Quick Guide EE850
CO2, Humidity and Temperature Duct Sensor
Please Note
Find this document and further product information on our website at www.epluse.com/ee850.
Electrical Connection
[Warning] Incorrect installation, wiring or power supply may cause overheating and result in personal injury or property damage. Cables must not be under voltage during electrical installation and connection or disconnection, especially at terminal connections on circuit boards. For correct cabling, always observe the presented wiring diagram for the product version used. The manufacturer cannot be held responsible for personal injury or damage to property caused by incorrect handling, installation, wiring, power supply or maintenance of the device.
Hardware
The bus termination shall be realized with a 120 Ω resistor (slide switch on the board).
NOTICE: For proper function, the power supply must be strong enough to ensure supply voltage within the specified range (see technical data) at any time and at all devices in the bus. This is particularly relevant when using long and thin cables which can cause high voltage drop. Please note that a single digital EE850 requires peak current of 150 mA.
Wiring
Digital Interface
Power Supply: 24 V AC/DC ±20% / 15-35 V DC
Supply and RS485 Interface Connections:
- Pin 1: V+
- Pin 2: GND
- Pin 3: RS485 A (=D+)
- Pin 4: RS485 B (=D-)
A 120 Ohm termination resistor is available via a slide switch (ON/OFF) on the board.
Address Setting
Address Switch
The EE850 uses an 8-position DIP switch for address configuration.
Example DIP switch settings:
- All switches OFF (00000000)
- Example setting: 11010000
Options
Address setting via PCS10 Product Configuration Software (= factory setting)
- All DIP switches at position 0: Address must be set via PCS10.
- Modbus (slave device): Factory setting is 67 (permitted values: 1...247).
- BACnet (master device): Factory setting is 67 (permitted values: 0...127).
Address setting via DIP switches
- Modbus (slave device): Setting DIP switches to any address other than 0 overrides the Modbus address set via PCS10 (permitted values: 1...247).
- BACnet (master device): Setting DIP switches to any address other than 0 overrides the BACnet address set via configuration software.
- BACnet Note: Permitted values are 0...127. The 8th bit of the DIP switches is ignored (ID 127 = 0111 111BIN). To set address 0 via DIP switches, the 8th bit shall be set to 1 (ID 0 = 1000 0000BIN). Example: Address set to 11 DEC (00001011BIN).
BACnet Setup
The EE850 PICS (Product Implementation Conformance Statement) is available on the E+E website at www.epluse.com/ee850.
EE850 BACnet factory settings: Address 67 (0x43), Baud rate as ordered via order code, 8 data bits, parity none, 1 stop bit.
Modbus Setup
The measured values are saved as a 32-bit float value and a 16-bit signed integer.
EE850 Modbus factory settings: Address 67 (0x43), Baud rate as ordered via order code, 8 data bits, parity even, 1 stop bit.
This Modbus address can be changed by the user in register 1 (0x00) with function code 0x06. Permitted values are 1...247.
The serial number as ASCII-code is located at read register addresses 1-8 (0x00 - 0x07) and function code 0x03 or 0x04.
The firmware version is located at register address 9 (0x08) and function code 0x03 or 0x04 (bit 15...8 = major release; bit 7...0 = minor release).
Data Registers
FLOAT32 Parameters
Parameter | Unit | Register number1) [DEC] | Register address2) [HEX] |
---|---|---|---|
Read register: function code 0x03/0x04 | |||
Temperature | °C | 1003 | 3EA |
°F | 1005 | 3EC | |
Relative humidity | % | 1021 | 3FC |
CO2 (average) | ppm | 1061 | 424 |
CO2 (raw) | ppm | 1063 | 426 |
Water vapour partial pressure | mbar | 1101 | 44C |
psi | 1103 | 44E | |
Dew point temperature | °C | 1105 | 450 |
°F | 1107 | 452 | |
Absolute humidity | g/m3 | 1113 | 458 |
gr/ft3 | 1115 | 45A | |
Mixing ratio | g/kg | 1121 | 460 |
gr/lb | 1123 | 462 | |
Specific enthalpy | kJ/kg | 1125 | 464 |
ft lb/lb | 1127 | 466 | |
BTU/lb | 1129 | 468 | |
Frost point temperature | °C | 1131 | 46A |
°F | 1133 | 46C |
INT16 Parameters
Parameter | Unit | Scale3) | Register number1) [DEC] | Register address2) [HEX] |
---|---|---|---|---|
Read register: function code 0x03/0x04 | ||||
Temperature | °C | 100 | 100 | 4002 (FA1) |
°F | 50 | 50 | 4003 (FA2) | |
Relative humidity | % | 100 | 1021 | 4011 (FAA) |
CO2 (average) | ppm | 1 | 1061 | 4031 (FBE) |
CO2 (raw) | ppm | 1 | 1063 | 4032 (FBF) |
Water vapour partial pressure | mbar | 10 | 1101 | 4051 (FD2) |
psi | 1000 | 1103 | 4052 (FD3) | |
Dew point temperature | °C | 100 | 1105 | 4053 (FD4) |
°F | 100 | 1107 | 4054 (FD5) | |
Absolute humidity | g/m3 | 10 | 1113 | 4057 (FD8) |
gr/ft3 | 10 | 1115 | 4058 (FD9) | |
Mixing ratio | g/kg | 10 | 1121 | 4061 (FDC) |
gr/lb | 10 | 1123 | 4062 (FDD) | |
Specific enthalpy | kJ/kg | 1 | 1125 | 4063 (FDE) |
ft lb/lb | 1 | 1127 | 4064 (FDF) | |
BTU/lb | 1 | 1129 | 4065 (FE0) | |
Frost point temperature | °C | 100 | 1131 | 4066 (FE1) |
°F | 100 | 1133 | 4067 (FE2) |
1) Register number (decimal) starts from 1.
2) Register address (hexadecimal) starts from 0.
3) Examples for factory scaling of stored value:
- 100 is the scale 1:100 (e.g., 2550 is equivalent to 25.5 °C)
- 50 is the scale 1:50 (e.g., 2550 is equivalent to 51 °F)
- 10 is the scale 1:10 (e.g., 135 is equivalent to 13.5 mbar)
- 1 is the scale 1:1 (e.g., 800 is equivalent to 800 ppm)
Communication settings (INT16)
Parameter | Register number1) [DEC] | Register address2) [HEX] |
---|---|---|
Write register: function code 0x06 | ||
Modbus address3)4) | 1 | 00 |
Modbus protocol settings4) | 2 | 01 |
Parameter | Register number1) [DEC] | Register address2) [HEX] |
---|---|---|
Read register: function code 0x03/0x04 | ||
Serial number (as ASCII) | 1 | 00 |
Firmware version | 9 | 08 |
Sensor name (as ASCII) | 10 | 09 |
1) Register number (decimal) starts from 1.
2) Register address (hexadecimal) starts from 0.
3) If the Modbus address is set via DIP switch, the response will be NAK.
4) For Modbus address and protocol settings, see Application Note Modbus AN0103 (available at www.epluse.com/ee850).
Modbus RTU Example
Request [Hex]:
Modbus address | Function code | Starting address Hi | Starting address Lo | Qty. of registers Hi | Qty. of registers Lo | CRC |
---|---|---|---|---|---|---|
43 | 03 | 04 | 24 | 00 | 02 | 8A 12 |
Response [Hex]:
Modbus address | Function code | Byte count | Register 1 value Hi | Register 1 value Lo | Register 2 value Hi | Register 2 value Lo | CRC |
---|---|---|---|---|---|---|---|
43 | 03 | 04 | 0B | 00 | 44 | A1 | 68 AB |
Modbus response [Hex]
Data representation according to IEEE754
Byte 1 | Byte 2 | Byte 3 | Byte 4 | |
---|---|---|---|---|
Register 1 (Hi) | 0B | 0000 1011 | ||
Register 1 (Lo) | 00 | 0000 0000 | ||
Register 2 (Hi) | 44 | 0100 0100 | ||
Register 2 (Lo) | A1 | 1010 0001 |
Decimal value: 1288.34375
E+E Elektronik
E+E Elektronik Ges.m.b.H.
Langwiesen 7
4209 Engerwitzdorf | Austria
T +43 7235 605-0
F +43 7235 605-8
info@epluse.com
www.epluse.com
[CE Mark] [UKCA Mark] [Canada Mark]
QG_EE850 | Version v1.4 | 08-2025 | All rights reserved | 194791