This guide provides specifications for Unitronics' Short Range and Long Range Local Expansion Adapter Kits for Uni-I/O™. These kits increase the number of I/Os connected to a single UniStream™ controller by linking it to an additional row of Uni-I/O™ modules.
All Local Expansion Adapter Kits include a Base unit, an End unit, and a connecting cable. Two adapter series are available:
Model | Install via | Integrated Power Supply | Number of supported modules |
---|---|---|---|
UAG-XKxxx | Panel (DIN-rail structure) | No | 8, including modules installed on the panel |
UAG-XKPxxx | Yes | 16, in addition to any modules installed on the panel | |
UAG-XKPLxxx | Yes | ||
UAG-CX-XKPxxx | Controller (Jack) | Yes | 16 |
UniStream controller panels with a CPU-for-Panel can supply power to a maximum of 8 modules, Uni-I/O™ and/or Uni-COM™. Adapters that do not have a power supply draw power from UniStream and supply it to the modules. This means, for example, that if there are 3 modules snapped onto the panel, an additional 5 can be added via this type of adapter.
Adapters with an integrated power supply must be connected to a 24VDC power source. These adapters can then supply up to 16 modules with power, regardless of any modules mounted on the panel.
Installation Guides are available in the Unitronics Technical Library at www.unitronics.com.
The number of modules in the next table includes:
Note that:
Important Note: The Base and End Units of the Short-range and Long-range models look similar but are not interchangeable; do not mix them.
The number of modules in the next table refers only to the modules connected to the adapter. These controllers lack the DIN-rail structure and cannot be installed with Uni-COM or Uni-I/O.
UAG-XKxxx | UAG-XKPxxx, UAG-CX-XKPxxx | UAG-XKPLxxxx | |
---|---|---|---|
Up to 8 modules | Up to 16 modules | Up to 16 modules |
UAG-XKxxx | UAG-XKPxxx, UAG-CX-XKPxxx | UAG-XKPLxxxx | |
---|---|---|---|
Input voltage | Not applicable | 12 or 24 VDC | 12 or 24 VDC |
Permissible range | Not applicable | 10.2 to 28.8 VDC | 10.2 to 28.8 VDC |
Max. current consumption | Not applicable | 0.9A@12VDC, 0.5A@24VDC | 0.9A@12VDC, 0.5A@24VDC |
Module | Length |
---|---|
UAG-XK125 | 125cm (49") |
UAG-XKP125 | 125cm (49") |
UAG-CX-XKP125 | 125cm (49") |
UAG-XK300 | 300cm (118") |
UAG-XKP300 | 300cm (118") |
UAG-CX-XKP300 | 300cm (118") |
UAG-XKPL600 | 600cm (20') |
UAG-XKPL1200 | 1200cm (40') |
UAG-XKPL1500 | 1500cm (50') |
UAG-XKPL2000 | 2000cm (66') |
UAG-XKPL3000 | 3000cm (98') |
Green | Output state | Comment | |
---|---|---|---|
Base Unit | There are no LEDs in the Base Unit. | ||
End Unit | |||
UAG-XKxxx | Link | Off | Cable is not connected or no power from the Base unit |
On | Link with the base unit has been established | ||
Power | Off | No external power | |
UAG-XKPxxx, UAG-CX-XKPxxx | On | External power is connected to the unit | |
UAG-XKPLxxxx | Link | Off | Cable is not connected or no power from the Base unit |
On | Link with the base unit has been established |
Up to five Local Expansion Adapters may be chained to each other. The maximum number of I/O modules that can be connected to a single controller is:
UniStream can be expanded locally in a single cabinet, using Short range Adapters of up to 3 meters each (UAG-XKxxxx, UAG-XKPxxxx and UAG-CX-XKPxxxx). It can also be expanded further to another cabinet, using the Long Range Expansion Adapter (UAG-XKLxxxx).
Single Cabinet Configuration: A diagram shows a UniStream controller (CPU I/O) connected to a series of I/O modules. Following these, a UAG-XKPxxxx adapter is connected, leading to more I/O modules (up to 16 units). This setup illustrates local expansion within one cabinet.
Two Cabinets Configuration (Long-range Kit): A diagram depicts two separate cabinets. The first cabinet contains a UniStream controller (CPU I/O) connected to I/O modules, followed by a UAG-XKPxxxx adapter and more I/O modules (up to 16 units). This cabinet is then connected via a "Long-range Kit" (UAG-XKL) to a second cabinet. The second cabinet contains a UAG-XKPxxxx adapter connected to I/O modules (up to 16 units), demonstrating expansion across two cabinets using a long-range adapter.
To connect a UniStream™ controller to more than one row of I/O modules via Local I/O Expansion adapters, the following rules must be followed:
Notes:
A diagram illustrates the maximum number of I/O modules connected to a single UniStream™ controller using Uni-I/O modules and 5 Local I/O Expansion adapters with power supplies. The setup shows a CPU I/O unit connected to a series of I/O modules (up to 5 units). This is followed by a UAG-XKPxxxx adapter connected to more I/O modules (up to 16 units). This chain continues with a UAG-XKL (Long Range) adapter, then another UAG-XKPxxxx adapter with I/O modules (up to 16 units), and finally another UAG-XKPxxxx adapter with I/O modules (up to 16 units). This demonstrates a complex daisy-chaining configuration for maximum I/O expansion.
A diagram shows a CPU I/O unit connected to I/O modules (up to 5 units). If a UAG-XKxxxx adapter is the only adapter connected to the controller, it is shown connected to the I/O modules, supporting up to 8 modules in total.
If a UAG-XKxxxx follows another adapter with an integrated power supply (e.g., UAG-XKPxxx, UAG-CX-XKPxxx, or UAG-XKLxxxx), the support capacity of that powered module limits the number of Uni-I/Os that can be connected to the UAG-XKxxxx; in any event, no more than 8 Uni-I/Os can follow a UAG-XKxxxx adapter. A diagram illustrates this: a UAG-XKPxxx/UAG-CX-XKPxxx/UAG-XKLxxxx adapter is connected to I/O modules (up to 16 units), which then connects to a UAG-XKxxxx adapter, which in turn connects to I/O modules (up to 8 units).
The tables below show the possible configurations between two cabinets.
Optional configurations in the cabinet with the UniStream Controller | Optional configurations in the other cabinet | ||||||
---|---|---|---|---|---|---|---|
On Board | 1st | 2nd | Max. Modules | 3rd | 4th | 5th | Max. Modules |
- | - | 5 | - | - | 16 | ||
XK | - | 8 | XK | - | 16 | ||
CPU | XKP | - | 21 | XKL | XKP | - | 32 |
XKP | XK | 21 | XKP | XK | 32 | ||
XK | XKP | 24 | XK | XKP | 32 | ||
XKP | XKP | 37 | XKP | XKP | 48 | ||
XK-UAG-XKxxxx (Short Range Local Expansion Adapter without power supply) | |||||||
XKP-UAG-XKPxxxx (Short Range Local Expansion Adapter with power supply) | |||||||
XKL-UAG-XKLxxxx (Long Range Local Expansion Adapter) |
NOTE: Each combination in the right table can be used with each combination in the left table. They are independent of each other and the total number of I/O modules that are supported is the sum of the two tables (Maximum of 85).
Note that in the case of UniStream™ controllers comprising an I/O Expansion Jack, the UAG-CX-XKPxxx must be used, and it must be the adapter directly connected to the controller.
Optional configurations in the cabinet with the UniStream Controller | Optional configurations in the other cabinet | ||||||
---|---|---|---|---|---|---|---|
1st | 2nd | Max. Modules | 3rd | 4th | 5th | Max. Modules | |
- | - | 0 | - | - | 16 | ||
Controller jack | CX | - | 16 | XK | - | 16 | |
XK | 24 | XKL | XKP | - | 32 | ||
XKP | 32 | XKP | XK | 32 | |||
XK | XKP | 32 | |||||
XKP | XKP | 48 |
NOTE: The total number of I/O modules that are supported is the sum of the two tables (Maximum of 80).
Protection | IP20, NEMA1 |
Operating temperature | -20°C to 55°C (-4°F to 131°F) |
Storage temperature | -30°C to 70°C (-22°F to 140°F) |
Relative Humidity (RH) | 5% to 95% (non-condensing) |
Operating Altitude | 2,000 m (6,562 ft) |
Shock | IEC 60068-2-27, 15G, 11ms duration |
Vibration | IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration |
Refer to the descriptions below for unit dimensions.
This base unit is generally rectangular with a slightly tapered top. Key dimensions are:
This base unit has a distinct connector shape. Key dimensions are:
The end unit is a rectangular block with a ribbed top surface. Key dimensions are:
Dimensions | UAG-XKxxx | UAG-XKPxxx | UAG-CX-XKPxxx | UAG-XKPLxxxx |
---|---|---|---|---|
Weight | Base: 65 g (0.14 lb) End: 142 g (0.31 lb) | Base: 65 g (0.14 lb) End: 150 g (0.33 lb) | Base: 15 g (0.033 lb) End: 150 g (0.33 lb) | Base: 64 g (0.14 lb) End: 92 g (0.2 lb) |
![]() |
Unitronics UniStream I/O Expansion Adapter Kits: Technical Specifications and Configuration Guide Comprehensive technical specifications and configuration guide for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx) for increasing I/O modules in industrial automation systems. |
![]() |
Unitronics UniStream I/O Expansion Adapter Kits Technical Specifications Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx), covering models, power supply, module support, daisy-chaining rules, configuration examples, environmental conditions, and dimensions for expanding UniStream I/O capabilities. |
![]() |
UniStream Expansion Adapter Kit Technical Specifications Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits for Uni-I/O, including models, power supply, cable lengths, LED indications, daisy-chaining rules, configuration examples, environmental specifications, and dimensions. |
![]() |
Spécifications Techniques des Kits d'Adaptateurs d'Extension UniStream Unitronics Découvrez les spécifications techniques détaillées des kits d'adaptateurs d'extension court et longue distance Unitronics UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx et UAG-XKPLxxxx pour les systèmes UniStream, incluant les modèles, l'alimentation, les longueurs de câble et les configurations en cascade. |
![]() |
Système d'Automatisation Modulaire UniStream® - IHM et API Découvrez les systèmes UniStream® d'Unitronics, des solutions IHM et API modulaires et extensibles. Caractéristiques, spécifications techniques et options de communication pour les modèles 7", 10.4" et 15.6". |
![]() |
7" dotykový TFT LCD panel UniStream™ s CANbus, RS485 a USB 7" dotykový TFT LCD panel UniStream™ s rozlišením 800x480 (154,08 x 85,92mm), vybavený 2x Ethernet, 2x USB, mikro USB a slotem pro SD kartu. Objednací kód: U-USP-070-B08. |
![]() |
Unitronics PLC и HMI: Полный каталог продукции для автоматизации Обзор продукции Unitronics, включая серии UniStream, Vision, Samba и Jazz. Узнайте о программируемых логических контроллерах (ПЛК) и человеко-машинных интерфейсах (HMI), их возможностях, технических характеристиках и программном обеспечении UniLogic. |
![]() |
Unitronics EU Declaration of Conformity for Programmable Controllers and HMIs Official EU Declaration of Conformity from Unitronics GmbH for their range of programmable controllers and HMI panels, detailing compliance with LVD, EMC, and RoHS directives. |