NAVAC NR7 Recovery Unit User Manual

Empowering you to work smarter

Table of Contents

General Safety

Information Usage: To extend the service life of the recovery unit, please read the manual carefully before use to fully understand safety, specifications, and operating procedures.

! Warning: This mark indicates procedures that must be strictly observed to prevent risks to people.

Note: This mark indicates procedures that must be strictly followed to avoid damage or destruction of the unit.

General Safety Precautions:

Notes on Usage:

User Manual

  1. Connect the power supply. The toggle switch is in the "-" position, and the indicator light is on for 2 seconds then off. Press and hold the "<0xF0><0x9F><0x94><0x8B>" button for more than 0.2 seconds and release to start the unit. After an interval of more than 0.5s, press and hold the "<0xF0><0x9F><0x94><0x8B>" button for more than 0.2 seconds and release to shut down the unit. After an interval of more than 2 seconds, press the "<0xF0><0x9F><0x94><0x8B>" button to start the unit.
  2. Do not mix different refrigerants in the same tank, as they cannot be separated or reused.
  3. Before recovering refrigerant, the tank must reach a vacuum level of -29.6 inches of mercury to purge non-condensable gases. Each tank is filled with nitrogen at the factory; therefore, evacuate the nitrogen before first use.
  4. The knob must be in the "CLOSED" position before operation. All valves must be closed, and inlet/outlet connections should be protected with dust caps when the unit is not in operation. Air/moisture are detrimental to recovery results and will shorten the unit's lifespan.
  5. A desiccant filter must always be used and replaced regularly. Each type of refrigerant requires its own filter. To ensure proper unit performance, use a specified high-quality desiccant filter. A high-quality desiccant filter will help protect the machine.
  6. Special attention is required when recovering from the system, and two desiccant filters are necessary.
  7. The unit is equipped with an internal high-pressure protector. If the system pressure exceeds the rated cutoff pressure (refer to specifications), the compressor will automatically shut down, and "HP CUTOFF" will be displayed. To restart the compressor, reduce the internal pressure (outlet gauge shows pressure below 35 bar/507.6 PSI), and after the HP CUTOFF flashes, press the "START" button to restart the compressor. When the high-pressure protection is triggered, determine the cause and rectify it before restarting the unit.
    • The refrigerant tank inlet valve is closed - opening the valve will help resolve the issue.
    • The connection hose between the recovery unit and the refrigerant tank is blocked - close all valves and replace the connection hose.
    • The refrigerant tank temperature is too high, causing high pressure - cool the tank.
  8. The unit is equipped with an O.F.P. port and can be connected to a cylinder with a complete liquid shut-off using the O.F.P. cable. When the O.F.P. cable is not plugged in, the unit automatically blocks the O.F.P. function.
  9. When recovering a large amount of liquid refrigerant, the "push-pull" mode is recommended.
  10. To ensure no refrigerant remains in the equipment after recovery, carefully read the "self-purge procedure" in this manual. Residual liquid refrigerant in the condenser can expand and damage components.
  11. The low-pressure gauge on this equipment indicates the pressure at the compressor inlet within the recovery machine; the high-pressure gauge indicates the pressure at the outlet.
  12. After using the equipment, turn the knob to the "CLOSED" position.

Specifications

Specification NR7
Refrigerants Category III: R-12, R-134a, R-1234YF, R-401C, R-406A, R-500
Category IV: R-22, R-401A, R-401B, R-402B, R-407C, R-407D, R-408A, R-409A, R-502, R-509
Category V: R-143A, R-32, R-402A, R-404A, R-407A, R-407B, R-410A, R-454B, R-507
Power Supply 115V, 60Hz
Motor Brushless motor, 1 HP
Motor Speed 3000 rpm
Max Current Draw 12A
Compressor Oil-free, air-cooled, piston
High Pressure Protector 38.5 bar
Operating Temperature 32~104°F
Dimensions 12.2" x 9.4" x 9.6"
Net Weight 20.3 lbs

Flow Rate (lb/min)

Refrigerant R22 R134a R410A
Direct Vapor 0.58 lbs/min 0.47 lbs/min 0.54 lbs/min
Direct Liquid 9 lbs/min 8 lbs/min 12 lbs/min

Flow Rate vs. Inlet Pressure

Graph showing the relationship between vapor flow rate and inlet pressure for the NR7 unit.

Note: Vapor flow rate is proportional to inlet pressure.

Control Panel Introduction

Start-up Switch: Start/stop the unit. Press and hold for 0.3 seconds to start, press again after 2 seconds to stop.

Parts Diagram

Exploded view of the NAVAC NR7 recovery unit, showing all components with corresponding numbers.

List of parts:

Electrical Diagram

Schematic of the electrical connections for the NAVAC NR7 recovery unit, showing components like MCB, motor, switches, and indicators.

Component Key:

Operating Instructions

Step A: Hose Evacuation

Follow the diagram for proper hose connection.

  1. Ensure system and recovery tank vapor and liquid valves are closed.
  2. Open the collector gauge vapor and liquid valves.
  3. Loosen the refrigerant tank connection hoses.
  4. Open the hose control valve.
  5. Connect the power and turn on the unit.
  6. Turn the knob to "FAST".
  7. Press the "<0xF0><0x9F><0x94><0x8B>" button to start the unit and begin pumping air from the hose.
  8. Observe the low-pressure gauge; the needle should be between "-76 cmHg to 0" for 30s.
  9. Turn the knob to "CLOSED", then slowly to "PURGE" to remove remaining air.
  10. Observe the low-pressure gauge; the needle should be between "-76 cmHg to 0" for 30s.
  11. Connect the refrigerant hose to the tank.
  12. Turn the knob to "CLOSED".
  13. Press the "<0xF0><0x9F><0x94><0x8B>" button to stop the recovery machine.

Step B: Recovery Mode

Note: An electric scale is necessary to monitor the recovery process and prevent overfilling.

Connect hoses firmly as shown in the diagram.

  1. Open the system's vapor and liquid valves.
  2. Open the collector gauge's vapor valve.
  3. Turn the knob to "FAST".
  4. Slightly loosen the tank connection hose to vent air, then immediately tighten the connection.
  5. Close the collector gauge's vapor valve.
  6. Open the corresponding tank connection (vapor recovery to liquid port, liquid recovery to vapor port).
  7. Press the "<0xF0><0x9F><0x94><0x8B>" switch to start the unit.
  8. If recovering liquid refrigerant, open the collector gauge's liquid valve.
  9. If recovering vapor refrigerant, open the collector gauge's vapor valve.
  10. Run until the desired vacuum level is reached. Then, turn the knob to "PURGE" to start the purge process.

Note: If slugging occurs during recovery, slowly turn the knob to "SLOW" and monitor the low-pressure gauge until slugging stops. Do not let the reading pressure drop to zero, as the inlet port will not pump once pressure reaches zero.

If starting is difficult, turn the knob to "CLOSED" when handling liquid, turn to "PURGE" when handling vapor, then press "<0xF0><0x9F><0x94><0x8B>" to restart the machine and turn it to the required position.

Step C: PURGE Mode

Note: The unit must be purged after each use. Residual refrigerant can expand, damage components, and pollute the environment.

  1. Once the desired vacuum level is reached, turn the knob to "PURGE" and begin purging.
  2. Observe the low-pressure gauge; let it run until the desired vacuum level is achieved.
  3. Press the "<0xF0><0x9F><0x94><0x8B>" switch to stop the recovery machine.
  4. Close the tank's vapor valve.
  5. Disconnect the outlet hoses. (Note: residual refrigerant remains in the hose)
  6. Turn the knob to "CLOSED".
  7. Turn off the power switch. Disconnect the power cord.
  8. Disconnect all hoses.

Liquid Push-Pull Mode

Note: An electric scale is necessary to control the recovery process and prevent overfilling.

Connect hoses firmly as shown in the diagram. Ensure all valves are closed.

First, evacuate air from the recovery machine: loosen the outlet hose, turn on the recovery machine, turn the knob to "FAST", then turn the knob to "PURGE", turn off the recovery machine.

  1. Open the system's vapor valve, rapidly release some refrigerant, and tighten the outlet hose.
  2. Open the system's liquid valve, slightly loosen the liquid hose connected to the tank, rapidly release some refrigerant, and retighten it.
  3. Open the tank's vapor and liquid valves.
  4. Turn the knob to "FAST".
  5. Press the "<0xF0><0x9F><0x94><0x8B>" button to start the recovery machine.
  6. Once liquid is recovered, slowly turn the knob to "PURGE" to start purging.
  7. Close the system's vapor and liquid valves.
  8. Close the tank's vapor and liquid valves.
  9. Disconnect and reconnect all hoses for Step B - Recovery Mode.
  10. Turn the knob to "CLOSED".

Troubleshooting

Problem Cause Solution
Unit powers on, but no indicator light response 1. Power cord is damaged.
2. Internal connection is loose.
3. J1 connection is damaged.
4. Circuit board malfunction.
1. Replace cord.
2. Check connection.
3. Replace connection.
4. Replace MCB or DCN board. Contact NAVAC technical support.
Machine does not operate after pressing the start switch 1. The button was not held for more than 0.3s.
2. High-pressure protection switch is faulty, HP light is on.
3. OFP switch is off, OFP light is on.
4. Overload lamp is on.
5. Button is damaged.
6. Circuit board is damaged.
1. Press the button again.
2. Test the high-pressure switch connection.
3. Test the OFP switch connection.
4.1. Check input voltage.
4.2. Check TS and MCB connection.
4.3. Check TP and DCB connection.
4.4. Check PS and DCB connection.
4.5. If no load, power failure (fan blade cannot rotate), it's a mechanical blockage: return to factory for repair; if it can rotate, replace the control board.
4.6. Under load, turn the liquid recovery knob to "CLOSED", turn the gas knob to "PURGE", then press the button to start the unit.
5. Replace the button.
6. Replace the circuit board and contact NAVAC technical support.
Machine stops after a period of operation due to improper handling causing high-pressure switch trip. 1. Improper handling causes the high-pressure switch to trip, HP light is on.
2. Thermal protector trips, overload lamp is on.
3. Tank is filled to 80% refrigerant, and OFP cutoff is displayed.
1. Please read the USER MANUAL carefully.
2. When the switch is reset and the overload light flashes, you can restart the unit.
3. Replace the tank. When OFP cutoff and restart flash, press the start switch.
Slow recovery rate 1. Refrigerant tank pressure is too high.
2. Valve opening is too small.
3. Compressor piston ring is damaged.
1. Cool the tank to reduce pressure.
2. Turn the knob to "FAST".
3. Contact NAVAC technical support.
No evacuation 1. Connection hose is loose.
2. Machine is leaking.
1. Tighten connection hoses.
2. Contact NAVAC technical support.

Correct Disposal of this Product:

This marking indicates that this product should not be disposed of with other household wastes. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmentally safe recycling.

PDF preview unavailable. Download the PDF instead.

NR7-User-Manual-9-16 iLovePDF

Related Documents

Preview NAVAC NR7 Recovery Unit User Manual
Comprehensive user manual for the NAVAC NR7 Recovery Unit, detailing safety measures, operating instructions, specifications, and troubleshooting for HVAC and refrigeration system service.
Preview NAVAC Counter Day at Geary Pacific Supply
Join Geary Pacific Supply for a NAVAC Counter Day event featuring NAVAC vacuum pumps, recovery units, manifold gauges, and tube benders. Learn about the latest HVAC tools and technology.
Preview NAVAC Summer Slam Promotion: Deals on HVAC Tools
Discover NAVAC's Summer Slam Promotion, offering free tools with qualifying purchases of PowerT3 tools, NEXUS gauges, and recovery units. Valid from August 1st to September 30th, 2025.
Preview NAVAC Flex72 N2D72 Digital Manifold Gauge User Manual
User manual for the NAVAC Flex72 Manifold Gauge with Digital Display (N2D72). Provides comprehensive guidance on setup, operation, maintenance, and troubleshooting for HVAC professionals.
Preview NAVAC NTE11L BreakFree Tube Expander User Manual
User manual for the NAVAC NTE11L BreakFree Tube Expander, providing instructions on operation, safety, maintenance, and technical specifications.
Preview NAVAC NX1 NX1V Nexus Digital Manifold Gauge User Manual
User manual for the NAVAC NX1 and NX1V Nexus Digital Manifold Gauge, covering product overview, technical specifications, operation modes, safety information, and app connectivity.
Preview NAVAC NTB7L BreakFree Power Tube Bender User Manual
Comprehensive user manual for the NAVAC NTB7L BreakFree Power Tube Bender, detailing safety guidelines, parts diagrams, technical specifications, operating instructions, troubleshooting, and charging procedures.
Preview NAVAC NEF6LM BreakFree® Electric Flaring Tool User Manual
User manual for the NAVAC NEF6LM BreakFree® electric flaring tool, covering structure, operating instructions, troubleshooting, and detailed parts list.