Resideo Braukmann FF06-ZAR miniplus

Rinsable fine filter with 5 µm mesh size

Installation Instructions

Diagram: Fine Filter

Illustration of the Resideo Braukmann FF06-ZAR fine filter. It features a T-shaped body with inlet and outlet connections (DN25 PN16). A transparent cylindrical bowl is attached to the bottom of the T-body, containing the filter mesh (95/110µm). A drain valve is located at the very bottom of the bowl. The filter is labeled "Fine Filter" and shows specifications like V=11.1m³/h, Tmax. 40°C. It also has a DVGW certification mark.

1. Installation

During installation, codes of good practice, local requirements, and the installation instructions must be followed. The installation location must be freeze-protected and well accessible. Shut-off valves should be fitted before and after the fine filter.

1.1 Assembly

  1. Flush pipework thoroughly.
  2. Install fine filter:
    • Ensure correct flow direction as indicated by arrow [→].
    • Install in horizontal pipework with filter bowl downwards.
    • Install free of bending or twisting stress.
  3. Fine filter is ready to use.

Note: Where solder connections are used, the fine filter may not be in contact with the solder connections during soldering.

1.2 Rinsing water drainage

Installation options:

  1. At 20 mm distance from drain funnel (see Diagram 1.2).
  2. Drain into open container.

Diagram 1.1: Shows pipework being flushed, with water flowing from the pipe into an open container (e.g., a bucket).

Diagram 1.2: Illustrates the rinsing water drainage setup. The filter bowl is shown positioned above a drain funnel, with a measurement of 20 mm indicated between the filter's drain outlet and the funnel's opening.

2. Rinsing

Rinsing is carried out to discharge dirt particles that might have collected at the bottom of the filter bowl. Rinsing intervals depend on the degree of water contamination.

Note: Filtered water can still be drawn during the rinsing cycle.

2.1 Rinsing

If rinsing water is not being drained into a drain funnel, a suitable container must be placed underneath.

  1. Open ball valve by turning handle 7.
  2. Close ball valve after approximately 15 seconds.

Filter sieves are made of stainless steel. Rust deposit from pipes has no effect on filter functions and operation.

3. Maintenance

Frequency of filter insert change depends on local conditions and water quality.

For hygienic reasons, however, inspection should be carried out at least every six months.

3.1 Inspection

Diagram 3.1: Details the maintenance process. It shows the filter unit, the wrench (8) for unscrewing the bowl, removal of the filter insert, seal ring (3), and filter mesh (4) from carrier (5). It also illustrates applying a new mesh and reassembly steps.

4. Scope of Application

Medium: Water up to max. 40 °C

Operating pressure: max. 16 bar

For cleaning plastic parts, do not use any cleaning materials containing solvents.

Filters may not be installed in locations where ultra violet rays (sunlight) or solvent fumes are present.

5. Safety Guidelines

  1. Use the appliance:
    • In good condition.
    • According to regulations.
    • With due regard to safety.
  2. Follow installation instructions.
  3. Immediately rectify any malfunctions which may influence safety.
  4. FF 06 fine filters are exclusively for use in applications detailed in these installation instructions. Any variation from this or other use will not comply with requirements.

Note: Do not use where water is microbiologically unsafe or with water of unknown quality without adequate disinfection before or after the filter.

6. Spare Parts

7. Accessories

PDF preview unavailable. Download the PDF instead.

ff06-zar-ii-en1h1137ge23 Acrobat Distiller 7.0.5 (Windows)

Related Documents

Preview Braukmann MiniPlus FF06BRU/FF06-AAMBRU Installation and Maintenance Guide
Official installation, operation, and maintenance instructions for the Resideo Braukmann MiniPlus FF06 series fine water filters (FF06BRU, FF06-AAMBRU). Learn about safety, technical data, assembly, cleaning, and troubleshooting.
Preview Resideo Braukmann F78TS: High-Demand Reverse Rinsing Water Filter
Explore the Resideo Braukmann F78TS, a premium reverse rinsing fine filter for high water demand applications. Features include automatic rinsing, robust construction, and key approvals like DVGW and WRAS. Ideal for residential, commercial, and industrial use.
Preview Resideo Braukmann F76S Fine Water Filter: Installation and Maintenance Manual
Comprehensive installation, maintenance, and troubleshooting guide for the Resideo Braukmann F76S fine water filter. Covers safety guidelines, technical specifications, assembly, commissioning, reverse rinsing procedures, maintenance, troubleshooting, and disposal. Designed for drinking water installations.
Preview Resideo Braukmann F74CS/FN74CS/FK74CS/FKN74CS-LF Installation and Maintenance Manual
This document provides comprehensive installation, operation, and maintenance instructions for the Resideo Braukmann F74CS/FN74CS/FK74CS/FKN74CS-LF series of filters and filter combinations. It covers safety guidelines, technical data, assembly, startup, maintenance, troubleshooting, spare parts, and disposal.
Preview Braukmann F76S Water Filters & MV876B Automatic-Backwash Controls: Installation & Specifications
Comprehensive guide to Braukmann F76S water filters and MV876B automatic-backwash controls, covering installation, features, specifications, and replacement parts from Resideo.
Preview Braukmann HS10S-LF Lead-Free Water Filter and Pressure Reducing Station with Backwash
Comprehensive technical details, specifications, and installation guidance for the Braukmann HS10S-LF, a lead-free water filter and pressure reducing station featuring backwash technology for potable water systems.
Preview Resideo Braukmann MV300 Installation Instructions
Installation guide for the Resideo Braukmann MV300 solenoid valve, detailing components, installation steps, and operating conditions.
Preview Braukmann FK06 DialSet Pressure Regulating Filter Combination Installation Guide
This guide provides essential installation, operation, and maintenance instructions for the Resideo Braukmann FK06 DialSet pressure regulating filter combination, ensuring optimal performance and safety in water systems.