This guide provides specifications for Unitronics' Short Range and Long Range Local Expansion Adapter Kit for Uni-I/O™.
All Kits comprise a Base unit, an End unit, and a connecting cable. The cable length varies according to kit model.
Kits whose models contain the letter 'P' include a built-in power supply; a powered adapter module supports a greater number of I/O modules.
There are two main classes of adapters:
Both the Base and End units of these adapters have DIN-rail clips. Users can:
The base unit of these adapters has a plug; the end unit has DIN-rail clips. Users can plug the base unit only into the I/O Expansion Jack offered by the UniStream Built-in series.
Note that the maximum number of modules supported by a single controller is provided in the controller's technical specifications.
Technical specifications are available in the Unitronics Technical Library at www.unitronicsplc.com.
The 'x's in the model numbers are placeholders for the cable lengths.
Model | Installation Options | Integrated Power Supply | Module Support |
---|---|---|---|
UAG-XKxxx | DIN-rail structure | No | 8, includes any modules directly connected to a controller |
UAG-XKPxxx | DIN-rail | Yes | 16 |
UAG-XKPLxxxx | Yes | 16, in addition to any modules directly connected to a controller | |
UAG-CX-XKPxxx | Plug into controller Jack | Yes | 16 |
UAG-CX-XKPLxxxx | Yes | 16 |
Installation Guides are available in the Unitronics Technical Library at www.unitronicsplc.com.
Power Supply | UAG-XKxxx | UAG-XKPxxx, UAG-CX-XKPxxxx, UAG-CX-XKPLxxxx, UAG-XKPLxxxx |
---|---|---|
Input voltage | Not applicable | 12 or 24 VDC |
Permissible range | Not applicable | 10.2 to 28.8 VDC |
Max. current consumption | Not applicable | 0.9@12VDC, 0.5A@24VDC |
Module | Length |
---|---|
UAG-XK125 | 125cm (49") |
UAG-XKP125 | 125cm (49") |
UAG-CX-XKP125 | 125cm (49") |
UAG-XK300 | 300cm (118") |
UAG-XKP300 | 300cm (118") |
UAG-CX-XKP300 | 300cm (118") |
UAG-CX-XKPL600 | 600cm (20') |
UAG-CX-XKPL1200 | 1200cm (40') |
UAG-CX-XKPL1500 | 1500cm (50') |
UAG-CX-XKPL2000 | 2000cm (66') |
UAG-CX-XKPL3000 | 3000cm (98') |
UAG-XKPL600 | 600cm (20') |
UAG-XKPL1200 | 1200cm (40') |
UAG-XKPL1500 | 1500cm (50') |
UAG-XKPL2000 | 2000cm (66') |
UAG-XKPL3000 | 3000cm (98') |
Unit | Green | Output state | Comment |
---|---|---|---|
Base Unit | There are no LEDs in the Base Unit. | ||
End Unit | Link | Off | Cable is not connected, or no power from the Base unit |
On | Link has been established with the base unit | ||
UAG-XKPxxx, UAG-CX-XKPxxxx, UAG-XKPLxxxx | Power | Off | No external power |
On | External power is connected to the unit | ||
UAG-XKxxxx, UAG-CX-XKPLxxxx | Link | Off | Cable is not connected, or no power from the Base unit |
On | Link has been established with the base unit |
Up to five Local Expansion Adapters may be chained to each other. The maximum number of I/O modules that can be connected to a single controller is:
UniStream can be expanded locally in a single cabinet, using Short range Adapters of up to 3 meters each (UAG-XKxxxx, UAG-XKPxxxx and UAG-CX-XKPxxxx).
It can also be expanded further to another cabinet, using the Long Range Expansion Adapter (UAG-XKLxxxx, UAG-CX-XKPLxxxx) as shown in the following descriptions:
A diagram depicts a single cabinet setup. It shows a CPU connected to I/O modules, followed by a UAG-XKPxxxx adapter, then more I/O modules, and another UAG-XKPxxxx adapter, extending up to 5 units. This configuration supports up to 16 units of I/O modules. Another line shows a UAG-XKL adapter connected to I/O modules, supporting up to 16 units.
A diagram illustrates two cabinets connected by a long-range kit. The first cabinet contains a CPU connected to I/O modules, followed by a UAG-XKPxxxx adapter, then more I/O modules, extending up to 16 units. This cabinet is connected via a long-range kit to a second cabinet, which also contains a UAG-XKPxxxx adapter and I/O modules, supporting up to 16 units.
In order to connect a UniStream™ controller to more than one row of I/O modules via Local I/O Expansion adapters, the following rules must be followed:
Notes:
A diagram shows the greatest number of I/O modules that can be connected to a single UniStream™ controller using Uni-I/O modules and 5 Local I/O Expansion adapters with power supplies. The top row shows a CPU connected to I/O modules (up to 5 units), followed by a UAG-XKPxxxx adapter and I/O modules (up to 16 units), and another UAG-XKPxxxx adapter and I/O modules (up to 16 units). The bottom row shows a UAG-XKL adapter connected to I/O modules (up to 16 units), followed by a UAG-XKPxxxx adapter and I/O modules (up to 16 units), and another UAG-XKPxxxx adapter and I/O modules (up to 16 units).
If UAG-XKxxxx is the only adapter connected to the controller, the system can support up to 8 modules.
A diagram illustrates a CPU connected to I/O modules (up to 5 units), followed by a UAG-XKxxxx adapter and I/O modules (up to 8 units).
If a UAG-XKxxxx follows another adapter with an integrated power supply, the support capacity of that powered module limits the number of Uni-I/Os that can be connected to the UAG-XKxxxx; in any event, no more than 8 Uni-I/Os can follow a UAG-XKxxxx adapter.
A diagram shows a UAG-XKPxxx, UAG-CX-XKPxxx, or UAG-XKLxxxx adapter connected to I/O modules (up to 16 units), followed by a UAG-XKxxxx adapter and I/O modules (up to 8 units).
A complex diagram illustrates various combinations. The top row shows a CPU connected to I/O modules (up to 5 units), followed by a UAG-XKPxxxx adapter and I/O modules (up to 16 units), then a UAG-XKxxxx adapter and I/O modules (up to 8 units), and finally another UAG-XKPxxxx adapter and I/O modules (up to 16 units). The bottom row shows a UAG-XKL adapter connected to I/O modules (up to 16 units), followed by a UAG-XKxxxx adapter and I/O modules (up to 8 units), and then a UAG-XKPxxxx adapter and I/O modules (up to 16 units).
The tables below show the possible configurations between two cabinets.
Controller | 1st | 2nd | Max. UniStream Modular 7" | Max. UniStream Modular 10.4",15.6" | Max. UniStream PLC |
---|---|---|---|---|---|
- | - | 3 | 5 | 8 | |
XK | - | 8 | 8 | 8 | |
XKP | - | 19 | 21 | 24 | |
XKP | XK | 19 | 21 | 24 | |
XK | XKP | 24 | 24 | 24 | |
XKP | XKP | 35 | 37 | 40 |
3rd | 4th | 5th | Max. Modules |
---|---|---|---|
- | - | - | 16 |
XK | - | - | 16 |
XKP | - | - | 32 |
XKL | XKP | XK | 32 |
XK | XKP | 32 | |
XKP | XKP | 48 |
Key for Adapter Models:
Note: Each combination in the right table can be used with each combination in the left table. They are independent of each other and the total number of I/O modules that are supported is the sum of the two tables.
Users must use the UAG-CX-XKPxxx or UAG-CX-XKPLxxx, and it must be the adapter that is directly connected to the controller.
Controller | 1st | 2nd | Max. Modules |
---|---|---|---|
- | - | 0 | |
- | - | 16 | |
CX | XK | 24 | |
XKP | 32 |
3rd | 4th | 5th | Max. Modules |
---|---|---|---|
- | - | - | 16 |
XK | - | - | 16 |
XKP | - | - | 32 |
XKL | XKP | XK | 32 |
XK | XKP | 32 | |
XKP | XKP | 48 |
Protection | IP20, NEMA1 |
---|---|
Operating Temperature | -20°C to 55°C (-4°F to 131°F) |
Storage Temperature | -30°C to 70°C (-22°F to 140°F) |
Relative Humidity (RH) | 5% to 95% (non-condensing) |
Operating Altitude | 2,000 m (6,562 ft) |
Shock | IEC 60068-2-27, 15G, 11ms duration |
Vibration | IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration |
Dimensions for UAG-XKxxx, UAG-XKPxxx, UAG-XKPLxxxx, UAG-CX-XKPxxx, UAG-CX-XKPLxxxx models:
UAG-XKxxx | UAG-XKPxxx | UAG-XKPLxxxx | UAG-CX-XKPxxx | UAG-CX-XKPLxxxx | |
---|---|---|---|---|---|
Weight | Base: 65 g (0.14 lb) End: 142 g (0.31 lb) | Base: 65 g (0.14 lb) End: 150 g (0.33 lb) | Base: 64 g (0.14 lb) End: 92 g (0.2 lb) | Base: 15 g (0.033 lb) End: 150 g (0.33 lb) | Base: 15 g (0.14 lb) End: 92 g (0.2 lb) |
Size | Refer to the images below |
Top View: A rectangular unit with a rounded top, showing internal components. Overall width is 64.0 mm (2.52").
Side View: A profile view showing the unit's height and depth. Total height is 122.5 mm (4.83"). The main body height is 114.8 mm (4.52").
Front View: A front profile view showing the unit's depth and width. Total depth is 24.0 mm (0.94"). The main body depth is 16.0 mm (0.63"). A smaller protrusion is 9.3 mm (0.37").
Top View: A rectangular unit with a plug connector on one side. The main body width is 20.28 mm (0.798"). The plug section has a width of 14.62 mm (0.575") and a height of 18.7 mm (0.735"). The overall height including the plug is 41 mm (1.614").
Side View: A profile view showing the unit's height and depth. The main body height is 22.32 mm (0.879"). The plug extends 11 mm (0.433") from the bottom.
Front View: A front profile view showing the unit's width and depth. The main body width is 28.3 mm (1.114").
Top View: A rectangular unit with a series of connectors on one side. Overall width is 64.5 mm (2.54").
Side View: A profile view showing the unit's height and depth. Total height is 115.0 mm (4.53").
Front View: A front profile view showing the unit's width and depth. Total depth is 29.0 mm (1.14"). Overall height is 119.2 mm (4.69").
![]() |
Unitronics UniStream I/O Expansion Adapter Kits: Technical Specifications and Configuration Guide Comprehensive technical specifications and configuration guide for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx) for increasing I/O modules in industrial automation systems. |
![]() |
Unitronics UniStream I/O Expansion Adapter Kits Technical Specifications Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx), covering models, power supply, module support, daisy-chaining rules, configuration examples, environmental conditions, and dimensions for expanding UniStream I/O capabilities. |
![]() |
UniStream Local Expansion Adapter Kit Technical Specifications Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx), covering adapter models, power supply, module support, daisy-chaining rules, configuration examples, environmental conditions, and dimensions. |
![]() |
Spécifications Techniques des Kits d'Adaptateurs d'Extension UniStream Unitronics Découvrez les spécifications techniques détaillées des kits d'adaptateurs d'extension court et longue distance Unitronics UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx et UAG-XKPLxxxx pour les systèmes UniStream, incluant les modèles, l'alimentation, les longueurs de câble et les configurations en cascade. |
![]() |
Système d'Automatisation Modulaire UniStream® - IHM et API Découvrez les systèmes UniStream® d'Unitronics, des solutions IHM et API modulaires et extensibles. Caractéristiques, spécifications techniques et options de communication pour les modèles 7", 10.4" et 15.6". |
![]() |
7" dotykový TFT LCD panel UniStream™ s CANbus, RS485 a USB 7" dotykový TFT LCD panel UniStream™ s rozlišením 800x480 (154,08 x 85,92mm), vybavený 2x Ethernet, 2x USB, mikro USB a slotem pro SD kartu. Objednací kód: U-USP-070-B08. |
![]() |
Unitronics PLC и HMI: Полный каталог продукции для автоматизации Обзор продукции Unitronics, включая серии UniStream, Vision, Samba и Jazz. Узнайте о программируемых логических контроллерах (ПЛК) и человеко-машинных интерфейсах (HMI), их возможностях, технических характеристиках и программном обеспечении UniLogic. |
![]() |
Unitronics EU Declaration of Conformity for Programmable Controllers and HMIs Official EU Declaration of Conformity from Unitronics GmbH for their range of programmable controllers and HMI panels, detailing compliance with LVD, EMC, and RoHS directives. |