Empowering you to work smarter

NAVAC Logo

NAVAC NR7 Recovery Unit

User Manual

Important Safety Information:

Failure to follow warnings may result in death or serious injury. Keep this manual for future reference.

General Safety Measures:

Notice:

Instructions for Use:

  1. Connect the power supply. The rocker switch should be in the "-" position. The indicator light will illuminate for 2 seconds and then turn off. Press the "ON" button for more than 0.2s and release to start the device. After a pause of more than 0.5s, press the "OFF" button for more than 0.2s and release to turn off the device. After a pause of more than 2s, press the "ON" button to start the device.
  2. Do not mix different refrigerants in the same tank, as they cannot be separated or utilized.
  3. Before recovering refrigerant, the tank must reach a vacuum level of -29.6inHg to purge non-condensable gases. Each tank is filled with nitrogen at the factory; therefore, the nitrogen must be evacuated before first use.
  4. The knob must be in the "CLOSE" position before operation. All valves must be closed, and the inlet/outlet fittings must be covered with protective caps when the unit is not in use. Air or moisture is detrimental to recovery results and will shorten the unit's lifespan.
  5. Always use a filter drier and replace it regularly. Each type of refrigerant requires its own filter. Use the specified high-quality filter drier to ensure normal unit operation. A high-quality filter drier will help protect the machine.
  6. Special caution is needed when recovering from the system, requiring two filter driers.
  7. The unit has an internal high-pressure protector. If the system pressure exceeds the rated disconnection pressure (see specifications), the compressor will automatically shut off, and the HP CUT indicator will display. To restart the compressor, lower the internal pressure (so the outlet gauge reads less than 35 bar/507.6 PSI). After the HP CUT flashes, press the "START" button to restart the compressor. When high-pressure protection is activated, determine the cause and solution before restarting the unit.
  8. The refrigerant tank's liquid shut-off valve is closed: opening the valve will help resolve the issue.
  9. The connection hose between the recovery unit and the refrigerant tank is blocked: close all valves and replace the connection hose.
  10. The refrigerant tank temperature is too high, causing high pressure; cool the tank.
  11. The unit is equipped with an O.F.P. port and can be connected to a cylinder with liquid-filled output protection using the O.F.P. connection cable. When the O.F.P. cable is not plugged in, the unit automatically blocks the O.F.P. function.
  12. When recovering a large amount of liquid refrigerant, it is recommended to use the "push/pull" mode.
  13. To ensure no refrigerant remains in the equipment after recovery, carefully read the "self-purge" operating procedure in this manual. Residual liquid refrigerant in the condenser can expand and damage components.
  14. The low-pressure gauge on this unit indicates the compressor inlet pressure, and the high-pressure gauge indicates the outlet pressure.
  15. After using the equipment, turn the knob back to the "CLOSE" position.

Specifications:

NR7 R22 R134a R410A
Refrigerants Category III: R-12, R-134a, R-1234YF, R-401C, R-406A, R-500
Category IV: R-22, R-401A, R-401B, R-402B, R-407C, R-407D, R-408A, R-409A, R-502, R-509
Category V: R-143A, R-32, R-402A, R-404A, R-407A, R-407B, R-410A, R-454B, R-507
0.58 lbs/min 0.47 lbs/min 0.54 lbs/min
Power 115V, 60Hz
Motor Brushless motor, 1 HP
Motor speed 3000 RPM
Max current consumption 12A
Compressor Piston, oil-less, air-cooled
High-pressure protector 38.5 bar
Operating temperature 32~104°F
Dimensions 12.2"x9.4"x9.6"
Net weight 20.3 lbs
Flow rate
Direct vapor 9 lbs/min 8 lbs/min 12 lbs/min 12 lbs/min
Direct liquid

Flow Rate vs. Inlet Pressure:

Flow Rate vs. Inlet Pressure Diagram
The vapor flow rate is proportional to the inlet pressure.

Control Panel Introduction:

Control Panel Diagram
  • Overload: Overload warning.
  • O.F.P Cutoff: Illuminates when the recovery cylinder is 80% full, or if the O.F.P. cable is short-circuited. The machine will stop operating.
  • HP Cutoff: Illuminates when the high-pressure switch activates above 560 Psi.
  • CLOSE: Inlet valve closed.
  • Recovery: Inlet valve partially open.
  • FAST: Inlet valve fully open.
  • PURGE: Inlet valve closed, outlet valve open, to recover refrigerant from the system.

Parts Diagram:

Parts Diagram
NO.Part NameNO.Part Name
1Left side panel13Fan blade cover
2Start switch14Fan blade
3Rocker switch15Right side panel
4O.F.P. port16Knob
5Power supply17Duct
6Condenser18Control assembly
7Top panel19Motor control board
8Rear panel20Base
9Inlet duct21Inlet pressure gauge
10Outlet duct22Outlet pressure gauge
11Compressor23Indicator board
12Motor24Front side panel

Wiring Diagram:

Wiring Diagram
Graphic CodeComponent
HSHigh-pressure sensor
MMotor
MCBMotor control board
XSPlug
DCBIndicator board
LSLow-pressure sensor
OFPOverfill protector
TPTemperature protector
HPHigh-pressure switch
TSTemperature sensor
PSStart/stop switch
RSRocker switch
L1High-pressure alarm indicator
L2Liquid fill alarm indicator
L3Overload alarm indicator

Operating Instructions:

Step A: Evacuation Hose

Evacuation Hose Diagram
  1. Connect the hoses firmly as shown in the diagram.
  2. Confirm that the vapor and liquid valves of the air conditioning system are in the closed position.
  3. Confirm that the vapor and liquid valves of the recovery tank are in the closed position.
  4. Open the vapor and liquid valves of the manifold gauge.
  5. Loosen the refrigerant tank connection hoses.
  6. Open the check valve of the hoses.
  7. Plug in the machine and turn it on.
  8. Turn the knob to "FAST".
  9. Press the "ON" button to start the machine, beginning to pump air into the hose.
  10. Observe the low-pressure gauge; the needle should be in the range of "-76cmHg~0" for 30s.
  11. Turn the knob to "CLOSE", then slowly turn it to "PURGE" to start purging.
  12. Observe the low-pressure gauge; the needle should be in the range of "-76cmHg~0" for 30s.
  13. Connect the refrigerant hose to the tank.
  14. Turn the knob to "CLOSE".
  15. Press "ON" to stop the recovery machine.

Step B: Recovery Mode

Notice: An electric scale is needed to monitor the recovery process and prevent overfilling.

Recovery Mode Diagram
  1. Connect the hoses firmly as shown in the diagram.
  2. Ensure all valves are closed.
  3. Open the vapor and liquid valves of the refrigerant system.
  4. Open the vapor valve of the refrigerant tank.
  5. Turn the knob to "FAST".
  6. Slightly loosen the hose connector attached to the tank to extract air from the inside, then immediately tighten the connector.
  7. Close the vapor valve of the manifold gauge.
  8. Open the corresponding tank connection (vapor recovery to liquid port, liquid recovery to vapor port).
  9. Press the "ON" button to start the machine.
  10. If recovering liquid refrigerant, open the liquid valve of the manifold gauge.
  11. If recovering refrigerant vapor, open the vapor valve of the manifold gauge.
  12. Run until the desired vacuum level is reached to complete the recovery. Once reached, turn the knob to purge to initiate the purge process.

Notice: If a surge occurs during recovery, slowly turn the knob to the "SLOW" position, then the low-pressure gauge reading will decrease until the surge stops; however, do not let the pressure reading drop to zero, otherwise the inlet port will not pump once at zero pressure.

If it is difficult to start, turn to "CLOSE" when it is liquid, turn to "PURGE" when it is vapor, then press "ON" to restart the machine, and turn to the desired position.

Step C: Purge Mode

Notice: The unit must be purged after each use. Residual liquid refrigerant can expand, damage components, and contaminate the environment.

Purge Mode Diagram
  1. Once the desired vacuum level is reached, turn the knob to "PURGE" and begin purging.
  2. Observe the low-pressure gauge and let it run until the desired vacuum level is reached.
  3. Press the "ON" button to stop the recovery machine.
  4. Close the tank's vapor valve.
  5. Disconnect the outlet hoses. (Note: residual refrigerant remains in the hose)
  6. Turn the knob to "Close".
  7. Turn off the power switch. Disconnect the power cord.
  8. Disconnect all hoses.

Step D: Push/Pull Liquid Mode

Notice: An electric scale is needed to monitor the recovery process and prevent overfilling.

Push/Pull Liquid Mode Diagram
  1. Connect the hoses firmly as shown in the diagram.
  2. Ensure all valves are closed.
  3. First, evacuate the air from the recovery machine: loosen the outlet hose, turn on the recovery machine, turn the knob to "FAST", then turn the knob to "PURGE", and turn off the recovery machine.
  4. Open the vapor valve of the air conditioning system, quickly release some refrigerant, and tighten the outlet hose.
  5. Open the liquid valve of the air conditioning system, slightly loosen the liquid hose connected to the tank, quickly release some refrigerant, and tighten it again.
  6. Open the vapor valve and liquid valve of the tank.
  7. Turn the knob to "FAST".
  8. Press the "ON" button to start the recovery machine.
  9. After recovering the liquid, slowly turn the knob to "PURGE" to initiate the purge mode.
  10. Close the vapor valve and liquid valve of the air conditioning system.
  11. Close the vapor valve and liquid valve of the tank.
  12. Reconnect and connect all hoses for STEP B - Recovery Mode.
  13. Turn the knob to "Close".

Troubleshooting:

PROBLEMCAUSESOLUTION
No power, indicator light does not respond1. Power cord is damaged.
2. Internal connection is loose.
3. Connection to J1 is damaged.
4. Malfunction of the circuit board.
1. Replace the cable.
2. Check the connection.
3. Replace the connection.
4. Replace the MCB or DCN circuit board. Contact NAVAC technical service.
Machine does not operate after pressing the start switch1. The button was not held for more than 0.3s.
2. High-pressure protection switch is faulty, HP light is on.
3. OFP switch is off and OFP light is on.
4. Overload light is on.
5. Button is damaged.
6. Circuit board is damaged.
1. Press the button again.
2. Check if the high-pressure switch connection is correct.
3. Check if the OFP switch connection is correct.
4.1. Check if the input voltage is correct.
4.2. Check if the connection between TS and MCB is correct.
4.3. Check if the connection between TP and DCB is correct.
4.4. Check if the connection between PS and DCB is correct.
4.5. Also error in vacuum, power failure, such as inability to rotate the impeller, it is a mechanical jam, return to the factory for repair; if it can rotate, replace the control board.
4.6. With load, turn the liquid recovery knob to "CLOSE", turn the gas knob to "PURGE", and then press the button to start the equipment.
5. Replace the button.
6. Replace the circuit board and contact NAVAC technical service.
Machine stops after operating for a period of time1. Malfunction causes the high-pressure switch to operate, turning on the high-pressure light.
2. Thermal protector action, overload lamp lights up.
3. Refrigerant is at 80% in the tank, and O.F.P. Cutoff is displayed.
1. Refer to the USER MANUAL.
2. When the switch resets and the overload light flashes, you can restart the unit.
3. Replace the tank. When O.F.P Cutoff and Restart flash, press the Start switch.
Slow recovery rate1. Refrigerant tank pressure is too high.
2. Valve opening is too small.
3. Compressor piston ring is damaged.
1. Cooling the tank helps reduce pressure.
2. Turn the knob to "FAST".
3. Contact NAVAC technical service.
Does not evacuate1. Connection hose is loose.
2. Machine has leaks.
1. Tighten the connection hoses.
2. Contact NAVAC technical service.

Correct Disposal of this Product:

This symbol indicates that this product should not be disposed of with other household waste. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. Contact the retailer where you purchased the product. They can take this product for environmentally safe recycling.

PDF preview unavailable. Download the PDF instead.

NR7-User-Manual-17-24 iLovePDF

Related Documents

Preview NAVAC NR7 Recovery Unit User Manual
User manual for the NAVAC NR7 recovery unit, detailing its specifications, operation, safety precautions, and troubleshooting.
Preview NAVAC NRDC4M Refrigerant Recovery Unit User Manual
Comprehensive user manual for the NAVAC NRDC4M Refrigerant Recovery Unit, detailing safety precautions, operation procedures, specifications, parts identification, wiring diagrams, and troubleshooting for HVAC/R technicians. Includes version information.
Preview NAVAC Counter Day at Geary Pacific Supply
Join Geary Pacific Supply for a NAVAC Counter Day event featuring NAVAC vacuum pumps, recovery units, manifold gauges, and tube benders. Learn about the latest HVAC tools and technology.
Preview NAVAC Summer Slam Promotion: Deals on HVAC Tools
Discover NAVAC's Summer Slam Promotion, offering free tools with qualifying purchases of PowerT3 tools, NEXUS gauges, and recovery units. Valid from August 1st to September 30th, 2025.
Preview NAVAC Flex72 N2D72 Digital Manifold Gauge User Manual
User manual for the NAVAC Flex72 Manifold Gauge with Digital Display (N2D72). Provides comprehensive guidance on setup, operation, maintenance, and troubleshooting for HVAC professionals.
Preview NAVAC NTE11L BreakFree Tube Expander User Manual
User manual for the NAVAC NTE11L BreakFree Tube Expander, providing instructions on operation, safety, maintenance, and technical specifications.
Preview NAVAC NSH1 Bluetooth Psychrometer User Manual
Comprehensive user manual for the NAVAC NSH1 Bluetooth Psychrometer with Digital Display, detailing safety precautions, product features, technical specifications, operation, and app integration.
Preview NAVAC NX1 NX1V Nexus Digital Manifold Gauge User Manual
User manual for the NAVAC NX1 and NX1V Nexus Digital Manifold Gauge, covering product overview, technical specifications, operation modes, safety information, and app connectivity.