Trane Split System Heat Pump Product Data

Model Series: 4TWA4036A, 4TWA4042A, 4TWA4048A, 4TWA4060A

Product Specifications

208-230V Models

Outdoor Unit (a)4TWA4036A3000A4TWA4042A3000A4TWA4048A3000A4TWA4060A3000A
Power Conns. - V/Ph/Hz208-230/3/60208-230/3/60208-230/3/60208-230/3/60
Min. Brch. Cir. Ampacity (b)13181821
Br. Cir. Prot. Rtg. - Max. (Amps)20303035
CompressorCLIMATUFF®- SCROLLCLIMATUFF®- SCROLLCLIMATUFF®- SCROLLCLIMATUFF®- SCROLL
R.L. Amps - L.R. Amps9.9 - 7013.5 - 8813.7 - 83.115.9 - 110
Outdoor Fan Dia. (in.) - No. UsedPROPELLER 27.6 - 1PROPELLER 27.6 - 1PROPELLER 27.6 - 1PROPELLER 27.6 - 1
No. Motors - HP1 - 1/81 - 1/51 - 1/51 - 1/5
F.L. Amps0.81.11.11.1
Outdoor Coil - TypeSPINE FIN™SPINE FIN™SPINE FIN™SPINE FIN™
Refrigerant Lbs. - R-410A (O.D. Unit)7 LBS., 1 OZ7 LBS., 8 OZ8 LBS., 2 OZ10 LBS., 9 OZ
Line Size - In. O.D. Gas (c)7/87/87/81-1/8
Line Size - In. O.D. Liq. (d)3/83/83/83/8
Charging Specifications Subcooling10°F10°F10°F8°F
Dimensions Crated (in.)H X W X D 34.4 x 38.7 x 35.1H X W X D 34.4 x 38.7 x 35.1H X W X D 38.4 x 38.7 x 35.1H X W X D 51 x 38.7 x 35.1
Weight Shipping (Lbs.)240240252325
Net (Lbs.)208208218275
Optional Accessories:
Anti-short Cycle TimerTAYASCT501ATAYASCT501ATAYASCT501ATAYASCT501A
Evaporator Defrost ControlAY28X084AY28X084AY28X084AY28X084
Rubber Isolator KitBAYISLT101BAYISLT101BAYISLT101BAYISLT101
Extreme Condition Mount KitBAYECMT004BAYECMT004BAYECMT004BAYECMT004
Seacoast KitBAYSEAC001BAYSEAC001BAYSEAC001BAYSEAC001
Low Ambient KitBAYLOAM107BAYLOAM107BAYLOAM107BAYLOAM107
Refrigerant Lineset (e)TAYREFLN3*TAYREFLN3*TAYREFLN3*TAYREFLN3*
Sound EnclosureBAYSDEN004BAYSDEN004BAYSDEN004BAYSDEN004
Service Valve Panel CoverTAYSVPANL3343AATAYSVPANL3343AATAYSVPANL0046AATAYSVPANL0032AA

Notes:

  1. Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which is based on AHRI standard 210/240.
  2. Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
  3. Reference the outdoor unit ship-with literature for refrigerant piping length and lift guidelines. Reference the refrigerant piping software pub #32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denotes latest revision).
  4. Outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit and 15 feet of tested connecting lines. If connecting line length exceeds 15 feet, then final refrigerant charge adjustment is necessary. Each additional foot over 15 feet requires 0.6 ozs of refrigerant. See the Installer's Guide for full charging instructions.
  5. * = 15, 20, 25, 30, 40 and 50 foot lineset available.

460V Models

Outdoor Unit (a)4TWA4036A4000A4TWA4042A4000A4TWA4048A4000A4TWA4060A4000A
Power Conns. - V/Ph/Hz460/3/60460/3/60460/3/60460/3/60
Min. Brch. Cir. Ampacity (b)6889
Br. Cir. Prot. Rtg. - Max. (Amps)15151515
CompressorCLIMATUFF®- SCROLLCLIMATUFF®- SCROLLCLIMATUFF®- SCROLLCLIMATUFF®- SCROLL
R.L. Amps - L.R. Amps4.3-316-446.2-417.1-52
Outdoor Fan Dia. (in.) - No. UsedPROPELLER 27.6 - 1PROPELLER 27.6 - 1PROPELLER 27.6 - 1PROPELLER 27.6 - 1
No. Motors - HP1 - 1/81 - 1/51 - 1/51 - 1/5
F.L. Amps0.40.60.60.6
Outdoor Coil - TypeSPINE FIN™SPINE FIN™SPINE FIN™SPINE FIN™
Refrigerant Lbs. - R-410A (O.D. Unit)7 LBS., 1 OZ7 LBS., 8 OZ8 LBS., 2 OZ10 LBS., 9 OZ
Line Size - In. O.D. Gas (c)7/87/87/81-1/8
Line Size - In. O.D. Liq. (d)3/83/83/83/8
Charging Specifications Subcooling10°F10°F10°F8°F
Dimensions Crated (in.)H X W X D 34.4 x 38.7 x 35.1H X W X D 34.4 x 38.7 x 35.1H X W X D 38.4 x 38.7 x 35.1H X W X D 51 x 38.7 x 35.1
Weight Shipping (Lbs.)240240252324
Net (Lbs.)208208218274
Optional Accessories:
Anti-short Cycle TimerTAYASCT501ATAYASCT501ATAYASCT501ATAYASCT501A
Evaporator Defrost ControlAY28X084AY28X084AY28X084AY28X084
Rubber Isolator KitBAYISLT101BAYISLT101BAYISLT101BAYISLT101
Extreme Condition Mount KitBAYECMT004BAYECMT004BAYECMT004BAYECMT004
Seacoast KitBAYSEAC001BAYSEAC001BAYSEAC001BAYSEAC001
Low Ambient KitBAYLOAM107BAYLOAM107BAYLOAM107BAYLOAM107
Refrigerant Lineset (e)TAYREFLN3*TAYREFLN3*TAYREFLN3*TAYREFLN3*
Sound EnclosureBAYSDEN004BAYSDEN004BAYSDEN004BAYSDEN004
Service Valve Panel CoverTAYSVPANL3343AATAYSVPANL3343AATAYSVPANL0046AATAYSVPANL0032AA

Notes:

  1. Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which is based on AHRI standard 210/240.
  2. Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
  3. Reference the outdoor unit ship-with literature for refrigerant piping length and lift guidelines. Reference the refrigerant piping software pub #32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denotes latest revision).
  4. Outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit and 15 feet of tested connecting lines. If connecting line length exceeds 15 feet, then final refrigerant charge adjustment is necessary. Each additional foot over 15 feet requires 0.6 ozs of refrigerant. See the Installer's Guide for full charging instructions.
  5. * = 15, 20, 25, 30, 40 and 50 foot lineset available.

Sound Power Level

ModelA-Weighted Sound Power Level [dB(A)]Full Octave Sound Power (dB)
63 Hz*125 Hz250 Hz500 Hz1000 Hz2000 Hz4000 Hz8000 Hz
4TWA4036A3757272716970625752
4TWA4042A3748574686969635854
4TWA4048A3748574686969635854
4TWA4060A3748574686969635854
4TWA4036A4757272716970625752
4TWA4042A4748574686969635854
4TWA4048A4748574686969635854
4TWA4060A4748574686969635854

Accessory Description and Usage

Anti-Short Cycle Timer

Solid state timing device that prevents compressor recycling until five (5) minutes have elapsed after satisfying call or power interruptions. Use in areas with questionable power delivery, commercial applications, or long linesets.

Evaporation Defrost Control

SPST Temperature actuated switch that cycles the condenser off as indoor coil reaches freeze-up conditions. Used for low ambient cooling to 30°F with TXV.

Rubber Isolators

Five (5) large rubber donuts to isolate condensing unit from transmitting energy into mounting frame or pad. Use on any application where sound transmission needs to be minimized.

Extreme Condition Mount Kit

Bracket kits to securely mount condensing unit to a frame or pad without removing any panels. Use in areas with high winds, or on commercial roof tops.

AHRI Standard Capacity Rating Conditions

AHRI Standard 210/240 Rating Conditions:

  1. Cooling: 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil.
  2. High Temperature Heating: 47°F DB, 43°F WB air entering indoor coil, 70°F DB air entering indoor coil.
  3. Low Temperature Heating: 17°F DB air entering outdoor coil.
  4. Rated indoor airflow for heating is the same as for cooling.

AHRI Standard 270 Rating Conditions

Noise rating numbers are determined with the unit in cooling operations. Standard Noise Rating number is at 95°F outdoor air.

Model Nomenclature

The model number for Trane Outdoor Units follows a specific structure:

4 T W V 0 0 3 6 A 1 0 0 0 A A

  • Position 1: Refrigerant Type
    • 2 = R-22
    • 4 = R-410A
  • Positions 2-5: TRANE Product Type
    • TW = Split Heat Pump
    • TT = Split Cooling
  • Position 6: Product Family
    • V = Variable Speed
    • Z = Leadership - Two Stage
    • X = Leadership
    • R = Replacement/Retail
  • Position 7: Family SEER
    • 3=13, 4=14, 5=15, 6=16, 8=18, 9=19
  • Position 8: Split System Connections 1-6 Tons
    • 0 = Brazed
  • Positions 9-10: Nominal Capacity in 000s of BTUs
  • Position 11: Major Design Modifications
    • A = Light Commercial
    • M or B = Basic
    • L = Side Discharge
  • Position 12: Power Supply
    • 1 = 200-230/1/60 or 208-230/1/60
    • 3 = 200-230/3/60
    • 4 = 460/3/60
  • Position 13: Secondary Function
  • Position 14: Minor Design Modifications
  • Position 15: Unit Parts Identifier

Electrical Schematic (3.5, 4.0 & 5.0 Ton 460V Models)

This section provides a detailed electrical schematic for Trane 3.5, 4.0, and 5.0 Ton 460V Split System Heat Pumps. The diagram illustrates the power supply connections, internal wiring, and control circuits.

Legend:

  • 24V Factory Wiring: Solid line with circle.
  • 24V Field Wiring: Dashed line with circle.
  • Field Installed: Dashed line.
  • Factory Wiring: Solid line.
  • Terminal Block/Board: Square with 'TB'.
  • Relay Contact (N.O.): Open contact symbol.
  • Relay Contact (N.C.): Closed contact symbol.
  • Thermistor: Resistor with diagonal line.
  • Motor Winding: Coil symbol.
  • Magnetic Coil: Coil symbol.
  • Ground: Ground symbol (three horizontal lines decreasing in length).
  • Junction: Dot.
  • Capacitor: Two parallel lines.
  • Wire Nut or Terminal: Triangle.
  • Fuse: Rectangle with line through it.

Component Abbreviations:

  • ACR: A/C Rectifier
  • CBS: Coil Bottom Sensor
  • CF: Fan Capacitor
  • CN: Wire Connector
  • CPR: Compressor
  • CR: Run Capacitor
  • CS: Starting Capacitor
  • CSR: Capacitor Switching Relay
  • DFC: Defrost Control
  • EEV: Electronic Exp Valve
  • EEVC: Electronic Exp Valve Control
  • IFR: Indoor Fan Relay
  • HPCO: High Pressure Cutout Switch
  • IOL: Internal Overload Protector
  • LPCO: Low Pressure Cutout Switch
  • MCC: Compressor Motor Contactor
  • ODA: Outdoor Anticipator
  • ODF: Outdoor Fan Relay
  • OFT: Outdoor Fan Thermostat
  • ODS: Outdoor Temperature Sensor
  • ODT: Outdoor Thermostat
  • P-TRD: Pressure Transducer
  • SC: Switch Over Valve Solenoid
  • SHR: Sump Heater Relay
  • SM: System On-Off Switch
  • TDL: Discharge Line Thermostat
  • TDR: Time Delay Relay (5 Sec Delay On)
  • TNS: Transformer
  • TS: Temp Sensor, Temperature
  • Y2C: High Capacity Control Relay

Notes:

  1. Ensure power supply agrees with equipment nameplate.
  2. Power wiring and grounding of equipment must comply with local codes.
  3. Low voltage wiring to be No. 18 AWG minimum conductor.
  4. ODT-B must be set lower than ODT-A. If ODT-B is not used, add jumper between W2 and W3 at air handler. If used, ODT-B must be mounted remote of control box in an approved weatherproof enclosure.
  5. If ODT-A is not used, add jumper between W1 and W2 at air handler.

Dimensional Outline Drawing

This section provides the outline drawing and critical dimensions for the Trane Split System Heat Pumps. The unit features a top discharge area that should be unrestricted for at least 1524 mm (5 feet) above the unit. The unit should be placed so roof run-off water does not pour directly on it, and should be at least 305 mm (12 inches) from walls and all surrounding shrubbery on two sides. The other two sides should remain unrestricted.

Key Dimensions (in millimeters and inches):

  • A: Overall Height
  • B: Overall Width
  • C: Overall Depth
  • D: Gas Line Service Valve Diameter
  • E: Liquid Line Service Valve Diameter
  • F: Distance from front to liquid line service valve
  • G: Distance from side to liquid line service valve
  • H: Distance from base to electrical service panel
  • J: Distance from base to low voltage access
  • K: Electrical Service Panel width

The drawing also indicates a 22.2 mm (7/8 inch) diameter hole for low voltage and a 28.6 mm (1-1/8 inch) diameter knockout with a 22.2 mm (7/8 inch) diameter hole in the control box bottom for electrical power supply. There is also a knockout for alternate electrical routing.

ModelBaseABCDEFGHJK
4TWA4036A34741 (29-1/8)946 (37-1/4)870 (34-1/4)3/43/8143 (5-5/8)83 (3-1/4)206 (8-1/8)70 (2-3/4)508 (20)
4TWA4042A34741 (29-1/8)946 (37-1/4)870 (34-1/4)3/43/8143 (5-5/8)83 (3-1/4)206 (8-1/8)70 (2-3/4)508 (20)
4TWA4048A34841 (33-1/8)946 (37-1/4)870 (34-1/4)3/43/8156 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)508 (20)
4TWA4060A341147 (45-1/8)946 (37-1/4)870 (34-1/4)7/83/8152 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)813 (32)
4TWA4036A44741 (29-1/8)946 (37-1/4)870 (34-1/4)7/83/8143 (5-5/8)83 (3-1/4)206 (8-1/8)70 (2-3/4)508 (20)
4TWA4042A44741 (29-1/8)946 (37-1/4)870 (34-1/4)3/43/8143 (5-5/8)83 (3-1/4)206 (8-1/8)70 (2-3/4)508 (20)
4TWA4048A44841 (33-1/8)946 (37-1/4)870 (34-1/4)3/43/8156 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)508 (20)
4TWA4060A441147 (45-1/8)946 (37-1/4)870 (34-1/4)7/83/8152 (6)98 (3-7/8)219 (8-5/8)86 (3-3/8)813 (32)

Mechanical Specification Options

General

The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.

Casing

Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint finish. The corner panels are prepainted. All panels are subjected to a 1,000 hour salt spray test.

Refrigerant Controls

Refrigeration system controls include condenser fan, compressor contactor and low and high pressure switches. A factory supplied, field installed liquid line drier is standard.

Compressor

The compressor features internal over temperature and pressure protection. Other features include: Centrifugal oil pump and low vibration and noise.

Condenser Coil

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.

Low Ambient Cooling

As manufactured, this system has a cooling capacity to 55°F. The addition of an evaporator defrost control permits operation to 40°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30°F. The addition of the BAYLOAM107A low ambient kit permits ambient cooling to 20°F.

Thermostats

Cooling only and heat/cooling (manual and automatic change over) thermostats are available. Sub-base to match thermostat and locking thermostat cover.

PDF preview unavailable. Download the PDF instead.

22-1929-1C-EN 03182019 PDFlib PDI 9.0.6 (C /Win64)

Related Documents

Preview Trane 4TWA4000A Series Split System Heat Pump Product Data
Comprehensive product data for Trane 4TWA4000A series split system heat pumps, including detailed specifications for 208-230V and 460V models, accessory descriptions, model nomenclature, and sound power levels. Learn about Trane's reliable heat pump technology.
Preview Trane Split System Heat Pump Product Data and Specifications
Detailed product data and specifications for Trane's Split System Heat Pumps, including model numbers, electrical requirements, compressor details, dimensions, and optional accessories. This document provides technical information for various Trane heat pump models.
Preview Trane Horizon Outdoor Air Unit Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane Horizon Outdoor Air Units, including Water Source Heat Pump models OABE, OADE, OAGE, OAKE, and OANE. Covers safety, procedures, and technical details.
Preview Trane 4TWR Series Split System Heat Pump Product Data and Specifications
Detailed product data, specifications, sound power levels, outline drawings, and mechanical options for Trane 4TWR Series Split System Heat Pumps.
Preview Trane E4HL5036A1000A Split System Heat Pump Specifications and Outline Drawing
Detailed specifications, outline drawings, and mechanical options for the Trane E4HL5036A1000A split system heat pump. Includes dimensions, sound power levels, electrical data, refrigerant details, and operational capabilities. Certified by AHRI and UL.
Preview Trane Single Packaged Heat Pump, Priority, Two Stage, Convertible, 2-5 Ton, R-454B Product Data and Specifications
Comprehensive product data, specifications, optional equipment, and safety information for Trane's 2-5 Ton Single Packaged Heat Pump systems (R-454B). Details include model numbers (5WCZ5024-5WCZ5060), performance metrics, mechanical features, installation clearances, and available accessories for commercial and residential applications.
Preview Trane R-410A Split Wall System Installation Manual
This manual provides detailed installation instructions for the Trane R-410A Split Wall System, covering indoor and outdoor unit setup, electrical connections, refrigerant piping, drainage, and final checks. It includes safety precautions and operational guidance for various modes.
Preview Trane 4TWR6048H1000A Split System Heat Pump Service Facts
This document provides service facts, safety warnings, product specifications, wiring diagrams, refrigerant charging procedures, defrost control information, troubleshooting guides, and pressure curves for the Trane 4TWR6048H1000A Split System Heat Pump.