Sealed System Information Integrated (700-3 TALL) Series
HFC-134a REFRIGERANT SERVICE INFORMATION
The 700-3 Series sealed systems contain HFC-134a refrigerant. This section provides some general rules for working with 134a, and explains procedures to be followed while servicing the sealed system. This is followed by diagrams which illustrate sealed system operation, then model-specific refrigerant flow diagrams.
CAUTION
134a refrigerant requires Synthetic Ester oil in the compressor, and does not tolerate contamination from other refrigerants, moisture, petroleum-based lubricants, silicone lubricants, cleaning compounds, rust inhibitors, leak detection dyes, or any other type of additive.
General Rules for Working with 134a Refrigerant
- Use equipment dedicated to 134a sealed system service only.
- Use only 134a refrigerant for back-flushing and sweep charging.
- Always replace the filter-drier when servicing the sealed system.
- The filter-drier must be cut from the sealed system. Never un-braze the drier as the heat will drive moisture back into the sealed system.
- Do not leave sealed system nor replacement compressor open to the atmosphere for more than 10 minutes.
- When the rubber plugs are pulled from the service compressor, a release of pressure should be heard. If no release of pressure is heard, do not use the compressor.
- Use ONLY virgin 134a refrigerant when recharging the sealed system.
SEALED SYSTEM REPAIR PROCEDURES
Problem | Service Procedures |
---|---|
Non-Operating, Inefficient, Noisy Compressor |
NOTE: To check for a non-operating compressor, a hard start kit can be used. |
High Side leak |
|
Low Side Leak |
|
Contaminated Sealed System Examples: > Burned out compressor > Excessive moisture from leak in condensate loop or in low side > Plugged capillary tube |
|
Restriction NOTE: If restriction is due to sealed system being contaminated, see Contaminated Sealed System above. |
|
Overcharge |
|
SEALED SYSTEM OPERATION
The six diagrams on these pages illustrate a basic sealed system. The components are listed in order of refrigerant flow, with an explanation of their fundamental role as part of a sealed system. NOTE: These illustrations do not represent any specific 700-3 sealed system.
Compressor (Figure 4-1)
The compressor creates a high side and low side pressure difference in the sealed system by compressing the refrigerant gas, thus raising the pressure and temperature. The compressor pushes this high-pressure/high-heat gas to the condenser.
[Diagram: Compressor showing high and low side pressure lines.]
Condenser (Figure 4-2)
The high-pressure/high-heat gas travels through the condenser, where the heat is dissipated by cooler air being drawn over the condenser tubing by the condenser fan. This changes the gas into a high-pressure/warm liquid that is then routed through the door gasket seat heater loop to prevent sweating. After traveling through the heater loop, the high-pressure/warm liquid enters the high-side filter-drier.
[Diagram: Condenser and Heater Loop showing refrigerant flow.]
Filter-Drier (Figure 4-3)
The high-pressure/warm liquid travels through the high-side filter-drier, which removes moisture from the refrigerant before it enters the capillary tube.
[Diagram: Filter-Drier showing refrigerant entering and exiting.]
Capillary Tube (& Heat Exchanger) (Figure 4-4)
The warm liquid refrigerant travels through the long skinny capillary tube which is soldered to the suction line. (These two tubes soldered together create the heat exchanger.) As the warm liquid refrigerant travels through the capillary tube it gives up heat to the cool refrigerant gas traveling through the suction line and the pressure drops, so it is a low-pressure/cool liquid before it enters the evaporator.
[Diagram: Capillary Tube and Heat Exchanger showing refrigerant flow.]
Evaporator (Figure 4-5)
As the low-pressure/cool liquid refrigerant enters the evaporator, it vaporizes. This is caused by a dramatic pressure change which occurs when the refrigerant enters the larger diameter evaporator tubing from the smaller diameter capillary tubing. This vapor travels through the evaporator absorbing heat from the compartment, gradually converting it to a cool gas. This cool gas then enters the suction line.
[Diagram: Evaporator showing refrigerant vaporizing and absorbing heat.]
Suction Line (& Heat Exchanger) (Figure 4-6)
The cool gas travels through the suction line which is soldered to the capillary tube. (As mentioned earlier, these two tubes soldered together create the heat exchanger.) As this cool refrigerant gas travels through the suction line it absorbs heat from the warm liquid refrigerant traveling through the capillary tube, making it a luke warm gas. The lukewarm refrigerant gas then returns to the compressor where the process begins again.
[Diagram: Suction Line and Heat Exchanger showing cool gas absorbing heat.]
SEALED SYSTEM REFRIGERANT FLOW DIAGRAMS
Key:
- > = REFRIGERATOR SEALED SYSTEM
- > = FREEZER SEALED SYSTEM
Figure 4-7. Models 700TC/I-3 and 736TC/I-3 Refrigerant Flow
[Diagram: Refrigerant flow for Models 700TC/I-3 and 736TC/I-3, showing refrigerator and freezer systems, compressors, heat exchangers, evaporators, filter-driers, and condenser.]
Figure 4-8. Model 700TR-3 and 736TR-3 Refrigerant Flow
[Diagram: Refrigerant flow for Model 700TR-3 and 736TR-3, showing upper and lower refrigerator systems, compressors, heat exchangers, evaporators, filter-driers, and condenser.]
Figure 4-9. Model 700TF/I-3 Refrigerant Flow
[Diagram: Refrigerant flow for Model 700TF/I-3, showing freezer system, compressor, heat exchanger, evaporator, filter-drier, and condenser.]