Raychem Mineral Insulated (MI) Series Heating Systems

Installation, Maintenance and Operation Manual

1. General Information

This manual applies to Raychem Mineral Insulated (MI) series resistance heating cable systems installed on thermally insulated pipes and vessels and associated equipment. It provides general information and an overview of common installations and applications. In cases of conflict, project-specific information takes precedence.

Chemelex offers two types of electrical heat-tracing cables: single conductor cables (typically laid in loop configurations) and dual conductor cables (typically laid in single runs).

Figure 1: Typical Cable Construction

A diagram illustrating the construction of single-conductor and dual-conductor MI heating cables, showing the heating conductor(s), insulation (magnesium oxide), and metal sheath.

Types of MI Bulk Heating Cables:

Figure 2: Typical Heating Unit Designs

Diagrams showing Design type B (Single conductor) and Design type D (Dual conductor) heating units, illustrating the hot/cold joint, cold lead cable, gland, potted seal, and flexible tail length.

Joints can be brazed or laser welded. Refer to Raychem product literature for details.

Note: This manual covers the installation of pre-fabricated MI heating units. Termination and repair of heating cable units are not covered and require qualified personnel. Keep cable ends and kit components dry during installation.

Important: To maintain Chemelex warranty, follow manual instructions. Design, installation, inspection, operation, and maintenance must comply with IEC EN 60079-0, IEC EN 60079-30-1, IEC EN 60079-31, and local electrical codes. Personnel must be trained in special techniques and general electrical work. Supervisors should be experienced in heat-tracing applications. Caution signs or markings should indicate the presence of heating cables.

2. Area Classification

Details are provided for Ordinary Area Classification and Hazardous Area Classification (Zone 1 or Zone 2 for gas, Zone 21 or Zone 22 for dust).

Specific Conditions of Use in Hazardous Areas:

  1. MI Cable Seal assembly must be installed in a suitable enclosure to protect from light and impact.
  2. Service temperature range: -30°C to +120°C, -30°C to +105°C, or -60°C to +70°C.
  3. Maximum withstand temperatures and supply voltages are shown in Table 1.
  4. Minimum installation temperature: -60°C.
  5. Minimum cable spacing: 25 mm.
  6. Minimum bending radius: 6 x cable diameter.
  7. Handle MI Electric Heating cables with care to avoid weakening the mechanical strength.
  8. Consider environmental exposure when selecting sheath material to prevent stress corrosion cracking (SCC).
  9. When PVC sleeving is used, operating temperature must not exceed +85°C.
  10. In dust atmospheres, the Compression Ring Type cable Gland must be sealed according to manufacturer's instructions and applicable codes. The enclosure must have a minimum ingress protection of IP6X.
  11. The heating element supply circuit must include an electrical protection device per EN 60079-30-1.

Certificates and Codes:

Information on ATEX, IECEx, and EAC certifications and corresponding code numbers for heating units and bulk cable is provided, including ambient temperature ranges and specific conditions for hazardous locations.

3. Heating Cable Selection and Storage

Order Reference Nomenclature:

An explanation of the order reference nomenclature for MI heating units is provided, detailing each component of the reference string.

Table 1: Properties of MI Heating Units

A table summarizing the properties of MI heating units, including Number of conductors, Maximum voltage, Withstand temperatures (brazed and laser welded), Temperature classification, Minimum cable spacing, Minimum installation temperature, Minimum bending radius, and Chemical resistance for various MI Heating Cable Types (HCC/HCH, HDC/HDF, HSQ, HAx1N, HAx2N, HAx2M, HIQ).

Storage and Transportation:

4. Heating Cable Installation

WARNING:

Improper installation can lead to electrical tracking, arcing, and fire hazards. Unconnected heating cable ends exposed to the environment must be sealed.

3.1 Pre-installation Checks:

3.2 Heating Cable Pulling and Laying and General Installation Guidelines:

Figure 3: Importance of Cable Pulling Direction

Diagrams illustrating correct and incorrect cable pulling directions to avoid distortion and kinking.

When pulling the heating cable, avoid:

The minimum bending radius must be respected.

Figure 4: Minimum Bending Radius of MI Heating Cables

Diagram showing the minimum bending radius (6 x Ø Cable).

Figure 5: Minimal Spacing Must Be Respected

Diagrams illustrating minimum cable spacing requirements. Standard minimum spacing is 25 mm, and 50 mm for hazardous areas unless otherwise specified.

Heating Cable Allowances:

Areas with increased surface area (fittings, supports) require compensation through higher design safety factors or extra cable length. Consult design software and documentation for allowances.

3.3 Heating Cable Attachment:

Figure 6: Cable Orientation on Pipe

Diagrams showing cable orientation on pipes for one and two heating cables, including temperature sensors.

Figure 7: Typical Cable Layout on Large Surfaces like Tank Walls

Diagram showing cable layout on tank walls using pre-punched strapping and banding.

Figure 8: Fixing Device: Pre-punched Metal Strap

Diagram illustrating a pre-punched metal strap fixing device.

3.4 Attachment Materials:

3.5 Typical Installation Details:

Figure 9: Uncoiling Heating Cable

Diagram showing uncoiling of heating cable.

Figure 10: Attaching Hot-Cold Joint and End Cap

Diagrams showing the attachment of the hot-cold joint and end cap.

Figure 11: Allowances for Valves, Flanges, and Pipe Supports

Diagram showing allowances for valves, flanges, and pipe supports, using various attachment materials.

Figure 12: Installing Cable on Valves and Pipe Supports

Diagrams showing cable installation on valves and pipe supports.

Figure 13: Completed MI Heating Cable Installation

Diagram showing a completed MI heating cable installation.

Figure 14: Pipe Strap Spacing

Diagram illustrating pipe strap spacing for hot-cold joints and junction boxes.

Figure 15: Fastening Several Runs of Cable

Diagram showing fastening of multiple runs of cable using banding and strapping.

Figure 16a & 16b: Valves

Diagrams showing cable attachment to valves of different sizes.

Figure 17: Installation at 90° Elbow

Diagram showing cable installation on a 90° elbow.

Figure 18: Flanges

Diagram showing cable attachment to flanges.

Figure 19: Cable Layout Over Clamps and Straps

Diagram showing cable layout over clamps and straps.

Figure 20: Shoe and Sleeve Type Support

Diagram showing cable attachment to shoe and sleeve type supports.

Figure 21: Dummy Supports

Diagram showing cable attachment to dummy supports.

Figure 22: Pumps

Diagram showing cable attachment to pumps.

Figure 23: Cable Applied on Metal Wire Mesh

Diagram showing cable applied on metal wire mesh.

3.6 Heating Cable Allowances:

Increased heat loss areas require compensation. Refer to Raychem design specification for details.

5. Components Selection and Installation

4.1 General Notes:

Use the Design Specification to select components. Raychem components are required for warranty and compliance.

4.2 Component Installation Hints:

Important: Tighten compression nut to the torque setting indicated on the tag to ensure proper grounding and prevent moisture entry.

6. Temperature Control and Limitation

5.1 General Rules:

Raychem MI heating cables typically require temperature control. Independent temperature limitation devices may be required based on local regulations and environmental conditions.

5.2 Sensor Placement: Temperature Control Device:

Sensor placement depends on fluid flow direction, heat sinks, chimney effect, accessibility, and other heat sources.

5.3 Sensor Placement: Temperature Limiter Device:

Sensor placement for limiter devices depends on similar factors, with specific considerations for upstream/downstream placement and proximity to heat sinks.

7. Thermal Insulation and Marking

6.1 Pre-insulation Checks:

6.2 Insulation Related Requirements:

6.3 Marking:

MI-Heating Unit Identification:

Figure 24: Typical MI Identification Tag (for use in hazardous areas)

An example of a typical MI identification tag, showing catalogue number, serial number, output power, circuit ID, maximum sheath temperature, design method, hazardous location certifications, and other relevant data.

8. Power Supply and Electrical Protection

7.1 Earth Connection:

7.2 Electrical Loading:

Size overcurrent protective devices according to design specification and local practices.

7.3 Residual Current (Earth Fault) Protection:

7.4 Isolation from Power Supply:

Means of isolation from the supply is mandatory for heating circuits in hazardous areas.

7.5 Circuit Marking:

System must be properly marked with a heating cable tag in hazardous area installations.

9. System Testing and Commissioning

WARNING:

Megger tests can produce sparks. Ensure no flammable vapors are present before testing.

8.1 Testing of Insulation Resistance and Conductor Resistance:

8.2 Test Method for Insulation Resistance Testing:

8.3 Commissioning:

10. Documentation, Operation, Maintenance and Repairs

WARNING:

Heating cables reach high temperatures and can cause burns. Avoid contact when powered. Thermally insulate traced pipes/equipment before energizing. Use only trained personnel.

Caution:

Consult documentation prior to maintenance/repair/modification. Test earth-fault device after maintenance.

In case of earth fault or overcurrent interruption, the device shall not be reset until the cause is investigated.

9.1 Documentation:

Retain trace heating system documentation for each circuit. It should include:

This data is usually part of as-built documentation or calculation reports.

9.2 Heating Cable Operation:

9.3 Inspection and Maintenance:

11. Troubleshooting

WARNING:

Damaged cables can cause arcing or fire. Do not energize damaged cables. Repairs must be done by qualified personnel. Contact Chemelex for assistance.

Evaluate damage severity to determine if repair or replacement is needed.

Symptom and Probable Causes:

A. Insulation resistance less than expected:

  1. Rainy or high humidity
  2. Nicks or cuts in heating cable sheath with moisture
  3. Kinked or crushed heating cable
  4. Arcing from cable damage
  5. Physical damage causing a direct short
  6. Moisture in terminations or connections
  7. Damaged termination
  8. Moisture in junction boxes

B. Circuit breaker trips:

  1. Circuit breaker undersized
  2. Defective circuit breaker
  3. Short circuit in electrical connections
  4. Excessive moisture in connection boxes
  5. Nicks or cuts in heating cable sheath with moisture
  6. Kinked or crushed heating cable
  7. Defective RCD
  8. Excessive earth leakage current, RCD trips

C. Power output correct, but pipe temperature below design:

  1. Wet or missing insulation
  2. Insufficient heating cable on valves, flanges, supports, pumps
  3. Temperature controller set incorrectly
  4. Improper thermal design
  5. Temperature sensor in wrong location
  6. Low fluid temperature entering pipe

D. Power output is zero or incorrect:

  1. No input voltage
  2. Temperature controller wired incorrectly (N.O. position)
  3. Limiter has tripped
  4. Broken or damaged heating element, hot-cold joint, end cap, or tail
  5. Wrong cable used
  6. Improper voltage used

Locate Faults:

  1. Visually inspect power connections, splices.
  2. Look for damage at end seals, valves, pumps, flanges, supports, and areas of recent maintenance.
  3. Look for crushed or damaged insulation and cladding.
  4. If fault persists, consult Chemelex.

Corrective Actions:

For Insulation Resistance Less Than Expected:

  1. Dry tails and face of seal.
  2. Inspect cable for damage, especially at elbows, flanges, valves. Repair or replace if damaged.
  3. Inspect power connection box for moisture.
  4. Dry connections and retest.
  5. Check areas of maintenance work for damage. Replace damaged sections if necessary.
  6. Dry cold lead/connections and replace termination if needed.
  7. Replace termination.
  8. Check and replace seals on junction boxes.

For Circuit Breaker Trips:

  1. Recalculate load current, resize breaker.
  2. Repair or replace breaker.
  3. Eliminate short circuit, dry connections.
  4. Eliminate short circuit, dry connections.
  5. Repair or replace damaged section.
  6. Repair or replace damaged section.
  7. Replace RCD.
  8. Check insulation resistance. Evaluate electrical design for RCD compatibility.

For Pipe Temperature Below Design:

  1. Remove wet insulation, replace with dry, and secure.
  2. Confirm compliance with system design; additional cable may be needed for changed fittings/supports.
  3. Reset temperature controller.
  4. Contact Chemelex for design confirmation and modification.
  5. Confirm sensor location.
  6. Verify fluid temperature.

For Zero or Incorrect Power Output:

  1. Repair electrical supply lines and equipment.
  2. Confirm wiring using normally closed (N.C.) terminals.
  3. Check reason for limiter trip, resolve, and reset limiter.
  4. Repair or replace heating cable.
  5. Verify installation and replace cable if necessary.
  6. Verify voltage and connect to proper voltage.

12. Installation Record Sheet

A record sheet is provided for documenting installation details, including company, project, site, area, installer, circuit number, P&ID number, drawing number, panel/breaker number, heating cable type, and cable length.

Required Value vs. Actual Value:

Sections for visual inspection, insulation resistance tests, and prior to energizing the cable, comparing required values with actual recorded values for spacing, bending radius, sensor installation, insulation resistance, loop resistance, and cable covering.

Models: MI Series Heating Systems, MI Series, Heating Systems, Systems

File Info : application/pdf, 40 Pages, 1.98MB

PDF preview unavailable. Download the PDF instead.

RAYCHEM-IM-DOC586-MI-EN ?srsltid=AfmBOoqLG4KwkDKEPDmr83gCKETG0KMB-XHsS1VBsm6CIIa39dH85z9t

References

Adobe PDF Library 17.0 Adobe InDesign 20.3 (Windows)

Related Documents

Preview Raychem MI Series Heating Systems (IEC / ATEX) - Chemelex
Explore Raychem MI Series Mineral Insulated heating systems, designed for hazardous areas (ATEX/IECEx) with robust construction, advanced control and monitoring capabilities, and optimized system design using Raychem TraceCalc Pro software.
Preview Raychem XPI-S Polymer Insulated Resistance Heating Cable Datasheet
Comprehensive datasheet for the Raychem XPI-S Polymer Insulated (PI) series resistance heating cable. Details product overview, technical specifications, hazardous area approvals, and ordering information for industrial heating applications.
Preview Raychem Mineral Insulated Cable Repair Guide: Procedures and Safety
Comprehensive guide for repairing and modifying Raychem Mineral Insulated (MI) heating cables by Chemelex. Covers safety, tools, repair kits, joining, end caps, and testing for copper and Alloy 825 sheath cables.
Preview Industrial Electrical Heat Tracing Systems Engineering Specification
This engineering specification details requirements for Raychem's advanced industrial electrical heat-management and heat tracing systems, covering design, materials, installation, and testing.
Preview Raychem MI Heating Cable System Installation and Operation Manual
Comprehensive guide for the installation, operation, and maintenance of Raychem MI heating cable systems for various applications including heat loss replacement, freezer frost heave prevention, comfort floor heating, and radiant space heating. Covers safety guidelines, electrical codes, component installation, power supply, commissioning, and troubleshooting.
Preview Raychem Industrial Heat-Tracing: Installation and Maintenance Manual
Comprehensive guide for the installation and maintenance of Raychem Series Resistance (SC) heating cable systems for pipes. Covers general information, safety, installation procedures, component installation, control and monitoring, thermal insulation, power supply, commissioning, testing, and troubleshooting.
Preview Raychem Self-Regulating Heating Cable: The Original and Reliable Solution
Explore Raychem's original self-regulating heating cable, detailing its performance characteristics based on ambient temperature (cold, warm, hot). Learn about its user-friendly and reliable features, historical significance, and industry certifications. Includes contact information for Chemelex, a leading manufacturer.
Preview Raychem XTV Self-Regulating Heating Cable: Product Overview and Specifications
Detailed product overview and technical specifications for the Raychem XTV self-regulating heating cable, including applications, performance data, approvals, and ordering information. Suitable for process temperature maintenance and frost protection in ordinary and hazardous areas.