Komfovent Domekt R 200 V C8 Air Handling Unit
Technical specifications and performance data for the Komfovent Domekt R 200 V C8 air handling unit.
Product Overview
The Komfovent Domekt R 200 V C8 is an air handling unit designed for efficient ventilation with heat recovery. It features a rotating heat exchanger for optimal performance.
Technical Specifications
ePM1 60 (F7) ePM10 50 (M5)Specification | Value |
Maximum airflow, m³/h | 233 |
Maximum airflow, l/s | 65 |
Reference airflow, l/s | 0,05 |
Reference pressure drop, Pa | 50 |
Specific fan power, W/(m³/h) | 0,29 |
Temperature efficiency for heat recovery, % | 80 |
Electrical post-heater power, kW / At, °C | 0,5/8,1 |
Supply voltage, V | 1~230 |
Maximum operating current, A | 3,9 |
Power supply cable, mm² | 3x1,5 |
Fan power at maximum airflow, W | 63 |
Fan power at reference airflow, W | 23 |
Sound power level, LWA, dB(A) | 38 |
Sound pressure level, LpA, dB(A) (3 m) | 28 |
Filter dimensions B×H×L, mm | 285×125×46 |
Supply air filter | |
Exhaust air filter | |
Unit dimensions B×H×L, mm | 325×607×600 |
Service space, mm | 300 |
Unit weight, kg | 39 |
Performance Data
Standard equipped unit performance.
Temperature Efficiency
Outdoor air temperature, °C | -23 | -15 | -10 | -5 | 0 | 25 | 30 | 35 |
Indoor air temperature, °C | 12,0 | 14,5 | 15,5 | 16,5 | 17,5 | 22,6 | 23,6 | 24,6 |
Indoor air +22 °C, 20% RH |
Connections (R1)
Accessories
Accessory | Model/Part Number |
Shut-off damper | AGUJ-M-125+TF230/CM230 |
Silencer | ODA/EHA ASTS-125-600-M |
SUP/ETA ASTS-125-900-M | |
Heating coil | DH-125 |
Circulation pump unit | PPU-HW-3R-15-0,4-W2 |
2-way valve (heating coil) | VVP47.10-0,4+SSF161.05HF |
Hood | 392-12 |
Adapter | 392-12 |
Hood | Monolit |
Adapter | Monolit |
Air distribution box | OSD-200VE/OSD2-200VE |
Combined hood | LD-125 |
Connections (L1)
Connection key: ODA - outdoor air, SUP - supply air, ETA - exhaust air, EHA - extract air, ETB - additional exhaust air connection (bypass - extraction without heat recovery), ETH - hood connection (bypass - extraction without heat recovery).