Domekt R 150 F C8
Equipment with Rotary Heat Exchanger
Technical Specifications
Parameter | Value |
---|---|
Maximum airflow, m³/h | 150 |
Maximum airflow, l/s | 42 |
Reference flow rate, m³/s | 0.029 |
Reference pressure drop, Pa | 50 |
SPI, W/(m³/h) | 0.34 |
Heat recovery thermal efficiency, % | 82 |
Electric air heater power, kW / Δt, °C | 0.5/13.9 |
Supply voltage, V | 1~230 |
Maximum operating current HE, A | 3.2 |
Supply cable, mm² | 3×1.5 |
Fan drive electrical power at maximum flow, W | 41 |
Fan drive electrical power at reference flow, W | 17 |
Sound power level, LWA, dB(A) | 43 ? |
Sound pressure level, LPA, dB(A), (3 m) | 32 |
Filter dimensions B×H×L, mm | 225×172×46 |
Supply filter class | ePM1 60 (F7) |
Exhaust filter class | ePM10 50 (M5) |
Unit dimensions BxHxL, mm | 460×280×780 |
Service area, mm | 780 |
Unit weight, kg | 29 ⚖️ |
Performance Data
The unit features an energy efficiency rating of A.
Key Performance Indicators:
- Sound Power Level: 43 dB ?
- Maximum Airflow: 150 m³/h ?
Performance Curve:
The performance curve graph illustrates the relationship between airflow (Gaisa plūsma, m³/h) on the x-axis and static pressure (Statiskais spiediens, Pa) on the y-axis for a unit with standard equipment. It displays several performance lines labeled SPI 0.3, SPI 0.4, SPI 0.5, and SPI 0.6, indicating different efficiency or operating points.
X-axis: Airflow (m³/h) from 0 to 200.
Y-axis: Static Pressure (Pa) from 0 to 250.
Temperature Efficiency
Parameter | Winter (°C) | Summer (°C) | ||||||
---|---|---|---|---|---|---|---|---|
-23 | -15 | -10 | -5 | 0 | 25 | 30 | 35 | |
Outdoor temperature, °C | -23 | -15 | -10 | -5 | 0 | 25 | 30 | 35 |
Temperature after recuperator, °C | 13.9 | 15.4 | 16.3 | 17.2 | 18.1 | 22.5 | 23.4 | 24.3 |
Note: Exhaust air condition +22°C, 20% RH.
Accessories
- Duct connection: AGUJ-M-160+TF230/CM230
- Silencer: ODA/EHA ASTS-160-600-M, SUP/ETA ASTS-160-900-M
- Water heater: DH-160
- PPU (mixing unit): PPU-HW-3R-15-0.4-W2
- Two-way valve (for water heater): VVP47.10-0.4+SSF161.05HF
- Air intake-exhaust device: LD-160
Dimensions and Connections
The unit has dimensions of 460 mm (Width) × 280 mm (Height) × 780 mm (Length). A service area of 780 mm is required.
Diagram Description:
A diagram shows the main unit with dimensions. Key connection ports are labeled:
- ODA: Outdoor air intake (Green circle) ➡️
- SUP: Supply air supply (Blue circle) ⬆️
- ETA: Exhaust air from room (Yellow circle) ⬇️
- EHA: Extract air (Brown circle) ⬅️
- ETB: Additional extract connection (bypass - extract without heat recovery) (Grey circle with Ø125 indication)
The diagram also indicates dimensions: 125 mm for the ETB connection, 280 mm width, 460 mm height, and 812 mm overall length (including connections). Two smaller diagrams show cross-sections of the air intake/exhaust ports.
Mounting Variants
The unit supports multiple mounting configurations. The diagram shows four options, illustrating different orientations and positions relative to walls and floors, including a "Left-hand version (L1)" designation.
- Option 1: Mounted on a floor with connections on top.
- Option 2: Mounted on a wall with connections on the side.
- Option 3: Mounted on a floor with connections on the side.
- Option 4: Mounted on a wall with connections on the top.
Visual indicators show airflow directions for ODA, SUP, ETA, EHA, and ETB connections.
Disclaimer
Latest data can be checked in the latest version of the selection software. UAB KOMFOVENT reserves the right to make changes to parameters and dimensions in the process of improving ventilation equipment.