Trane Product Data

Split System Cooling

The following Trane split system cooling units are detailed in this document:

Note: Graphics in this document are for representation only. Actual models may differ in appearance.

Document Number: 22-1916-1E-EN
Publication Date: January 2017

Product Specifications

The following tables detail the specifications for the Trane Split System Cooling units.

Model No. (a)POWER CONNS. - V/PH/HZ (b)MIN. BRCH. CIR. AMPACITYBR. CIR. PROT. RTG. MAX. (AMPS)COMPRESSORRL AMPS - LR AMPSOutdoor Fan FL AMPSFan HPFan Dia (inches)CoilRefrigerant R-410ALINE SIZE - IN. O.D. GAS (c)LINE SIZE - IN. O.D. LIQ.Charge Spec. SubcoolingDimensions H x W X D Crated (IN.)Weight - Shipping (lbs.)Weight - Net (lbs.)
4TTR6018J1000A208/230/1/601220CLIMATUFF®- SCROLL9 - 47.50.641/823.02 - 1SPINE FIN™4 LBS., 15 OZ3/43/88°F34 x 30.1 x 33189161
4TTR6024J1000B208/230/1/601320CLIMATUFF®- SCROLL10.1 - 520.641/823.02SPINE FIN™5 LBS., 3 OZ3/43/88°F34 x 30.1 x 33190162
4TTR6030J1000A208/230/1/601725CLIMATUFF®- SCROLL12.8 - 67.80.641/823.02SPINE FIN™6 LBS., 7 OZ3/43/88°F42 x 30.1 x 33220184
4TTR6036J1000A208/230/1/601830CLIMATUFF®- SCROLL13.6 - 790.771/824SPINE FIN™7 LBS., 11 OZ7/83/88°F42 x 35.1 x 38.7246212
4TTR6042J1000A208/230/1/602135CLIMATUFF®- SCROLL16.7 - 1090.641/827.5SPINE FIN™8 LBS., 10 OZ7/83/88°F50.4 x 35.1 x 38.7302252
4TTR6048J1000A208/230/1/602440CLIMATUFF®- SCROLL18.5 - 1240.931/527.5SPINE FIN™8 LBS., 10 OZ7/83/88°F50.4 x 35.1 x 38.7306256
4TTR6049J1000A208/230/1/602640CLIMATUFF®- SCROLL18.5 - 1242.801/327.5SPINE FIN™10 LBS., 3 OZ7/83/810°F50.4 x 35.1 x 38.7322272
4TTR6060J1000A208/230/1/603250CLIMATUFF®- SCROLL23.7 - 152.51.051/527.5SPINE FIN™9 LBS., 13 OZ1-1/83/810°F50.4 x 35.1 x 38.7327277
4TTR6061C1000A208/230/1/603250CLIMATUFF®- SCROLL23.7 - 152.51.051/527.6SPINE FIN™10 LBS., 15 OZ1-1/83/810°F50.4 x 35.1 x 38.7327277
Model No. (a)Optional Accessories: Anti-short Cycle TimerEvaporator Defrost ControlRubber Isolator KitExtreme Condition Mount KitStart KitCrankcase Heater KitSeacoast KitLow Ambient KitRefrigerant Lineset (d)Service Valve Panel Cover
4TTR6018J1000ATAYASCT501AAY28X079BAYISLT101BAYECMT023BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN7*TAYSVPANL0032AA
4TTR6024J1000BTAYASCT501AAY28X079BAYISLT101BAYECMT023BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN7*TAYSVPANL0032AA
4TTR6030J1000ATAYASCT501AAY28X079BAYISLT101BAYECMT023BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN7*TAYSVPANL0044AA
4TTR6036J1000ATAYASCT501AAY28X079BAYISLT101BAYECMT004BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN3*TAYSVPANL0044AA
4TTR6042J1000ATAYASCT501AAY28X079BAYISLT101BAYECMT004BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN3*TAYSVPANL0046AA
4TTR6048J1000ATAYASCT501AAY28X079BAYISLT101BAYECMT004BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN3*TAYSVPANL0046AA
4TTR6049J1000ATAYASCT501AAY28X079BAYISLT101BAYECMT004BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN3*TAYSVPANL0046AA
4TTR6060J1000ATAYASCT501AAY28X079BAYISLT101BAYECMT004BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN3*TAYSVPANL0046AA
4TTR6061C1000ATAYASCT501AAY28X079BAYISLT101BAYECMT004BAYKSKT263BAYCCHT302BAYSEAC001BAYLOAM103TAYREFLN3*TAYSVPANL0046AA

Notes:
(a) Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard 210/240.
(b) Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
(c) Standard line lengths - 60', Standard lift - 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0* (* denotes latest revision).
(d) * = 15, 20, 25, 30, 40 and 50 foot lineset available.

Sound Power Level

Sound power levels for the Trane split system cooling units, rated in accordance with AHRI Standard 270-2008.

MODELA-Weighted Sound Power Level [dB(A)]Full Octave Sound Power (dB)
63 Hz*125 Hz250 Hz500 Hz1000 Hz2000 Hz4000 Hz8000 Hz
4TTR6018J737969677070645953
4TTR6024J737969677070645953
4TTR6030J737969677070645953
4TTR6036J717872696866615853
4TTR6042J728175717068635853
4TTR6048J728175717068635853
4TTR6049J728175717068635853
4TTR6060J728175717068635853
4TTR6061C746856637369645951

Note: Rated in accordance with AHRI Standard 270-2008. *For Reference Only.

Accessory Description and Usage

AHRI Standard Capacity Rating Conditions

AHRI Standard 210/240 Rating Conditions

  1. Cooling: 80°F DB, 67°F WB air entering indoor coil; 95°F DB air entering outdoor coil.
  2. High Temperature Heating: 47°F DB, 43°F WB air entering outdoor coil; 70°F DB air entering indoor coil.
  3. Low Temperature Heating: 17°F DB air entering indoor coil.
  4. Rated indoor airflow for heating is the same as for cooling.

AHRI Standard 270 Rating Conditions

(Noise rating numbers are determined with the unit in cooling operations.) Standard Noise Rating number is at 95°F outdoor air.

Model Nomenclature

The model number provides specific information about the unit. For example, the model number 4TWV0036A1000AA breaks down as follows:

Other elements in the nomenclature indicate:

Schematic Diagrams

The document includes electrical schematic diagrams for different model series:

Outline Drawing

The outline drawing provides physical dimensions and connection points for the outdoor units. The table below details these dimensions (labeled A through K) for each model.

Diagram Description: The drawing shows a typical outdoor unit with a top-mounted fan. It indicates clearances for the service panel, electrical, and refrigerant components. It also highlights the location of the electrical service panel, low voltage K.O., and gas/liquid line service valve connections.

ModelBaseABCDEFGHJK
4TTR6018J3730 (28-3/4)829 (32-5/8)756 (29-3/4)3/43/8127 (5)76 (3)197 (7-3/4)60 (2-3/8)508 (20)
4TTR6024J3730 (28-3/4)829 (32-5/8)756 (29-3/4)3/43/8127 (5)76 (3)197 (7-3/4)60 (2-3/8)508 (20)
4TTR6030J3933 (36-3/4)829 (32-5/8)756 (29-3/4)3/43/8143 (5-5/8)92 (3-5/8)210 (8-1/4)79 (3-1/8)508 (20)
4TTR6036J4943 (37-1/8)946 (37-1/4)870 (34-1/4)3/43/8143 (5-5/8)98 (3-7/8)219 (8-5/8)86 (3-3/8)508 (20)
4TTR6042J41147 (45-1/8)946 (37-1/4)870 (34-1/4)7/83/8152 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)813 (32)
4TTR6048J41147 (45-1/8)946 (37-1/4)870 (34-1/4)7/83/8152 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)813 (32)
4TTR6049J41147 (45-1/8)946 (37-1/4)870 (34-1/4)7/83/8152 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)813 (32)
4TTR6060J41147 (45-1/8)946 (37-1/4)870 (34-1/4)7/83/8152 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)813 (32)
4TTR6061C41147 (45-1/8)946 (37-1/4)870 (34-1/4)7/83/8152 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)813 (32)

Mechanical Specification Options

General

The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.

Casing

Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint finish on all louvered panels and the fan top panel. The corner panels are prepainted. All panels are subjected to our 1,000 hour salt spray test. The base is made of a CMBP-G30 weatherproof material to resist corrosion.

Refrigerant Controls

Refrigeration system controls include condenser fan, compressor contactor, and high pressure switch. High and low pressure controls are inherent to the compressor. A factory supplied liquid line drier is standard. Some models may require field installation.

Compressor

The compressor features internal over temperature, pressure protection, and a total dipped hermetic motor. Other features include: Centrifugal oil pump and low vibration and noise.

Condenser Coil

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.

Low Ambient Cooling

As manufactured, this system has a cooling capacity to 55°F. The addition of an evaporator defrost control permits operation to 40°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30°F.

Thermostats

Cooling only and heat/cooling (manual and automatic change over). Sub-base to match thermostat and locking thermostat cover.

Evaporator Defrost Control

See Low Ambient Cooling.

PDF preview unavailable. Download the PDF instead.

22-1916-1E-EN 01272017 PDFlib PDI 9.0.3p4 (C /Win64)

Related Documents

Preview Trane 4TWA4000A Series Split System Heat Pump Product Data
Comprehensive product data for Trane 4TWA4000A series split system heat pumps, including detailed specifications for 208-230V and 460V models, accessory descriptions, model nomenclature, and sound power levels. Learn about Trane's reliable heat pump technology.
Preview Trane XB 1000 Split System Cooling Product Data
This document provides comprehensive product data, features, specifications, and ratings for the Trane XB 1000 series of split system cooling units. It includes detailed information on models such as TTB012C100A, TTB018C100A, TTB024C100A, TTB030C100A, TTB036C100A, TTB042C100A, TTB048C100A, and TTB060C100B, covering general data, electrical specifications, dimensions, and mechanical options.
Preview Trane Split System Air Conditioner Product Data and Specifications
Comprehensive product data and technical specifications for Trane 3-Phase Split System Air Conditioners, including models 5TTA3036A, 5TTA3042A, 5TTA3048A, and 5TTA3060A. This document provides detailed specifications, accessory descriptions, sound power levels, wiring diagrams, and outline drawings for 208/230V and 460V units.
Preview Trane XR17 4 Ton Split System Cooling - Product Data and Specifications
Detailed product data, features, benefits, specifications, dimensions, and model nomenclature for the Trane XR17 4 Ton Split System Cooling unit (Model 4TTR7048B). Includes technical details, electrical schematics, and mechanical specifications.
Preview Trane Split System Cooling Product Data and Specifications
Detailed product data, specifications, schematic diagrams, and mechanical options for Trane's 4TTR series split system cooling units, manufactured by Ingersoll Rand.
Preview Trane Split System Heat Pump Product Data
Comprehensive product data for Trane Split System Heat Pumps, including 208-230V and 460V models (4TWA4036A, 4TWA4042A, 4TWA4048A, 4TWA4060A series). Features detailed specifications, accessory descriptions, model nomenclature, schematics, outline drawings, and mechanical specifications.
Preview Trane Split System Air Conditioner Product & Submittal Data | 5TTA4036A-5TTA4060A
Comprehensive product and submittal data for Trane 3-Phase Split System Air Conditioners (208/230V & 460V), including detailed specifications, sound power levels, dimensions, accessories, and mechanical options.
Preview Trane 4MXW/4MYW Inverter Ductless Mini-Split Air Conditioners - High Efficiency
Discover the Trane 4MXW/4MYW series of high-efficiency inverter ductless mini-split air conditioners, offering up to 23 SEER, advanced Wi-Fi control, superior indoor air quality features, and quiet operation for optimal comfort in residential and commercial spaces.