Philips Dynalite DDBC300-D DALI Driver Controller
Installation Instructions
General Safety and Installation Requirements
Important: Devices must be installed in an approved enclosure by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
The installation must comply with all national and local electrical and construction codes and regulations. Devices must be installed in an approved enclosure by a qualified electrician.
French: Les appareils doivent être installés dans un lieu jugé apte, par un électricien qualifié et conformément aux règles et normes locales et nationales en matière d'électricité et de construction.
German: Die Geräte müssen von einem geprüften Elektriker entsprechend allen nationalen und lokalen Elektro und Bauvorschriften in einem zugelassenen Gehäuse installiert werden.
Spanish: Los dispositivos se deben instalar en un recinto aprobado por un electricista cualificado de acuerdo a todos los reglamentos eléctricos y de construcción locales y nacionales pertinentes.
Italian: I dispositivi devono essere installati da un elettricista qualificato in un luogo approvato, in conformità a tutti gli standard e le norme nazionali e locali vigenti in materia di impianti elettrici e costruzioni edilizie.
Dutch: Apparaten moeten door een erkende elektricien worden geïnstalleerd in een goedgekeurde behuizing in overeenstemming met alle nationale en lokale elektriciteits en bouwvoorschriften en wetgeving.
Japanese: デバイスを取り付ける際は、資格のある電気技師に依頼し、電気と建設に関する国および地域のすべての法令に従って、認可されている筐体内に取り付けてください。
Chinese: 根据国家/地区及当地的电气与建筑规范和法规,该设备必须由有资质的电工安装在经批准的外罩内。
Arabic: يلزم تركيب الأجهزة داخل حاوية معتمدة، من قبل كهربائي مؤهل وفقًا لجميع قوانين ولوائح الكهرباء والإنشاءات الوطنية والمحلية
Environmental Information: IEC Pollution Degree II
Certifications: CE, UK CA
Operating Temperature: 0° C (32° F) to 40° C (104° F)
Humidity: ≤90%
Product Dimensions and Connections
Dimensions: 211 mm (8.31 in) width, 94 mm (3.70 in) height, 75 mm (2.95 in) depth.
Connection Type: RJ12 connector for DALI communication.
Diagram Description: The diagram shows the DDBC300-D unit with its dimensions and the RJ12 port.
Electrical Connections and Specifications
Power Input: 100-240 V~ 0.5 A
DALI Bus: Supports DALI 1, DALI 2, DALI 3 with up to 64 devices per channel, guaranteed 128 mA, maximum 250 mA. Insulation: basic.
DALI Wiring: DA-, DA+, SHLD terminals for DALI communication. Maximum wire size: 2.5 mm² (12 AWG). Torque: 0.5 Nm (4.4 Lb-in).
Auxiliary Power: +12V output, 200 mA maximum. AUX/UL924 terminal for auxiliary power.
RS-485 DyNet/DMX: Rx terminal for communication. Maximum wire size: 2.5 mm² (12 AWG). Torque: 0.5 Nm (4.4 Lb-in).
IEC Overvoltage Category: III
Diagram Description: Diagram 2 shows the overall wiring diagram for the DALI driver controller, including power input, DALI connections, and auxiliary power. Diagram 3 illustrates the power connection (100-240V) and the DALI bus connections (DA-, DA+, SHLD). Diagram 4 details the RS-485 DyNet/DMX and AUX/UL924 connections, including wire size and torque specifications. It also shows the RJ12 connector for DALI. Diagram 5 shows the terminal blocks for DALI and RS-485 connections, with specifications for wire size and torque.
Note on Radio Interference: This is a class A product. In a domestic environment, this product may cause radio interference, in which case the user may be required to take adequate measures.
System Compliance: Installation of a home and building automation and control system shall comply with IEC 60364 (all parts). The temperature limits and current-carrying capacities for the communication wires specified in IEC 60364-5-52 shall not be exceeded.
Control Channel Ratings
Addressable: Up to 64 devices per channel.
Total Devices: Less than 192 devices.
Current Rating: Guaranteed 128 mA, Maximum 250 mA.
Insulation: Basic.