ℹ️ Document Conversion Notice:
This document has been converted from PDF and formatted to fit this screen. Diagrams and images may be available only in the original here.
R. STAHL 9176A/20-15-00k Galvanic Isolator
Loop-powered binary output, Ex i field circuit
Product Overview
The R. STAHL 9176A series binary output isolators provide binary signals for the operation of Ex i solenoid valves, indicator lamps, or sirens. These devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsic safety outputs are electrically separated from the inputs. Two-channel variants feature electrical channel separation.
Suitable for solenoid valves and signaling devices
Space-saving two-channel variants
No separate auxiliary power supply required
Technical Characteristics
Explosion Protection
Application (zones)
0, 1, 2, 20, 21, 22
Ex zone interface
IECEx BVS 13.0012 X
IECEx gas explosion protection
Ex nA [ia Ga] IIC T4 Gc
IECEx dust explosion protection
[Ex ia Da] IIIC
ATEX gas explosion protection
BVS 04 ATEX E 075 X; II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX dust explosion protection
BVS 04 ATEX E 075 X; II (1) D [Ex ia Da] IIIC
FM16US0122X
FM16CA0067X
cFM Marking
Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC T4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C (See Doc. 91 76601 31 1)
Certifications
ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), Korea (KTL), USA (FM), IECEx (BVS), SIL (exida)
Marine approval
CCS, EU RO MR (DNV)
Declaration of conformity
ATEX (EUK), China (CCC)
Safety Values
Maximum voltage Uo
27.6 V
Maximum current Io (Ex ia)
86.5 mA
Maximum current Io (Ex ib)
44 mA
Maximum power Po
596 mW
Max. external capacitance Co for IIC
0.085 µF
Max. external inductance Lo for IIC
1.8 mH
Max. external capacitance Co for IIB
0.667 µF
Max. external inductance Lo for IIB
17 mH
Internal capacitance
1.1 nF
Internal inductance
Negligible
Maximum voltage Uo parallel
27.6 V
Maximum power Po parallel
1192 mW
Max. current Io (Ex ia) parallel
173 mA
Max. current Io (Ex ib) parallel
88 mA
Internal capacitance parallel
2.2 nF
Internal inductance parallel
Negligible
Maximum safety technical voltage
253 V
Intrinsic safety limit values inductance L / capacitance Co (2 channels in parallel)
Test voltage according to standard (Ex i to Ex i input)
EN IEC 60079-11; 500 V AC
Test voltage according to standard (Input to input)
EN 50178; 350 V AC
Input
According to EN 61131-2
Input voltage for SWITCH ON
18–31.2 V
Input voltage for SWITCH OFF
0–5 V
Output Characteristics
Output voltage at no load Uv
25 V
Maximum output current Ia
29 mA
Maximum output current Ia (parallel channels)
58 mA
Internal resistance R
320 ohms / parallel: 160 ohms
Output residual ripple
< 100 mV
Output switching frequency
≤ 10 Hz
Switch-on delay / SWITCH OFF
≤ 50 ms
Switch-off delay / SWITCH ON
≤ 18 ms
Switching status indication
Yellow LED "OUT"
Output Characteristic Curve 9176/.0-15-00
The diagram shows output current [mA] on the X-axis and voltage [V] on the Y-axis. Curve A represents the characteristic per channel, and Curve B represents the characteristic for 1 parallel channel 2 (for types 9176/20-...). The operating temperature range is -20 °C to +60 °C.
Ambient Conditions
Ambient temperature (single device)
-20 °C ... 70 °C
Ambient temperature (group assembly)
-20 °C ... 60 °C
Ambient temperature (single device, Fahrenheit)
-4 °F ... +158 °F
Ambient temperature (group assembly, Fahrenheit)
-4 °F ... +140 °F
Note on ambient conditions
Installation conditions affect ambient temperature. Refer to "Installation Instructions - Control Cabinet".
Storage temperature
-40 °C ... 80 °C (-40 °F ... +176 °F)
Maximum relative humidity
95%
Operation at altitude
< 2000 m
Electromagnetic compatibility
Complies with standards and directives: EN 61326-1, industrial sector use; NAMUR NE 21
Mechanical Characteristics
Degree of protection (IP)
IP30
Degree of protection (IP) for plug/socket contacts
IP20
Fire resistance (UL 94)
VO
Enclosure material
Polyamide
Pitch
17.6 mm (0.69 in)
Width
17.6 mm (0.69 in)
Length
128 mm (5.04 in)
Weight
180 g (0.4 lb)
Mounting / Installation
DIN rail NS35/15, NS35/7.5
Mounting position
Horizontal or vertical
Connection type
Spring terminal
Minimum conductor cross-section (solid)
0.2 mm²
Maximum conductor cross-section (solid)
2.5 mm²
Minimum conductor cross-section (flexible)
0.2 mm²
Maximum conductor cross-section (flexible)
2.5 mm²
Conductor cross-section AWG
24 ... 14
Technical Drawings (subject to modification)
Hazardous area vs. Safe area
Diagram shows a simplified block representation of the isolator, separating a 'Field Device' in a hazardous area (Division 1, Zone 0/1) from a 'Control System' in a safe area (Division 2, Zone 2). It indicates 'active' connections for both the field device and the control system, with an 'ISpac Isolator' in between.
Outline Drawing (dimensions in mm [inches])
The outline drawing shows the physical dimensions of the isolator, with a length of 114.5 mm [4.51 in] and a width of 17.6 mm [0.69 in]. It also indicates compatibility with various ISpac series and IBus series modules.
Accessories
Description
Part No.
Transparent cover for ISpac 91xx modules (yellow, transparent) - Precise device marking for SIL applications (packaging unit: 10 pieces)
200914
Spare Parts
Screw terminal
Description
Part No.
3-pole plug, screw connection, M3 thread, 7 mm stripping length, green
112817
3-pole plug, screw connection, M3 thread, 7 mm stripping length, black
112816
3-pole plug, screw connection, M3 thread, 7 mm stripping length, blue
112818
Screw terminal with control tap
Description
Part No.
3-pole plug with control tap, screw connection, M3 thread, 7 mm stripping length, black
113005
3-pole plug with control tap, screw connection, M3 thread, 7 mm stripping length, blue
113004
Spring terminal
Description
Part No.
3-pole plug with control tap, spring terminal, 10 mm stripping length, green
112825
3-pole plug with control tap, spring terminal, 10 mm stripping length, black
112824
3-pole plug with control tap, spring terminal, 10 mm stripping length, blue
ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-20-15-00k-222181-fr-fr-rstahl Adobe PDF Library 17.0
Related Documents
R. STAHL 9176/20-15-00k Isolator Barrier: Technical Specifications and Features Detailed technical data, safety information, and specifications for the R. STAHL 9176/20-15-00k loop-powered binary output isolator barrier for Ex i field circuits. Includes explosion protection, electrical data, ambient conditions, and mechanical data.
R. STAHL 9176A Galvanic Isolator: Ex i Field Circuit Output Technical specifications and features of the R. STAHL 9176A loop-powered binary output galvanic isolator for Ex i field circuits. Details on safety, electrical characteristics, environmental conditions, and mechanical specifications.
R. STAHL 9176A Isolator Barriers: Loop-Powered Binary Output for Ex i Field Circuits Technical specifications and details for the R. STAHL 9176A series isolator barriers, designed for loop-powered binary outputs in Ex i field circuits. Features include intrinsic safety, galvanic separation, and suitability for solenoid valves and signaling devices.
R. STAHL 9176A Galvanic Isolator: Ex i Field Circuit Output Technical specifications and features of the R. STAHL 9176A loop-powered binary output Ex i field circuit isolator, including safety, electrical, and mechanical characteristics.
R. STAHL 9176/20-16-00k Galvanic Isolator: Technical Specifications and Features Detailed technical specifications, safety features, and electrical characteristics of the R. STAHL 9176/20-16-00k loop-powered binary output Ex i field circuit galvanic isolator. Includes ATEX and IECEx certifications, environmental conditions, and mechanical data.
R. STAHL 9176A Galvanic Isolator: Ex i Field Circuit Output Technical specifications and features of the R. STAHL 9176A galvanic isolator, a binary output for Ex i field circuits. Details include safety values, electrical characteristics, environmental conditions, and mechanical specifications.
R. STAHL 9176/20-15-00s Isolator Barrier: Technical Specifications Detailed technical specifications for the R. STAHL 9176/20-15-00s loop-powered binary output isolator barrier for Ex i field circuits, including explosion protection, safety data, electrical data, ambient conditions, and mechanical data.