Resideo Braukmann F76S Water Filter Installation and Maintenance Manual

Resideo Braukmann F76S Water Filter

Installation and Maintenance Manual

1 Safety Guidelines

Follow the installation instructions.

Use the appliance:

  • According to its intended use
  • In good condition
  • With due regard to safety and risk of danger.

Note that the appliance is exclusively for use in the applications detailed in these installation instructions (see 2 Technical Data). Any other use will not be considered to comply with requirements and would invalidate the warranty.

Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.

Immediately rectify any malfunctions which may influence safety.

2 Technical Data

Medium Drinking water
Connections/Sizes 1/2" - 2"
Pressure values Max. operating pressure with clear filter bowl: 1.5 - 16 bar
Max. operating pressure with red bronze filter bowl: 1.5 - 25 bar
Operating temperatures Operating temperature range medium acc. to EN 1567: 5 °C - 30 °C
Max. operating temperature medium (clear filter bowl): 40 °C
Max. operating temperature medium (red bronze filter bowl): 70 °C
Specifications Installation position: Horizontal, with filter bowl downwards

The filter is constructed for drinking water installations. In case of a process water application the filter has to be proven individually.

3 Options

For options visit homecomfort.resideo.com/europe.

4 Assembly

4.1 Installation Guidelines

  • Install in horizontal pipework with filter bowl downwards. This position ensures optimum filter efficiency.
  • Install shut-off valves. These filters are armatures which need to be maintained regularly.
  • Ensure good access: Pressure gauge can be read off easily. Degree of contamination can be easily seen with clear filter bowl. Simplifies maintenance and inspection.
  • The installation location should be protected against frost.
  • Related to EN 806-2, it is recommended to install the filter immediately after the water meter.
  • To avoid flooding, it is recommended to arrange a permanent, professionally dimensioned wastewater connection.

4.2 Assembly instructions

CAUTION! When connecting the solder sockets, do not solder the sockets together with the filter. High temperatures destroy internal parts which are important to the function!

  1. Thoroughly flush pipework.
  2. Install filter: Note flow direction. Install without tension or bending stresses.
  3. Seal in pressure gauges.

4.3 Discharge of reverse rinsing water

The reverse rinsing water must be routed to the drain channel in such a way that no backwater can occur. To do this there are 3 options:

  1. Direct connection: Connector DN50/70 as well as the necessary pipes and siphon (3 elbows 90°) in DN70.
  2. Discharge into floor drain.
  3. Drain into open container.
Filter size Reverse rinsing volume*
1/2" and 3/4" 12 Liter
1" and 1 1/4" 15 Liter
1 1/2" and 2" 18 Liter

*at 4 bar inlet pressure and 3 x 3 seconds reverse rinsing duration.

5 Commissioning

5.1 Reverse rinsing

During reverse rinsing, an inlet (dynamic) pressure of at least 1.5 bar is required. The reverse rinsing interval depends on the degree of dirt in the water. At the latest every 6 months, reverse rinsing should be carried out according to EN 806-5. Our recommendation at least every 2 months! To ensure convenient and regular adherence to the reverse rinsing interval, we recommend installing an automated reverse rinsing system Z11S.

Filtered water can also be tapped during reverse rinsing.

5.2 Manual reverse rinsing

If reverse rinsing water is not to be discharged via a direct connection, a collecting container must be positioned beneath before reverse rinsing.

  1. Open ball valve by turning the reverse rinsing button to the stop point:
    • Select bar must be upright.
    • The patented reverse rinsing system starts.
    • When filtering with Double Spin Technology, a visual function check is possible through the rotating red rotor.
  2. Close ball valve again after approx. 3 seconds. Repeat procedure three times.

If the filter is extremely dirty, the procedure may have to be repeated additional times.

With aid of the memory ring, the next deadline for manual reverse rinsing can be booked.

5.3 Automatic reverse rinsing with the Z11S

The automated reverse rinsing system Z11S is available as an accessory. The automated system reliably takes over reverse rinsing of the filter at intervals which can be set between 4 minutes and 3 months.

6 Maintenance

In order to comply with EN 806-5, water fixtures must be inspected and serviced on an annual basis.

As all maintenance work must be carried out by an installation company, it is recommended that a servicing contract should be taken out.

In accordance with EN 806-5, the following measures must be taken:

6.1 Inspection

  • The filter must be cleaned by reverse rinsing regularly, at least every 6 months (acc. to EN 806-5). Our recommendation at least every 2 months!
  • Non-compliance can lead to the filter becoming blocked. This results in a drop in pressure and decreased water flow.
  • The filter meshes are made of stainless steel. A red coating as a consequence of rust from the pipelines has no influence on function or the way the filter works.

CAUTION! Do not forget to do a visual check of the ball valve. Replace if it is dripping!

6.2 Maintenance

If necessary, the outside surface of the filter can be cleaned. Use only cold, clear drinking water to clean the surfaces! Any other cleansers cause damage to the plastic components!

  1. Close shut-off valve on inlet.
  2. Release pressure on outlet side (e.g. through water tap).
  3. Close shut-off valve on outlet.
  4. Unscrew filter bowl.
  5. Use double ring wrench ZR10K.
  6. Remove old filter insert and replace by a new one!
  7. Place O-ring onto filter bowl.
  8. Screw in filter cup hand-tight (up to max. 18Nm).
  9. Slowly open shut-off valve on inlet.
  10. Slowly open shut-off valve on outlet.

7 Disposal

Observe the local requirements regarding correct waste recycling/disposal!

8 Troubleshooting

Problem Cause Remedy
Too little or no water pressure Shut-off valves upstream or downstream from filter not fully open Open the shut-off valves fully
Filter mesh dirty Reverse rinsing

9 Spare Parts

For Spare Parts visit homecomfort.resideo.com/europe.

10 Accessories

For Accessories visit homecomfort.resideo.com/europe.

Models: Braukmann F76S

File Info : application/pdf, 28 Pages, 899.17KB

PDF preview unavailable. Download the PDF instead.

f76s-ii-mu1h1110ge23r0620

References

Acrobat Distiller 20.0 (Windows) FrameMaker 12.0

Related Documents

Preview Braukmann F76S Water Filters & MV876B Automatic-Backwash Controls: Installation & Specifications
Comprehensive guide to Braukmann F76S water filters and MV876B automatic-backwash controls, covering installation, features, specifications, and replacement parts from Resideo.
Preview Resideo Braukmann F78TS: High-Demand Reverse Rinsing Water Filter
Explore the Resideo Braukmann F78TS, a premium reverse rinsing fine filter for high water demand applications. Features include automatic rinsing, robust construction, and key approvals like DVGW and WRAS. Ideal for residential, commercial, and industrial use.
Preview Braukmann MiniPlus FF06BRU/FF06-AAMBRU Installation and Maintenance Guide
Official installation, operation, and maintenance instructions for the Resideo Braukmann MiniPlus FF06 series fine water filters (FF06BRU, FF06-AAMBRU). Learn about safety, technical data, assembly, cleaning, and troubleshooting.
Preview Resideo Braukmann FF06-ZAR miniplus Fine Water Filter Installation Guide
Comprehensive installation, rinsing, and maintenance instructions for the Resideo Braukmann FF06-ZAR miniplus fine water filter. Includes safety guidelines, spare parts, and accessories information.
Preview Resideo Braukmann F74CS/FN74CS/FK74CS/FKN74CS-LF Installation and Maintenance Manual
This document provides comprehensive installation, operation, and maintenance instructions for the Resideo Braukmann F74CS/FN74CS/FK74CS/FKN74CS-LF series of filters and filter combinations. It covers safety guidelines, technical data, assembly, startup, maintenance, troubleshooting, spare parts, and disposal.
Preview Braukmann NK300S Refilling Combination - Installation and Maintenance Guide
Comprehensive installation, maintenance, and troubleshooting guide for the Resideo Braukmann NK300S refilling combination unit. Covers safety, technical data, assembly, startup, maintenance procedures, and problem-solving.
Preview Resideo Braukmann NK300SE-VE Installation Instructions
This document provides installation instructions for the Resideo Braukmann NK300SE-VE refilling combination with softening cartridge. It includes safety guidelines, technical data, assembly instructions, start-up procedures, maintenance, disposal, troubleshooting, spare parts, and accessories information.
Preview Braukmann HS10S-LF Lead-Free Water Filter and Pressure Reducing Station with Backwash
Comprehensive technical details, specifications, and installation guidance for the Braukmann HS10S-LF, a lead-free water filter and pressure reducing station featuring backwash technology for potable water systems.