UniStream® Technical Specifications

UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx

This guide provides specifications for Unitronics' Short Range and Long Range Local Expansion Adapter Kit for Uni-I/O™.

The Short and Long Range Local Expansion Adapter Kits allow you to increase the number of I/Os connected to a single UniStream™ by linking it to an additional row of Uni-I/O™ modules.

All Local Expansion Adapter Kits comprise a Base unit, an End unit, and a connecting cable.

Note that there are two adapter series:

Adapter Models

ModelInstall viaIntegrated Power SupplyNumber of supported modules
UAG-XKxxxPanel (DIN-rail structure)No8, including modules installed on the panel
UAG-XKPxxxYes16, in addition to any modules installed on the panel
UAG-XKPLxxxYes
UAG-CX-XKPxxxController (Jack)Yes16

Power Supply

Installation Guides are available in the Unitronics Technical Library at www.unitronics.com.

Module Support

UniStream™ panels comprising a DIN-rail structure on the panel rear (compatible with UAG-XK)

The number of modules in the next table includes:

Note that:

Important Note:

The Base and End Units of the Short-range and Long-range models look similar but are not interchangeable; do not mix between them.

UniStream™ controllers that comprise an I/O Expansion Jack (compatible with UAG-CX)

The number of modules in the next table refers only to the modules connected to the adaptor.

These controllers lack the DIN-rail structure, and cannot be installed with Uni-COM or Uni-I/O.

UAG-XKxxxUAG-XKPxxx, UAG-CX-XKPxxxUAG-XKPLxxxx
Supported ModulesUp to 8 modulesUp to 16 modulesUp to 16 modules

Power Supply

UAG-XKxxxUAG-XKPxxx, UAG-CX-XKPxxxUAG-XKPLxxxx
Input voltageNot applicable12 or 24 VDC12 or 24 VDC
Permissible rangeNot applicable10.2 to 28.8 VDC10.2 to 28.8 VDC
Max. current consumptionNot applicable0.9@12VDC, 0.5A@24VDC0.9@12VDC, 0.5A@24VDC

Available Cable Length

ModuleLength
UAG-XK125125cm (49")
UAG-XKP125125cm (49")
UAG-CX-XKP125125cm (49")
UAG-XK300300cm (118″)
UAG-XKP300300cm (118″)
UAG-CX-XKP300300cm (118")
UAG-XKPL600600cm (20')
UAG-XKPL12001200cm (40')
UAG-XKPL15001500cm (50′)
UAG-XKPL20002000cm (66')
UAG-XKPL30003000cm (98')

LED Indications

GreenOutput stateComment
Base UnitThere are no LEDs in the Base Unit.
End UnitOffCable is not connected or no power from the Base unit
UAG-XKxxxLinkOnLink with the base unit has been established
OffNo external power
UAG-XKPxxxPowerOnExternal power is connected to the unit
UAG-CX-XKPxxxOffCable is not connected or no power from the Base unit
UAG-XKPLxxxxLinkOnLink with the base unit has been established

Daisy-Chaining: Extending and Expanding I/Os

Up to five Local Expansion Adapters may be chained to each other. The maximum number of I/O modules that can be connected to a single controller is:

UniStream can be expanded locally in a single cabinet, using Short range Adapters of up to 3 meters each (UAG-XKxxxx, UAG-XKPxxxx and UAG-CX-XKPxxxx).

It can also be expanded further to another cabinet, using the Long Range Expansion Adapter (UAG-XKLxxxx).

Daisy-chaining Rules

In order to connect a UniStream™ controller to more than one row of I/O modules via Local I/O Expansion adapters, the following rules must be followed:

UniStream™ comprising a DIN-rail structure (compatible with UAG-XK)

UniStream™ controllers comprising an I/O Expansion Jack (compatible with UAG-CX)

UniStream™ controllers of both series

Configuration Examples

Notes:

  1. All examples use the USP-104-B10 10.4″ HMI panel.
  2. The amount of modules in all examples relate to Uni-I/O modules. Uni-I/O modules can be mixed with Uni-I/O Wide modules, considering that 1 Uni-I/O Wide module equals 1½ Uni-I/O module.

Configuring for maximum I/Os

The maximum number of I/O modules that can be connected to a single UniStream™ controller using Uni-I/O modules and 5 Local I/O Expansion adapters with power supplies is achieved by chaining: CPU I/O → UAG-XKPxxxx (up to 5 units) → UAG-XKPxxxx (up to 16 units) → UAG-XKPxxxx (up to 16 units) → UAG-XKL (Long-range Kit) → UAG-XKPxxxx (up to 16 units) → UAG-XKPxxxx (up to 16 units).

Configurations with Short-range adapter, no Power Supply (UAG-XKxxxx)

If UAG-XKxxxx is the only adapter connected to the controller, the system can support up to 8 modules. This configuration is: CPU I/O → UAG-XKxxxx (up to 5 units) → UAG-XKxxxx (up to 8 units).

If a UAG-XKxxxx follows another adapter with an integrated power supply, the support capacity of that powered module limits the number of Uni-I/Os that can be connected to the UAG-XKxxxx; in any event, no more than 8 Uni-I/Os can follow a UAG-XKxxxx adapter. This configuration is: UAG-XKPxxx / UAG-CX-XKPxxx / UAG-XKLxxxx (up to 16 units) → UAG-XKxxxx (up to 8 units).

Daisy-chaining Configuration Summary

The tables below show the possible configurations between two cabinets.

Optional configurations in the cabinet with the UniStream Controller (DIN-rail CPU)

1st2ndMax. Modules
On Board--5
XK-8
XKP-21
CPUXKPXK21
XKXKP24
XKPXKP37

Optional configurations in the other cabinet (DIN-rail CPU)

3rd4th5thMax. Modules
---16
XK--16
XKP--32
XKLXKPXK-32
XKXKP-32
XKPXKP-48

NOTE: Each combination in the right table can be used with each combination in the left table. They are independent of each other and the total number of I/O modules that are supported is the sum of the two tables (Maximum of 85).

UniStream™ controllers comprising an I/O Expansion Jack

Note that in the case of UniStream™ controllers comprising an I/O Expansion Jack, the UAG-CX-XKPxxx must be used, and it must be the adaptor that is directly connected to the controller.

Optional configurations in the cabinet with the UniStream Controller (I/O Expansion Jack)

1st2ndMax. Modules
--0
-XK16
Controller jackCXXK24
XKP32

Optional configurations in the other cabinet (I/O Expansion Jack)

3rd4th5thMax. Modules
---16
XK--16
XKP--32
XKLXKPXK-32
XKXKP-32
XKPXKP-48

NOTE: The total number of I/O modules that are supported is the sum of the two tables (Maximum of 80).

Environmental

ProtectionIP20, NEMA1
Operating temperature-20°C to 55°C (-4°F to 131°F)
Storage temperature-30°C to 70°C (-22°F to 140°F)
Relative Humidity (RH)5% to 95% (non-condensing)
Operating Altitude2,000 m (6,562 ft)
ShockIEC 60068-2-27, 15G, 11ms duration
VibrationIEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration

Dimensions

DimensionsUAG-XKxxxUAG-XKPxxxUAG-CX-XKPxxxUAG-XKPLxxxx
WeightBase: 65 g (0.14 lb)
End: 142 g (0.31 lb)
Base: 65 g (0.14 lb)
End: 150 g (0.33 lb)
Base: 15 g (0.033 lb)
End: 150 g (0.33 lb)
Base: 64 g (0.14 lb)
End: 92 g (0.2 lb)
SizeRefer to the descriptions below.

Base Unit (UAG-XKxxx, UAG-XKPxxx and UAG-XKPLxxxx)

Base Unit (UAG-CX-XKPxxx)

End Unit

Legal Information

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the foregoing from the market.

All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.

The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.

PDF preview unavailable. Download the PDF instead.

SPEC UAG-XK XKP -XKPLxxxx UAG-CX-XKPxxx-08-17 Cara Levy Adobe PDF Library 10.0

Related Documents

Preview UniStream Local Expansion Adapter Kit Technical Specifications
Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx), covering adapter models, power supply, module support, daisy-chaining rules, configuration examples, environmental conditions, and dimensions.
Preview Unitronics UniStream I/O Expansion Adapter Kits Technical Specifications
Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx), covering models, power supply, module support, daisy-chaining rules, configuration examples, environmental conditions, and dimensions for expanding UniStream I/O capabilities.
Preview UniStream Expansion Adapter Kit Technical Specifications
Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits for Uni-I/O, including models, power supply, cable lengths, LED indications, daisy-chaining rules, configuration examples, environmental specifications, and dimensions.
Preview Spécifications Techniques des Kits d'Adaptateurs d'Extension UniStream Unitronics
Découvrez les spécifications techniques détaillées des kits d'adaptateurs d'extension court et longue distance Unitronics UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx et UAG-XKPLxxxx pour les systèmes UniStream, incluant les modèles, l'alimentation, les longueurs de câble et les configurations en cascade.
Preview 7" dotykový TFT LCD panel UniStream™ s CANbus, RS485 a USB
7" dotykový TFT LCD panel UniStream™ s rozlišením 800x480 (154,08 x 85,92mm), vybavený 2x Ethernet, 2x USB, mikro USB a slotem pro SD kartu. Objednací kód: U-USP-070-B08.
Preview Système d'Automatisation Modulaire UniStream® - IHM et API
Découvrez les systèmes UniStream® d'Unitronics, des solutions IHM et API modulaires et extensibles. Caractéristiques, spécifications techniques et options de communication pour les modèles 7", 10.4" et 15.6".
Preview Unitronics PLC и HMI: Полный каталог продукции для автоматизации
Обзор продукции Unitronics, включая серии UniStream, Vision, Samba и Jazz. Узнайте о программируемых логических контроллерах (ПЛК) и человеко-машинных интерфейсах (HMI), их возможностях, технических характеристиках и программном обеспечении UniLogic.
Preview Unitronics EU Declaration of Conformity for Programmable Controllers and HMIs
Official EU Declaration of Conformity from Unitronics GmbH for their range of programmable controllers and HMI panels, detailing compliance with LVD, EMC, and RoHS directives.