VIMAR XT 1M KNX Devices
Product Series: 32121.x - 32124.x - 32123.x - 32121.1x
This document provides technical specifications and installation guidelines for the VIMAR XT 1M KNX device series.
Featured Models:
- 32121: XT 1M KNX Device
- 32123: XT 1M KNX Advanced Device
- 32124: XT 1M 4P KNX Advanced Device
- 32144: XT 1M 4P KNX Functions Specifications
Technical Specifications:
- Power Supply: Supplied by the XT actuator (Art. x.32602, x.32603, x.32604, x.32613, x.32614) or its connection node (Art. 32101).
- Maximum Bus Absorption Current:
- 32121: x.32121
- 32123: x.32123
- 32124: x.32124
- 32144: x.32144
- Features: Red LED indicator and configuration/reset button.
- Operating Temperature: 5°C to +45°C (indoor use).
- Unit Size: Occupies 1 front unit of 30.5 mm.
- Stand-by Illumination: Levels are configurable via operating parameters.
- Rear Connection: Connects to the actuator (Art. x.32602, x.32604, x.32613, x.32614).
- Protection Rating: IP20
Device Configurations:
Art. No. | Features |
---|---|
x.32121 | 2 configurable buttons, also as 1 rocker. |
x.32123 | Central matrix of white LEDs for programmable icons or animations. Vertical bar of white LEDs for animations. Two long, lower white LEDs for operational status indication. |
x.32124 | Matrices of long, lower white LEDs for programmable icons, operational status, or animations. 4 loose buttons. 4 white LEDs for the loose buttons to indicate operational status. 4 backlit icons opposite the loose buttons to indicate thermostat operational status. Proximity function. |
x.32144 | 4 loose buttons. 4 white LEDs for the loose buttons to indicate operational status. 4 backlit icons opposite the loose buttons to indicate thermostat operational status. Proximity function. |
Configuration and Setup:
Device settings and operating parameters are configured using the 0TS software. Updated ETS databases can be downloaded from the 'Software' section on www.vimar.com.
Installation Rules:
Installation must be performed by specialized and certified technicians, adhering to local electrical installation regulations and directives.
The device must be installed on VIMAR XT actuators with the following cover sizes:
- 2 units: Art. x.32602
- 3 units: Art. x.32603 and x.32613 (rectangular cover)
- 4 units: Art. x.32604 and x.32614 (rectangular cover)
Installation Recommendations:
- To optimize operation, it is recommended to use only one proximity sensor (S-proximity function) for lighting control, disabling other sensors.
- Avoid installing one or two control units with an active proximity sensor (S-proximity function) facing each other if the distance is less than 4 meters. [Warning: Proximity sensor interference]
- Avoid installing a button with an active proximity sensor (S-proximity function) in front of an infrared receiver to prevent interference.
- When removing or fitting buttons, be careful not to scratch or damage the proximity sensor.
Compliance with Standards:
- Electromagnetic Compatibility Directive
- Restriction of Hazardous Substances Directive
- European Standards: EN IEC 63040, EN 10491-2, EN IEC 63041, EN 10491-2, EN IEC 63040, EN IEC 63044, EN 10491-2, EN IEC 63041-2
- Chemicals Registration, Evaluation, Authorisation and Restriction (UE) REACs Regulation No. 2006/1907 - Article 33. The product may contain traces of lead.
Electrical and Electronic Equipment (WEEE) Compliance:
This symbol ♻️ indicates that the product has reached the end of its life and must be disposed of separately from household waste. Users must deliver the device to an appropriate collection center for electrical and electronic waste. Alternatively, the device can be returned to the retailer when purchasing a new equivalent product. Separate collection of end-of-life equipment contributes to recycling, treatment, and environmentally sound disposal, preventing negative impacts on the environment and human health. Recycling of the materials contained in these devices is encouraged.
Device Views and Installation:
Front and Side Views:
Diagrams show front views of models 32144.x, 32124.x, 32123.x, and 32121.x, highlighting buttons (E1-E4), LEDs (D1-D4), and connection points (A, B, C).
- A: Status indicator LED (white)
- B: Proximity sensor
- C: Reset button
- D: Status indicator LED (white)
- E: Configurable button with white LED
Installation Steps:
- Mount the backplate.
- Attach the device to the backplate.
- Snap on the cover.
Removal Steps:
- Remove the cover.
- Detach the device from the backplate using a tool.
- Remove the backplate.