This guide provides specifications for Unitronics' Short Range and Long Range Local Expansion Adapter Kit for Uni-I/O™.
The Short and Long Range Local Expansion Adapter Kits allow you to increase the number of I/Os connected to a single UniStream™ by linking it to an additional row of Uni-I/O™ modules.
All Local Expansion Adapter Kits comprise a Base unit, an End unit, and a connecting cable.
Note that there are two adapter series:
Compatible with UniStream® controller panels that comprise a DIN-rail type structure on the panel rear. The Base unit of a UAG-XK
series adapter snaps onto it.
Compatible with UniStream® controllers that comprise an I/O Expansion Jack. The base unit of UAG-CK
series adapter plugs into it.
Model | Install via | Integrated Power Supply | Number of supported modules |
---|---|---|---|
UAG-XKxxx | Panel (DIN-rail structure) | No | 8, including modules installed on the panel |
UAG-XKPxxx | Yes | 16, in addition to any modules installed on the panel | |
UAG-XKPLxxx | Yes | ||
UAG-CX-XKPxxx | Controller (Jack) | Yes | 16 |
UniStream controller panels + CPU-for-Panel can supply power to a maximum of 8 modules, Uni-I/O™ and/or Uni-COM™, with power. Adapters that do not have a power supply draw power from UniStream and supply it to the modules. This means, for example, that if there are 3 modules snapped onto the panel, you can add an additional 5 via this type of adapter.
Adapters with integrated power supply must be connected to a 24VDC power source. The adapter can then supply up to 16 modules with power, regardless of any mounted on the panel.
Installation Guides are available in the Unitronics Technical Library at www.unitronics.com.
The number of modules in the next table includes:
Note that:
The Base and End Units of the Short-range and Long-range models look similar but are not interchangeable; do not mix between them.
The number of modules in the next table refers only to the modules connected to the adaptor.
These controllers lack the DIN-rail structure, and cannot be installed with Uni-COM or Uni-I/O.
UAG-XKxxx | UAG-XKPxxx , UAG-CX-XKPxxx | UAG-XKPLxxxx | |
---|---|---|---|
Supported Modules | Up to 8 modules | Up to 16 modules | Up to 16 modules |
UAG-XKxxx | UAG-XKPxxx , UAG-CX-XKPxxx | UAG-XKPLxxxx | |
---|---|---|---|
Input voltage | Not applicable | 12 or 24 VDC | 12 or 24 VDC |
Permissible range | Not applicable | 10.2 to 28.8 VDC | 10.2 to 28.8 VDC |
Max. current consumption | Not applicable | 0.9@12VDC, 0.5A@24VDC | 0.9@12VDC, 0.5A@24VDC |
Module | Length |
---|---|
UAG-XK125 | 125cm (49") |
UAG-XKP125 | 125cm (49") |
UAG-CX-XKP125 | 125cm (49") |
UAG-XK300 | 300cm (118″) |
UAG-XKP300 | 300cm (118″) |
UAG-CX-XKP300 | 300cm (118") |
UAG-XKPL600 | 600cm (20') |
UAG-XKPL1200 | 1200cm (40') |
UAG-XKPL1500 | 1500cm (50′) |
UAG-XKPL2000 | 2000cm (66') |
UAG-XKPL3000 | 3000cm (98') |
Green | Output state | Comment | |
---|---|---|---|
Base Unit | There are no LEDs in the Base Unit. | ||
End Unit | Off | Cable is not connected or no power from the Base unit | |
UAG-XKxxx | Link | On | Link with the base unit has been established |
Off | No external power | ||
UAG-XKPxxx | Power | On | External power is connected to the unit |
UAG-CX-XKPxxx | Off | Cable is not connected or no power from the Base unit | |
UAG-XKPLxxxx | Link | On | Link with the base unit has been established |
Up to five Local Expansion Adapters may be chained to each other. The maximum number of I/O modules that can be connected to a single controller is:
UniStream can be expanded locally in a single cabinet, using Short range Adapters of up to 3 meters each (UAG-XKxxxx
, UAG-XKPxxxx
and UAG-CX-XKPxxxx
).
It can also be expanded further to another cabinet, using the Long Range Expansion Adapter (UAG-XKLxxxx
).
In order to connect a UniStream™ controller to more than one row of I/O modules via Local I/O Expansion adapters, the following rules must be followed:
UAG-XKPxxxx
(that include an integrated power-supply), or one UAG-XKPxxxx
and one UAG-XKxxxx
.UAG-CX-XKPxxx
must be plugged into the jack, and may be followed by a UAG-XKPxxxx
or one UAG-XKxxxx
.UAG-XKPxxxx
, or one UAG-XKPxxxx
and one UAG-XKxxxx
.Notes:
USP-104-B10 10.4″ HMI
panel.The maximum number of I/O modules that can be connected to a single UniStream™ controller using Uni-I/O modules and 5 Local I/O Expansion adapters with power supplies is achieved by chaining: CPU I/O → UAG-XKPxxxx
(up to 5 units) → UAG-XKPxxxx
(up to 16 units) → UAG-XKPxxxx
(up to 16 units) → UAG-XKL
(Long-range Kit) → UAG-XKPxxxx
(up to 16 units) → UAG-XKPxxxx
(up to 16 units).
If UAG-XKxxxx
is the only adapter connected to the controller, the system can support up to 8 modules. This configuration is: CPU I/O → UAG-XKxxxx
(up to 5 units) → UAG-XKxxxx
(up to 8 units).
If a UAG-XKxxxx
follows another adapter with an integrated power supply, the support capacity of that powered module limits the number of Uni-I/Os that can be connected to the UAG-XKxxxx
; in any event, no more than 8 Uni-I/Os can follow a UAG-XKxxxx
adapter. This configuration is: UAG-XKPxxx
/ UAG-CX-XKPxxx
/ UAG-XKLxxxx
(up to 16 units) → UAG-XKxxxx
(up to 8 units).
The tables below show the possible configurations between two cabinets.
1st | 2nd | Max. Modules | |
---|---|---|---|
On Board | - | - | 5 |
XK | - | 8 | |
XKP | - | 21 | |
CPU | XKP | XK | 21 |
XK | XKP | 24 | |
XKP | XKP | 37 |
3rd | 4th | 5th | Max. Modules | |
---|---|---|---|---|
- | - | - | 16 | |
XK | - | - | 16 | |
XKP | - | - | 32 | |
XKL | XKP | XK | - | 32 |
XK | XKP | - | 32 | |
XKP | XKP | - | 48 |
NOTE: Each combination in the right table can be used with each combination in the left table. They are independent of each other and the total number of I/O modules that are supported is the sum of the two tables (Maximum of 85).
Note that in the case of UniStream™ controllers comprising an I/O Expansion Jack, the UAG-CX-XKPxxx
must be used, and it must be the adaptor that is directly connected to the controller.
1st | 2nd | Max. Modules | |
---|---|---|---|
- | - | 0 | |
- | XK | 16 | |
Controller jack | CX | XK | 24 |
XKP | 32 |
3rd | 4th | 5th | Max. Modules | |
---|---|---|---|---|
- | - | - | 16 | |
XK | - | - | 16 | |
XKP | - | - | 32 | |
XKL | XKP | XK | - | 32 |
XK | XKP | - | 32 | |
XKP | XKP | - | 48 |
NOTE: The total number of I/O modules that are supported is the sum of the two tables (Maximum of 80).
Protection | IP20, NEMA1 |
Operating temperature | -20°C to 55°C (-4°F to 131°F) |
Storage temperature | -30°C to 70°C (-22°F to 140°F) |
Relative Humidity (RH) | 5% to 95% (non-condensing) |
Operating Altitude | 2,000 m (6,562 ft) |
Shock | IEC 60068-2-27, 15G, 11ms duration |
Vibration | IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration |
Dimensions | UAG-XKxxx | UAG-XKPxxx | UAG-CX-XKPxxx | UAG-XKPLxxxx |
---|---|---|---|---|
Weight | Base: 65 g (0.14 lb) End: 142 g (0.31 lb) | Base: 65 g (0.14 lb) End: 150 g (0.33 lb) | Base: 15 g (0.033 lb) End: 150 g (0.33 lb) | Base: 64 g (0.14 lb) End: 92 g (0.2 lb) |
Size | Refer to the descriptions below. |
UAG-XKxxx
, UAG-XKPxxx
and UAG-XKPLxxxx
)UAG-CX-XKPxxx
)The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the foregoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
![]() |
UniStream Local Expansion Adapter Kit Technical Specifications Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx), covering adapter models, power supply, module support, daisy-chaining rules, configuration examples, environmental conditions, and dimensions. |
![]() |
Unitronics UniStream I/O Expansion Adapter Kits Technical Specifications Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits (UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx, UAG-XKPLxxxx), covering models, power supply, module support, daisy-chaining rules, configuration examples, environmental conditions, and dimensions for expanding UniStream I/O capabilities. |
![]() |
UniStream Expansion Adapter Kit Technical Specifications Detailed technical specifications for Unitronics UniStream Short Range and Long Range Local Expansion Adapter Kits for Uni-I/O, including models, power supply, cable lengths, LED indications, daisy-chaining rules, configuration examples, environmental specifications, and dimensions. |
![]() |
Spécifications Techniques des Kits d'Adaptateurs d'Extension UniStream Unitronics Découvrez les spécifications techniques détaillées des kits d'adaptateurs d'extension court et longue distance Unitronics UAG-XKxxx, UAG-XKPxxx, UAG-CX-XKPxxx et UAG-XKPLxxxx pour les systèmes UniStream, incluant les modèles, l'alimentation, les longueurs de câble et les configurations en cascade. |
![]() |
7" dotykový TFT LCD panel UniStream™ s CANbus, RS485 a USB 7" dotykový TFT LCD panel UniStream™ s rozlišením 800x480 (154,08 x 85,92mm), vybavený 2x Ethernet, 2x USB, mikro USB a slotem pro SD kartu. Objednací kód: U-USP-070-B08. |
![]() |
Système d'Automatisation Modulaire UniStream® - IHM et API Découvrez les systèmes UniStream® d'Unitronics, des solutions IHM et API modulaires et extensibles. Caractéristiques, spécifications techniques et options de communication pour les modèles 7", 10.4" et 15.6". |
![]() |
Unitronics PLC и HMI: Полный каталог продукции для автоматизации Обзор продукции Unitronics, включая серии UniStream, Vision, Samba и Jazz. Узнайте о программируемых логических контроллерах (ПЛК) и человеко-машинных интерфейсах (HMI), их возможностях, технических характеристиках и программном обеспечении UniLogic. |
![]() |
Unitronics EU Declaration of Conformity for Programmable Controllers and HMIs Official EU Declaration of Conformity from Unitronics GmbH for their range of programmable controllers and HMI panels, detailing compliance with LVD, EMC, and RoHS directives. |