or cold rooms. Do not attempt to recover exhaust air from a dryer or range hood (causes clogging). Use sheet metal for kitchen exhaust duct.
  5. Plan for at least one exhaust register on the highest lived-in level if the house has 2 floors or more.

Calculating the Duct Size

Use the table below to ensure ducts carry air flows at or under recommended values. Avoid installing ducts near maximum values, and never exceed maximum values.

DUCT DIAMETERRECOMMENDED AIR FLOWMAXIMUM AIR FLOW
CFML/Sm³/hCFML/Sm³/h
4" (102 mm)4019686028102
5" (127 mm)753512711052187
6" (152 mm)1205720418085306
7" (178 mm)18587314270127459
8" (203 mm)260123442380179645
NOTE: Examples 3.4.1 and 3.4.2 use imperial measures; the same calculation applies to metric measures.

Example of Calculation

PROBLEM: Installation requires two exhaust registers (kitchen, bathroom). These connect to a main duct, which connects to the unit (high speed performance 140 cfm). What size duct for the main exhaust duct and for the two end branches?

Diagram illustrating ductwork for the example: A main branch (6" Ø, 140 CFM) splits into two end branches (5" Ø, 70 CFM each) leading to registers.

SOLUTION: Simplified method (refer to ASHRAE or HRAI HANDBOOK for detailed method).

NOTE: A 4" Ø duct would have been too small (max 60 cfm).

Example of a Design for a Fully Ducted System for a Unit Having a High Speed Performance of 222 CFM

Diagram illustrating a complex fully ducted system with various duct diameters and CFM values. A 7" Ø main duct (222 CFM) branches into smaller ducts (e.g., 6" Ø 129 CFM, 6" Ø 93 CFM, 6" Ø 84 CFM, 6" Ø 96 CFM, 6" Ø 138 CFM) and further into 5" Ø and 4" Ø branches (e.g., 5" Ø 64 CFM, 5" Ø 65 CFM, 4" Ø 42 CFM). This shows how different duct sizes are used to manage varying airflows throughout a residential ventilation system.

Installing the Ductwork and the Registers

⚠ WARNING: Never install a stale air exhaust register in a room with a combustion device (gas furnace, water heater, fireplace).
⚠ CAUTION: Ductwork must comply with all local and national codes.

Fully Ducted System (as illustrated in Section 2.1)

Stale Air Exhaust Ductwork:

Fresh Air Distribution Ductwork:

Exhaust Ducted System (as illustrated in Section 2.2)

Stale Air Exhaust Ductwork:

Same as for Fully Ducted System (point 3.5.1).

Fresh Air Distribution:

⚠ WARNING: When connecting ducts to the furnace, installation must comply with all applicable codes and standards. Refer to local building code.
⚠ CAUTION: When connecting ducts to the furnace supply duct, this duct must be sized to support additional airflow from the ERV/HRV. Use metal duct. It is recommended that the ERV/HRV runs when the furnace is operating to prevent backdrafting.

Two methods for connecting the unit to the furnace:

Method 1: Supply Side Connection

Method 2: Return Side Connection

NOTE: For Method 2, it is not essential for the furnace blower to run when the unit is operating, but it is recommended. If desired, synchronize furnace blower operation with HRV/ERV operation (See Section 5).

Simplified Installation (as illustrated in Section 2.3)

⚠ WARNING: When performing duct connection to the furnace, installation must be done in accordance with all applicable codes and standards. Please refer to your local building code.
⚠ CAUTION: When connecting ducts to the furnace ducts (Method 1), these ducts must be sized to support the additional airflow produced by the ERV/HRV. Also, the supply duct must be a metal duct. It is recommended that the ERV/HRV is running when the furnace is in operation in order to prevent backdrafting inside ERV/HRV.

Two methods for connecting the unit to the furnace ducts:

Method 1: Return-Supply

Diagram shows the HRV/ERV unit connected to the furnace. The stale air intake connects to the furnace return duct (minimum 10 feet from furnace). The fresh air distribution connects to the furnace supply duct (minimum 18 inches from furnace). Both connections use metal duct.

Method 2: Return-Return

Diagram shows the HRV/ERV unit connected to the furnace. Both the stale air intake and fresh air distribution connect to the furnace return duct. The stale air intake connection is not less than 10 feet from the furnace, and the fresh air distribution connection is not less than 3 feet from the furnace.

Stale Air Intake:

Fresh Air Distribution:

Same instructions as for Method 1 or Method 2, section 3.5.2.

⚠ CAUTION: If using Method 2, ensure the furnace blower operation is synchronized with the unit operation! See Section 5.

For Method 2 (Return-Return), ensure a distance of at least 3 feet between the 2 connections to the furnace duct.

NOTE: For Method 1, it is not essential to synchronize furnace blower operation with HRV/ERV operation, but it is recommended.

Connecting the Ducts to the Unit

⚠ CAUTION: If ducts go through an unconditioned space (e.g., attic), always use insulated ducts.

Insulated Flexible Ducts

Procedure for connecting insulated flexible duct to unit ports (exhaust to outside and fresh air from outside):

  1. Pull back insulation to expose flexible duct and place it over inner port ring.
  2. Install good quality aluminum duct tape on flexible duct to prevent potential water leakage.
  3. Attach flexible duct to port using tie wrap.
  4. Pull insulation over the joint and tuck it between inner and outer rings of the double collar.
  5. Pull down vapor barrier (shaded part in illustrations) over outer ring to cover it completely. Fasten vapor barrier using port strap (included in unit parts bag). Insert one collar pin through vapor barrier and first strap hole, then insert other collar pin through vapor barrier and center strap hole, and close loop by inserting first collar pin in last strap hole.

Diagram illustrating the steps for connecting flexible ducts: 1. Flexible duct is placed over the inner port ring. 2. Aluminum duct tape is applied. 3. Tie wrap secures the duct to the port. 4. Insulation is pulled over the joint. 5. Vapor barrier is pulled down and secured with a collar pin and strap, showing the collar pin inserted through the vapor barrier and strap holes.

⚠ CAUTION: Ensure vapor barrier on insulated ducts does not tear during installation to avoid condensation within ducts.

Rigid Ducts

To prevent potential water leakage, use good quality aluminum duct tape to connect rigid ducts to ports.

⚠ CAUTION: Do not use screws to connect rigid ducts to ports.

Diagram showing the unit's ports with balancing dampers. Ensure both balancing dampers are left in a fully open position before connecting the Fresh air to building port and Exhaust air from building port.

Installing the Exterior Hoods

Choose appropriate location for exterior hoods:

⚠ WARNING: Ensure intake hood is at least 6 feet away from: dryer exhaust, high efficiency furnace vent, central vacuum vent, gas meter exhaust, gas barbecue-grill, any combustion source exhaust, garbage bin, and any other contamination source.

Diagram illustrating exterior hood installation: Shows an exhaust hood and an intake hood on an exterior wall. They are separated by a minimum of 6 feet horizontally. Both hoods are at least 18 inches from the ground. Ductwork connects to the hoods, with tape and duct ties used for sealing. Caulking is applied around the hoods for weather sealing. An optional duct location is shown for reference. An "Anti-Gust Intake Hood" is recommended in snowy regions.

Connecting the Drain

⚠ CAUTION: A drain tubing (included) must be installed for all HRV units. For ERV units, it is not required, but recommended for climates where outside temperature typically remains below -13°F (over 24 hours) combined with indoor humidity of 40% or higher.

HRV Units

Diagram showing HRV drain connection: Two sections of plastic tube (minimum 12" long) attach to inner drain fittings under the unit. These join to a "T" junction and then to a main tube. This setup prevents unpleasant odors from the drain source. The main tube runs to a floor drain or alternative drain pipe/pail. If using a pail, the tube end should be approximately 1" from the top of the pail to prevent water from being drawn back up into the unit.

ERV Unit

Diagram showing ERV drain connection: A water trap loop is formed in the tube to prevent unpleasant odors from the drain source. The tube runs to a floor drain or alternative drain pipe/pail. A drain plug is inserted into the alternate drain fitting on top of the unit. If the drain will not be used, a second drain plug is inserted into the drain fitting underneath the unit. If using a pail, the tube end should be approximately 1" from the top of the pail to prevent water from being drawn back up into the unit.

Controls

Integrated Control

All units have an integrated control on the electrical compartment front. Use the push button (1) to control the unit. The LED (2) indicates the unit's mode.

NOTES:
  1. The integrated control must be turned OFF to use an optional main control.
  2. If an optional auxiliary control is used, if activated, this auxiliary control will override the optional main control.

Table for operating the unit using its integrated control:

PRESS ON PUSH BUTTONLED COLORRESULTS
ONCEAMBERUNIT IS ON LOW SPEED
TWICEGREENUNIT IS ON HIGH SPEED
THREE TIMESNO LIGHTUNIT IS OFF

If a problem occurs, the integrated control LED (2) will blink. Color indicates error type. Refer to Section 9 Troubleshooting (pages 19-20).

Boot Sequence

Similar to a computer boot sequence. Each time the unit is plugged in or after a power failure, it performs a 30-second booting sequence. During booting, the integrated control LED lights GREEN (normal defrost) or AMBER (extended defrost) for 5 seconds, then off for 2 seconds. Then, RED lights for the rest of booting. During RED light phase, unit checks and resets motorized damper position. Once set, RED light turns off, and booting is done.

NOTE: No command will be taken until the unit is fully booted.

Setting Extended Defrost

Unit is factory set to normal defrost. In cold regions, extended defrost may be necessary. During the first 5 seconds of booting (while LED is GREEN), press the push button until LED turns AMBER (about 3 seconds).

Diagram shows the integrated control with a push button (1) and an LED indicator (2).

Electrical Connection to Optional Wall Controls

For convenience, units can be controlled using an optional main wall control.

⚠ WARNING: Always disconnect the unit before making any connections. Failure to disconnect power could result in electrical shock or damage to the wall control or electronic module.
⚠ CAUTION: Never install more than one optional main wall control per unit. Ensure wires do not short-circuit or touch other components. Avoid poor wiring connections. To reduce electrical interference (noise), do not run wall control wiring next to control contactors, light dimming circuits, electrical motors, dwelling/building power, lighting wiring, or power distribution panel.

Use the terminal connector included in the installation kit for electrical connection. Check if all wires are correctly inserted (a wire is correctly inserted when its orange receptacle is lower than another one without wire). Diagram shows correct (A) and incorrect (B) wire insertion into a terminal block.

Once wall control(s) connections are made, insert the terminal connector into the electrical compartment front face.

NOTE: For wall control operation, refer to the user guide.

Electrical Connection to VT7W Main Wall Control

Diagram showing the wiring connections for the VT7W main wall control. The terminal block has connections labeled NO, C, NC, I, OC, OL, Y, R, G, B. The VT7W control unit is shown with its display and buttons.

Electrical Connection to VT4W Main Wall Control

Diagram showing the wiring connections for the VT4W main wall control. The terminal block has connections labeled NO, C, NC, I, OC, OL, Y, R, G, B. The VT4W control unit is shown with its rear view, indicating G and B terminals.

Electrical Connection to VT6W Main Wall Control

Diagram showing the wiring connections for the VT6W main wall control. The terminal block has connections labeled NO, C, NC, I, OC, OL, Y, R, G, B. The VT6W control unit is shown with its display and buttons, branded BROAN.

Electrical Connection to Optional Auxiliary Wall Controls

Diagram showing the wiring connections for optional auxiliary wall controls (59W and VB20W). The terminal block has connections labeled NO, C, NC, I, OC, OL, Y, R, G, B. Both 59W and VB20W units are shown connected to this terminal block.

Electric Connection to the Furnace

⚠ WARNING: Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control.

For a Furnace Connected to a Cooling System:

On some older thermostats, energizing "R" and "G" terminals at the furnace also energizes "Y", turning on the cooling system. If this type of thermostat is identified, use the ALTERNATE FURNACE INTERLOCK WIRING.

Standard Furnace Interlock Wiring

Diagram showing standard furnace interlock wiring. The unit terminal connector (with terminals O, C, O, L, Y, G, R, B) connects to the furnace's 24-volt terminal block (with terminals R, G, Y, W, C). Four wires connect the unit to the thermostat terminals, and two wires connect for cooling system. This setup is for heating only.

Alternate Furnace Interlock Wiring

Diagram showing alternate furnace interlock wiring. The unit terminal connector (with terminals NO, C, NC, I, OC, OL, Y, G, R, B) connects to the furnace's 24-volt terminal block (with terminals R, G, Y, W, C). Four wires connect the unit to the thermostat terminals, and two wires connect for cooling system. This setup is for heating only, with wiring nuts for connections.

Wiring Diagram

⚠ WARNING:
  • Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
  • This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit. If the fuse blows, unplug the product and contact technical support.

Detailed wiring diagram for the HRV/ERV unit, showing both a logic diagram and a physical wiring diagram. It includes connections for 120V, 60Hz line and neutral, fan motors (HI, MED, LOW speeds), damper motor, defrost temperature sensor, electronic assembly, door interlock switch, and various terminal blocks (J1, J2, J3, J4, J6, J8, J9, J10, J11, J12, J13, J14). The diagram also shows the fuse (F1), capacitors, and optional remote control connections. Color codes for wires are provided: BK (BLACK), BL (BLUE), BN (BROWN), OR (ORANGE), R (RED), W (WHITE), GY (GRAY), Y (YELLOW), GN (GREEN). Notes indicate UL/CSA certification, wire replacement, compliance with codes, remote control availability, and furnace fan circuit requirements.

Balancing the Unit

What You Need to Balance the Unit

Diagram showing a magnehelic gauge with a dial indicating pressure readings in inches of water and Pascals, and two ports for connecting plastic tubes.

Preliminary Stage to Balance the Unit

Diagram showing a balancing damper with an adjustment screw and a scale, indicating its open position.

Balancing Procedure

  1. Set the unit to high speed. Ensure furnace/air handler blower is ON if connected to cold air return ductwork; otherwise, OFF. If outside temperature is below 32°F, ensure unit is not in defrost (wait 10 minutes after plugging in).
  2. Place the magnehelic gauge on a level surface and adjust to zero.
  3. Connect tubing from gauge to EXHAUST air flow pressure taps. Connect tubes to appropriate high/low fittings. If gauge drops below zero, reverse connections.
    NOTE: Start with exhaust air flow reading as it typically has more restriction than fresh air, especially in fully ducted or source point ventilation.
    Place gauge upright and level. Record equivalent AIR FLOW from reading according to balancing chart.
  4. Move tubing to FRESH air flow pressure taps. Adjust fresh air balancing damper until FRESH air flow is approximately the same as EXHAUST air flow. If FRESH air flow is less than EXHAUST air flow, go back and adjust exhaust balancing damper to equal FRESH air flow.
  5. Secure both dampers in place with a fastening screw.
  6. Write required air flow information on a label near the unit (date, maximum speed air flows, your name, phone number, business address).
  7. Install 4 pressure taps plugs (included in parts bag).

Diagram illustrating air flow balancing: Shows the unit with EXHAUST AIR FLOW and FRESH AIR FLOW ports. Arrows indicate air movement and pressure taps for connecting the magnehelic gauge. The diagram shows how to measure HIGH and LOW pressure points for both exhaust and fresh air flows.

NOTES:
  1. Use conversion chart with unit to convert magnehelic gauge readings to cfm values.
  2. Unit is balanced if difference is ±10 cfm (or ± 5 l/s or 17 m³/h) between the two air flows.

Service Parts

Exploded view diagram of the HRV/ERV unit showing various components with numerical labels. Key components include: Hinge assembly, Damper supply port assembly, Damper system actuator, Thermistor, Capacitor, Electronic board, Transformer, Double collar port, Blower assembly, Square damper kit, Magnet switch, Door assembly, Door latches, Diffuser, Filter kit, Core, Balancing damper, and Balancing double collar port.

Parts list table:

ITEMDESCRIPTIONHRV150SHRV190SERV180S
1Hinge assembly kitSV13036SV13036SV13036
2Damper supply port assemblySV17245SV17245SV17245
3Damper system actuator (including no. 4)SV17235SV17235SV17235
4Thermistor kitSV17242SV17242SV17242
5Capacitor 7.5 µFSV17240SV17240SV17240
6Electronic boardSV60809SV60809SV60812
7TransformerSV17244SV17244SV17244
8Double collar portSV60818SV60818SV60818
9Blower assembly (including no. 10)SV60804SV60805SV60806
10Square damper kitSV17243SV17243SV17243
11Magnet switchSV19060SV19060SV19060
12Door assembly (including hinges and latches)SV63500SV63500SV63501
13Door latches (keeper) and screwsSV00887 (2) SV00601 (4)SV00887 (2) SV00601 (4)SV00887 (2) SV00601 (4)
14DiffuserSV60822SV60822SV62756
15Filter kitSV60800SV60800SV60799
16CoreSV60801SV60803SV16582
17Door latches and screwsSV00886 (2) SV00601 (4)SV00886 (2) SV00601 (4)SV00886 (2) SV00601 (4)
18Balancing damperSV02253SV02253SV02253
19Balancing double collar portSV02256SV02256SV02256
*Terminal connectorSV16416SV16416SV16416
*Hardware kitSV20510SV20510SV20606

* Not shown.

Replacement Parts and Repairs

To ensure proper unit function, use only Broan-NuTone LLC genuine replacement parts. These parts are designed to comply with certification standards and maintain safety. Third-party parts may cause damage and reduce performance. Broan-NuTone LLC recommends contacting a certified service depot for all replacement parts and repairs.

Troubleshooting

If the integrated control LED flashes, unit sensors detected a problem. See list below:

⚠ WARNING: Some diagnosis procedures require unit operation. Open unit door and bypass magnetic switch by putting door white magnet on it. Be careful with moving/live parts. Risk of electric shocks. Electronic board connections must be checked by qualified personnel only.
PROBLEMSPOSSIBLE CAUSESYOU SHOULD TRY THIS
1. The error code E1 is displayed on VT7W wall control screen.
  • The wires may be in reverse position.
  • The wires may be broken.
  • The wires may have a bad connection.
  • Ensure color coded wires are connected to appropriate places.
  • Inspect every wire and replace damaged ones.
  • Ensure wires are correctly connected.
2. VT7W wall control screen alternates between normal display and E3 or E4 appears on screen.
  • The VT7W wall control needs to be reset.
  • Reset VT7W wall control by pressing simultaneously on DOWN arrow and OK keys for 8 seconds. Unplug unit for 30 seconds. Plug unit back.
3. Unit does not work (no LED is lit on the integrated control).
  • The VT7W wall control is defective.
  • The transformer may be defective.
  • The circuit board may be defective.
  • The unit is unplugged.
  • The unit door is opened.
  • A fuse is blown.
  • Wrong control connections.
  • If problem not solved, replace VT7W wall control.
  • Check for 24 VAC on J8-1 and J8-2.
  • Unplug unit. Disconnect main and optional controls. Jump G and B terminals. Plug unit back, wait 10 seconds. If motor runs on high speed and damper opens, circuit board is not defective.
  • Plug unit.
  • Close unit door.
  • Unplug product. Inspect fuse on circuit board (F1 on wiring diagram, page 16). If blown, discontinue use and contact technical support.
  • Try integrated control (Section 4.1).
4. The damper actuator does not work or rotates continuously.
  • The damper actuator or integrated damper port mechanism may be defective (integrated control LED flashes AMBER and unit is OFF).
  • The circuit board or the transformer may be defective (integrated control LED flashes AMBER and unit is OFF).
  • Unplug unit. Disconnect main and optional controls. Wait 10 seconds and plug unit back. Check if damper opens. If not, use multimeter to check for 24VAC on J12-1 and J12-2 (electrical compartment). If 24VAC, replace entire port assembly.
    NOTE: Normal small delay (7-8 seconds) before detecting 24 VAC signal at starting-up. Signal stays during 17-18 seconds before disappearing.
  • If no 24 VAC, check for 24 VAC between J8-1 and J8-2. If 24VAC, replace circuit board; if no 24 VAC, change transformer.
5. The wall control does not work OR its indicator flashes.
  • The wires may be in reverse position.
  • The wires may be broken.
  • The wire in the wall OR the wall control may be defective.
  • Ensure color coded wires are connected to appropriate places.
  • Inspect every wire and replace damaged ones.
  • Remove wall control and test it right beside unit using shorter wire. If it works, change wire. If not, change wall control.
6. The VB20W push-button does not work OR its indicator light does not stay on.
  • The wires may be in reverse position.
  • The VB20W may be defective.
  • Ensure color coded wires are connected to appropriate places.
  • Jump OL and OC terminals. If unit switches to high speed, remove VB20W push-button and test it right beside unit using shorter wire. If it works, change wire. If not, change VB20W.

PDF preview unavailable. Download the PDF instead.

Installation-Guide-HRV150S-HRV190S-ERV180S Acrobat Distiller 20.0 (Windows)

Related Documents

Preview Broan ERV/HRV Residential Ventilation Unit Installation Guide
Comprehensive installation guide for Broan ERV70S, ERV70T, HRV80S, HRV90S, HRV80T, and HRV90T ventilation units. This manual provides detailed instructions for residential installation, electrical connections, ductwork planning, unit balancing, and troubleshooting, ensuring optimal performance and energy efficiency.
Preview Broan ERV140 ECM, HRV160 ECM, HRV160 Installation Guide
Comprehensive installation guide for Broan ERV140 ECM, HRV160 ECM, and HRV160 energy and heat recovery ventilators. This document covers technical data, typical installations, ductwork, controls, and troubleshooting for residential use, ensuring energy efficiency and proper operation.
Preview Broan ERV100S Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for the Broan ERV100S Energy Recovery Ventilator, covering typical residential installations, unit preparation, ductwork planning, electrical connections, controls, speed selection, balancing procedures, service parts, and troubleshooting. Includes safety warnings and detailed instructions for optimal performance and compliance with building codes.
Preview Broan HRV150FL HRV190FL Heat Recovery Ventilator Installer Manual
This installer manual provides comprehensive instructions for the installation, operation, and troubleshooting of Broan HRV150FL and HRV190FL Heat Recovery Ventilators. It includes detailed technical data, specifications, typical installation methods, ductwork planning, electrical connections, wiring diagrams, balancing procedures, and a service parts list, ensuring optimal performance and compliance for residential applications.
Preview Broan ERV100S and ERV100SP Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators, covering typical installations, unit preparation, ductwork, electrical connections, controls, balancing, service parts, and troubleshooting for residential use.
Preview Broan ERV/HRV ECM User Guide: ERV200, ERV250, HRV200, HRV250
User guide for Broan Energy Recovery Ventilator (ERV) and Heat Recovery Ventilator (HRV) models ERV200 ECM, ERV250 ECM, HRV200 ECM, and HRV250 ECM. Includes sections on defrosting, booting sequence, controls, maintenance, and troubleshooting.
Preview Broan ERV100S and ERV100SP Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators, covering setup, controls, electrical connections, speed selection, balancing, service parts, and troubleshooting for residential use.
Preview Broan ERV100S ERV100SP Energy Recovery Ventilator Installation Guide
Comprehensive installation guide for Broan ERV100S and ERV100SP Energy Recovery Ventilators. Learn about typical installations, unit preparation, ductwork planning, electrical connections, speed selection, and troubleshooting for residential use.