EE660 - Low Air Velocity Sensor with RS485 Interface
Quick Guide
[E+E Elektronik Logo: Your partner in sensor technology]
Introduction
ℹ️ PLEASE NOTE
Find this document and further product information on our website at www.epluse.com/ee660.
Electrical Connection
⚠️ WARNING
Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property. For correct cabling of the device, always observe the presented wiring diagram for the product version used. The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.
Hardware
? NOTICE
Improper handling of the device may result in its damage.
The bus termination shall be realized with 120 Ω resistor using the switch on the electronics board.
The power supply must be strong enough to ensure supply voltage within the specified range (see technical data) at any time and at all devices in the bus. This is particularly relevant when using long and thin cables as those can cause high voltage drop. Please note that a single EE660 requires peak current of 150 mA.
Wiring
Digital Interface
The digital interface wiring diagram shows connections for power supply and the RS485 interface. Pin 1 is for V+ (Power Supply), Pin 2 for GND (Ground). Pins 3 and 4 are for the RS485 communication: Pin 3 is A (=D+) and Pin 4 is B (=D-). The diagram also indicates connections for a remote probe.
Power supply: 24 V AC/DC ±20%
Address Switch
The address switch section illustrates two DIP switches, S1 and S2. S1 controls the response time: 'ON' selects a slow response time, while 'OFF' selects a fast response time. S2 is for the termination resistor, with 'ON' enabling the 120 Ω termination resistor and 'OFF' disabling it.
Address Setting
Address Setting via PCS10 Product Configuration Software
All DIP switches at position 0 → address has to be set via PCS10.
Modbus (slave device): factory setting 65 (permitted values: 1...247).
BACnet (master device): factory setting 65 (permitted values: 0...127).
Example: Address is set via configuration software = factory setting.
Address Setting via DIP Switch
Modbus (slave device): Setting the DIP switches to any other address than 0, overrules the Modbus address set via PCS10 (permitted values: 1...247).
BACnet (master device): Setting the DIP switches to any other address than 0, overrules the BACnet address set via configuration software.
BACnet Note: permitted values are 0...127. The 8th bit of the DIP switches is ignored. To set address 0 via DIP switches, the 8th bit shall be set to 1 (ID 0 = 1000 0000). Example: Address set to 11 (= 0000 1011 binary).
BACnet Setup
Please refer to PICS (Product Implementation Conformance Statement), available on www.epluse.com/ee660.
Modbus Setup
FLOAT32 Parameters
Parameter | Unit1) | Register number2) [DEC] | Register address3) [HEX] |
Temperature | °C | 1003 | 3EA |
Temperature | °F | 1005 | 3EC |
Air velocity | m/s | 1041 | 410 |
Air velocity | ft/min | 1043 | 412 |
1) The choice of measurement units (metric or non-metric) must be done according to the ordering guide, refer to EE660 datasheet. Switching from metric to non-metric or vice versa by using the PCS10 is not possible.
2) Register number (decimal) starts from 1.
3) Register address (hexadecimal) starts from 0.
INT16 Parameters
Parameter | Unit1) | Scale4) | Register number2) [DEC] | Register address3) [HEX] |
Temperature | °C | 100 | 4002 | FA1 |
Temperature | °F | 50 | 4003 | FA2 |
Air velocity | m/s | 100 | 4021 | FB4 |
Air velocity | ft/min | 1 | 4022 | FB5 |
4) Examples: For scale 100, the reading of 2550 means a value of 25.5. For scale 50, the reading of 2550 means a value of 51.
Communication Settings (INT16)
Parameter | Register number1) [Dec] | Register address2) [Hex] | Size3) |
Write register: function code 0x06 Modbus address4)5) | 1 | 00 | 1 |
Modbus protocol settings4) | 2 | 01 | 1 |
1) Register number starts from 1.
2) Protocol address starts from 0.
3) Number of registers.
4) For Modbus address and protocol settings refer to Application Note Modbus AN0103 (available at www.epluse.com/ee660).
5) If the ID is set via DIP-Switch the response will be NAK.
Device Information (INT16)
Parameter | Register number1) [Dec] | Register address2) [Hex] | Size3) |
Read register: function code 0x03 / 0x04 Serial number (as ASCII) | 1 | 00 | 8 |
Firmware version | 9 | 08 | 1 |
Sensor name (as ASCII) | 10 | 09 | 8 |
EE660 - Low Air Velocity Sensor with Analogue Output
Wiring
Voltage output 0-10 V
The wiring diagram for voltage output 0-10 V shows power supply connections and remote probe connections. Power supply is 24 V AC/DC ±20%. Remote probe connections are: b (brown) for V+, g (green) for GND, y (yellow) for AV_U, and w (white) for AV_I. The device connections are: Pin 1: V+ = power supply, Pin 2: GND = ground, Pin 3: AV_U = voltage output, Pin 4: AV_I = current output.
Current output 4-20 mA
The wiring diagram for current output 4-20 mA shows power supply connections. Power supply is 24 V AC/DC ±20%. The device connections are: Pin 1: V+ = power supply, Pin 2: GND = ground, Pin 3: AV_U = voltage output, Pin 4: AV_I = current output.
Jumper Settings
For performing the EE660 settings via the PCS10 Product Configuration Software (free download from www.epluse.com/pcs10) the jumper for the measuring range must be set to HI.
Selection of response time t90
The diagram shows jumper positions labeled HI, MED, and LO for the t90 setting. The text specifies that the factory setting is a slow response time of 4 seconds, and a fast response time of 1 second is achieved with no jumper.
Selection of the measuring range
The diagram shows jumper positions labeled HI, MED, and LO for selecting the measuring range. 'Jumper HI' sets the range to 0...2 m/s (0...400 ft/min). 'Jumper MED' sets the range to 0...1.5 m/s (0...300 ft/min). With 'no jumper', the range is set to 0...1 m/s (0...200 ft/min).