Electrical Connection
The diagram illustrates the sensor's terminal block, which is a green screw terminal with 8 pins. The pins are numbered 1 to 8 from left to right, corresponding to the functions listed in the table below.
Pin number | Function |
---|---|
1 | V+ supply voltage (24 VAC ±15%, 15 - 35 V DC class III ⎓ (Europe); Max. 30 V DC class 2 (North America)) |
2 | GND |
3 | RS485 A (D+) |
4 | RS485 B (D-) |
5 | V+ supply voltage |
6 | GND |
7 | RS485 A (D+) |
8 | RS485 B (D-) |
Address Setting
DIP switch (Configuration Software)
The DIP switch for configuration software settings is shown below. All switches are in the '0' (off) position for software configuration.
ON ┌─┐┌─┐┌─┐┌─┐┌─┐┌─┐┌─┐┌─┐DIP 10 └─┘└─┘└─┘└─┘└─┘└─┘└─┘└─┘ 1 2 3 4 5 6 7 8 00000000
Address setting via PCS10 Product Configuration Software: If all DIP switches are at position 0, the address must be set via configuration software (factory setting: 45). Example: Address is set via configuration software.
DIP switch (Modbus Address)
The DIP switch for Modbus address settings is shown below. Switches 1, 2, 4, and 8 are in the '1' (on) position, representing a binary value of 00001011.
ON ┌─┐┌─┐┌─┐┌─┐┌─┐┌─┐┌─┐┌─┐DIP 10 └─┘└─┘└─┘└─┘└─┘└─┘└─┘└─┘ 1 2 3 4 5 6 7 8 11010000
Modbus address setting via DIP switch: Setting the DIP switch to any address other than 0 overwrites the address selected via configuration software. Example: Address set to 11 (=00001011 binary).
BACnet Setup
BACnet PICS (Product Implementation Conformance Statement) are available for download at the according product website.
Parameter | Factory settings | User selectable values (via PCS10) |
---|---|---|
Baud rate | acc. to ordering code | 9600, 19200, 38400, 57600, 76800, 115200 |
Data bits | 8 | 8 |
Parity | None | None |
Stop bits | 1 | 1 |
BACnet address | 45 | 0...127 |
The PICS (Product Implementation Conformance Statement) is available for download at the according product website. The recommended settings for multiple devices in a BACnet MS/TP network are 38400, 8, none, 1. The communication parameters can be set via:
- PCS10 Product Configuration Software and the appropriate configuration cable HA011018.
- The PCS10 can be downloaded free of charge from www.epluse.com/pcs10.
- BACnet protocol, see the PICS.
Modbus Setup
Parameter | Factory settings | User selectable values (via PCS10) |
---|---|---|
Baud rate | acc. to ordering code | 9600, 19200, 38400, 57600, 76800, 115200 |
Data bits | 8 | 8 |
Parity | Even | None, odd, even |
Stop bits | 1 | 1, 2 |
Modbus address | 45 | 1...247 |
Modbus Protocol
The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, Even, 1. The room sensor represents 1 unit load in a Modbus network.
Device address, baud rate, parity and stop bits can be set via:
- PCS10 Product Configuration Software and the appropriate configuration cable HA011018.
- The PCS10 can be downloaded free of charge from www.epluse.com/pcs10.
- Modbus protocol in the register 1 (0x00) and 2 (0x01). See Application Note Modbus AN0103 (available at the according product website).
The serial number in ASCII format is located in read-only register 1 - 8 (16 bits per register). The firmware version is located in register 9 (bit 15...8 = major release; bit 7...0 = minor release). The sensor name is located in registers 10 - 17 (16 bits per register).
Communication settings (INT16)
Parameter | Register number1) [Dec] | Register address2) [Hex] |
---|---|---|
Write register: function code 0x06 | ||
Modbus address | 1 | 0x00 |
Modbus protocol settings3) | 2 | 0x01 |
1) Register number starts from 1.
2) Protocol address starts from 0.
3) For Modbus protocol settings see Application Note Modbus AN0103 (available at the according product website).
Device information (INT16)
Parameter | Register number1) [Dec] | Register address2) [Hex] |
---|---|---|
Read register: function code 0x03 / 0x04 | ||
Serial number (as ASCII) | 1 | 0x00 |
Firmware version | 9 | 0x08 |
Sensor name | 10 | 0x09 |
Device status (bit decoded) | 602 | 0x259 |
1) Register number starts from 1.
2) Protocol address starts from 0.
Modbus Register Map
Parameter | Unit | FLOAT32 | INT16 | Scale | |||||
---|---|---|---|---|---|---|---|---|---|
Register1) | Address2) | Register1) | Address2) | CDS201 | HTS201 | TES201 | |||
Read register: function code 0x03 / 0x04 | |||||||||
Temperature | °C | 1003 | 0x3EA | 4002 | 0xFA1 | 100 | ☑ | ☑ | ☑ |
°F | 1005 | 0x3EC | 4003 | 0xFA2 | 50 | ☑ | ☑ | ☑ | |
°K | 1009 | 0x3F0 | 4005 | 0xFA4 | 50 | ☑ | ☑ | ☑ | |
Relative humidity RH, Uw | %RH | 1021 | 0x3FC | 4011 | 0xFAA | 100 | ☑ | ☑ | |
CO2 averaged | ppm | 1061 | 0x424 | 4031 | 0xFBE | 1 | ☑ | ||
CO2 non-averaged | ppm | 1063 | 0x426 | 4032 | 0xFBF | 1 | ☑ | ||
Dew point temperature Td | °C | 1105 | 0x450 | 4053 | 0xFD4 | 100 | ☑ | ☑ | |
°F | 1107 | 0x452 | 4054 | 0xFD5 | 100 | ☑ | ☑ | ||
°K | 1147 | 0x47A | 4074 | 0xFE9 | 100 | ☑ | ☑ |
1) Register number starts from 1 and is expressed as decimal number.
2) Protocol address starts from 0 and is expressed as hexadecimal number.
It is possible to map measured value/status registers arbitrarily in a block with up to 20 registers provided for this purpose (registers 3001...3020). Please find detailed information in the manual at the according product website.