Important Safety Information
Warning: Devices must be installed in an approved enclosure by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
French: Les appareils doivent être installés dans un lieu jugé apte, par un électricien qualifié et conformément aux règles et normes locales et nationales en matière d'électricité et de construction.
German: Die Geräte müssen von einem geprüften Elektriker entsprechend allen nationalen und lokalen Elektro und Bauvorschriften in einem zugelassenen Gehäuse installiert werden.
Spanish: Los dispositivos se deben instalar en un recinto aprobado por un electricista cualificado de acuerdo a todos los reglamentos eléctricos y de construcción locales y nacionales pertinentes.
Italian: I dispositivi devono essere installati da un elettricista qualificato in un luogo approvato, in conformità a tutti gli standard e le norme nazionali e locali vigenti in materia di impianti elettrici e costruzioni edilizie.
Dutch: Apparaten moeten door een erkende elektricien worden geïnstalleerd in een goedgekeurde behuizing in overeenstemming met alle nationale en lokale elektriciteits - en bouwvoorschriften en wetgeving.
Japanese: デバイスを取り付ける際は、資格のある電気技師に依頼し、電気と建設に関する国および地域のすべての法令に従って、認可されている筐体内に取り付けてください。
Chinese: 根据国家/地区及当地的电气与建筑规范和法规,该设备必须由有资质的电工安装在经批准的外罩内。
Arabic: يلزم تركيب الأجهزة داخل حاوية معتمدة، من قبل كهربائي مؤهل وفقًا لجميع قوانين ولوائح الكهرباء والإنشاءات الوطنية والمحلية.
Product Overview
The Philips Dynalite DDRC1220FR-GL is a Relay Controller designed for advanced lighting control systems.
Dimensions: 215 mm (8.46 in) width, 64 mm (2.52 in) depth, 45 mm (1.77 in) height.
Operating Conditions: 0° C (32° F) to 50° C (122° F), Humidity ≤ 90%.
Certifications: CE, UKCA, RCM, C-Tick, FCC, UL Listed, IEC Pollution Degree II.
Installation Examples
The following diagrams illustrate typical installation configurations.
Example 1: General Use Wiring (CH1-CH12)
This example shows the wiring for general use loads, with connections for 12 channels. Each channel supports up to 20A.
Wiring details:
- Supply: N, L1, L2, L3
- Channels: CH1 to CH12, with IN and OUT terminals for each.
- Communication: RS-485 DyNet/DMX Rx, SHLD, GND, D+, D-, +12V, AUX/UL924.
- Wire Gauge: Up to 5.5 mm² (10+ AWG)
- Torque: 0.62 Nm (5.5 Lb-in)
Note: The diagram shows specific wiring for a 3-phase supply (3~) and single-phase supply (1~).
Example 2: 3-Phase Supply Wiring (277/480 V~)
This example details wiring for a 3-phase, 277/480V~ supply, also covering 12 channels.
Wiring details:
- Supply: N, L1, L2, L3
- Channels: CH1 to CH12, with IN and OUT terminals for each.
- Communication: RS-485 DyNet/DMX Rx, SHLD, GND, D+, D-, +12V, AUX/UL924.
- Wire Gauge: Up to 5.5 mm² (10+ AWG)
- Torque: 0.62 Nm (5.5 Lb-in)
Note: Some connections are marked with 'xx', indicating specific configurations or exclusions.
Example 3: Communication Wiring (RS-485 DyNet)
This section illustrates the connection for the RS-485 DyNet communication bus.
Wiring details:
- Connectors: RJ12 sockets are used for communication.
- Cable Length: Recommended maximum cable length is 20 meters (approx. 65 feet).
- Terminals: D+, D-, GND, +12V, AUX/UL924.
Note: The diagram shows the internal connections for the RS-485 DyNet interface.
Output Ratings and Specifications
Output Ratings/Channel (CH)
Load Type | CH1-CH12 |
---|---|
General Use | 16 A, 277 V~ (UL) |
Incandescent | 20 A, 240 V~ (CE) |
Standard Driver | 16 A, 277 V~ |
Electronic Driver | 16 FLA (1 HP), 120 V~ |
Motor | 14.5 FLA (2 1/2 HP), 240 V~ 14.1 FLA (3 HP), 277 V~ |
Inrush Current | 500 A |
Output Ratings/Group
CH-CH ≤ 300 V~ (UL) / 400 V~ (CE)
DDRC1220FR-GL ≤ 180 A
Supply Voltage: 100-240 V~, 0.25 A
IEC Overvoltage Category: III
Device Interface Diagram
The diagram shows the layout of the device terminals, including SUPPLY, CH1-CH12 (IN/OUT), communication ports (RS-485 DyNet/DMX Rx), and auxiliary connections.
Key Components:
- Microprocessor (μP): Indicates the control unit.
- Relay Outputs: QO symbols represent the relay contacts for each channel.
- Communication Ports: RJ12 connectors for RS-485 DyNet/DMX.
- Auxiliary Power: +12V and AUX/UL924 terminals.
- Grounding: SHLD and GND terminals.
FCC Compliance and Installation Notes
Federal Communications Commission (FCC) Compliance Notice: This equipment complies with Part 15 of the FCC Rules for Class B digital devices. It generates, uses, and can radiate radio frequency energy. If interference occurs, users are encouraged to take corrective measures such as reorienting the antenna, increasing separation, or consulting a dealer.
Canadian Compliance: This Class B digital apparatus complies with Canadian ICES-003.
Installation Standards: Installation of home and building automation systems must comply with IEC 60364. Ensure communication wire temperature limits and current-carrying capacities are not exceeded.
General Notes:
- The product is manufactured by Signify Holding.
- Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V.
- All other trademarks are owned by Signify Holding or their respective owners.