Model | Current | Voltage, Frequency |
---|---|---|
KSS | 40-600 amps | 208-600 VAC, 50/60 Hz |
KSS | 800-1000 amps | 208-480 VAC, 50/60 Hz |
The ATS meets or exceeds the requirements of the following specifications:
Model | Switch Rating, Amps | Range of Wire Sizes, Copper or Aluminum* | ||
---|---|---|---|---|
Normal, Emergency, and Load | Neutral | Ground | ||
KSS | 40-150 | (1) #8 to 3/0 AWG † | (3) #6 - 3/0 AWG | (3) #6 - 3/0 AWG |
KSS | 200-225 | (1) #6 AWG to 250 KCMIL† | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL | (3) #6 - 3/0 AWG |
KSS | 260 | (1) #6 AWG to 350 KCMIL† | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL |
KSS | 400 | (1) #4 AWG to 600 KCMIL† or (2) #1/0 AWG to 250 KCMIL† | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL |
KSS | 600 | (2) #2 AWG to 600 KCMIL† | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL |
KSS | 800 | (2) #1/0 AWG to 750 KCMIL | (12) #2 - 600 KCMIL | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL |
KSS | 1000 | (4) #2 AWG to 600 KCMIL | (12) #2 - 600 KCMIL | (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL |
* Use 60°C minimum wire for #14 to #1 AWG. Use 75°C minimum wire for 1/0 AWG and larger.
† Use copper wire only.
Contact Type | Resistive Load | Inductive Load | Motor Load | |
---|---|---|---|---|
NC | NO | |||
Engine Start Contacts | 2 A @ 30 VDC | N/A | N/A | N/A |
Auxiliary Contacts, (40-600A)‡ | 15 A @ 250 VAC | N/A | N/A | N/A |
Auxiliary Contacts, (800-1000A) ‡ | 15 A @ 480 VAC | 15 A @ 250 VAC; 6 A @ 500 VAC | 5 A @ 125 VAC; 3 A @ 250 VAC; 1.5 A @ 500 VAC | 2.5 A @ 125 VAC; 1.5 A @ 250 VAC; 0.75 A @ 500 VAC |
‡ Auxiliary position-indicating contacts, one set Normal and one set Emergency
Weights and dimensions are shown for transfer switches in NEMA type 1 and type 3R enclosures, and open units. Consult the factory for open units and other enclosures.
Note: Weights and dimensions are provided for reference only and should not be used for planning installation. See your local distributor for submittal drawings.
Amps | NEMA Type | Dimensions mm (in.) | Weight kg (lb.) | ||||
---|---|---|---|---|---|---|---|
Height | Width | Depth § | 2-Pole | 3-Pole | 4-Pole | ||
40-225 | 1, 3R | 791 (31.1) | 450 (17.7) | 316 (12.5) | 28 (62) | 30 (65) | 31 (68) |
260-400 | 1, 3R | 1223 (48.1) | 560 (22.0) | 362 (14.3) | 52 (115) | 56 (123) | 59 (131) |
600 | 1, 3R | 1702 (67.0) | 610 (24.0) | 514 (20.2) | 179 (395) | 183 (403) | 186 (410) |
800 | 1, 3R | 1932 (76.1) | 864 (34.0) | 515 (20.3) | N/A | 226 (498) | 236 (520) |
1000 | 1, 3R | 1932 (76.1) | 864 (34.0) | 515 (20.3) | N/A | 231 (509) | 241 (531) |
§ Allow enough room to fully open the door for inspection and service per NEC and local codes. The NEMA type 3R enclosures have a security cover on the controller that extends 54 mm (2.1 in.) beyond the door.
The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical Amperes listed at the specified maximum voltage below, but no greater than the interrupting capacity of the selected circuit breaker or fuse. Circuit breakers and fuses are supplied by the customer.
Switch Rating, Amps | Fuse Class | Fuse Size, Max Amps | With Current-Limiting Fuses | Specific Coordinated Breaker Rating, (see the following tables) | Any Breaker Ratings ** | Time Duration, Seconds Max. | |||
---|---|---|---|---|---|---|---|---|---|
480 VAC | 600 VAC | Maximum Voltage | Maximum Circuit Amps | Maximum Voltage | Maximum Circuit Amps | ||||
40-150 | J | 400 | 200,000 | 200,000 | 600 V | 30,000 / 22,000 | 600 V | 10,000 / 10,000 | 0.025 |
200-225 | J | 400 | 200,000 | N/A | 600 V | 30,000 / 22,000 | 600 V | 10,000 / 10,000 | N/A |
260 | N/A | N/A | N/A | N/A | 480 V | 35,000 | N/A | N/A | N/A |
600 | J | 600 | 200,000 | 200,000 | 600 V | 50,000 / 42,000 | 600 V | 35,000 / 35,000 | 0.050 |
600 | RK5 | 600 | 100,000 | N/A | 600 V | 50,000 / 42,000 | N/A | N/A | N/A |
600 | RK1 | 600 | N/A | N/A | 600 V | 50,000 / 42,000 | N/A | N/A | N/A |
800 | L | 3000 | 200,000 | N/A | 480 V | 65,000 | N/A | N/A | N/A |
1000 | L | 4000 |
* All values are available symmetrical RMS Amperes and tested in accordance with the withstand/closing requirements of UL 1008.
** Applicable to breakers with instantaneous trip elements.
Switch Rating, Amps | Voltage, Max. | WCR, Amps RMS | Manufacturer | Type | Max. Size, Amps |
---|---|---|---|---|---|
40 | 480 | 30,000 | Eaton | FCL | 100 |
40 | 480 | 30,000 | Eaton | JGS, JGH, JGC, JGU, JGX, JBD, JD, HJD, JDC, LCL, LCLA | 250 |
40 | 480 | 30,000 | Eaton | LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD | 400 |
40 | 480 | 30,000 | ITE/Siemens | CED6, HED4, HED6 | 125 |
40 | 480 | 30,000 | ITE/Siemens | CFD6, FD6A, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 | 250 |
40 | 480 | 30,000 | ITE/Siemens | CJD6 | 400 |
40 | 480 | 30,000 | General Electric | SEL, SEP, THLC1 | 150 |
40 | 480 | 30,000 | General Electric | THLC2 | 225 |
40 | 480 | 30,000 | General Electric | SFH, SFL, SFP | 250 |
40 | 480 | 30,000 | General Electric | SGH, SGL, SGP, FGN, FGH, FGL, FGP | 400 |
40 | 480 | 30,000 | Schneider | HG, HJ, HL, HR | 150 |
40 | 480 | 30,000 | Schneider | JJ, JL, JR | 250 |
40 | 480 | 30,000 | Schneider | LG, LJ, LL, LR | 400 |
80 | 480 | 30,000 | Eaton | JGS, JGH, JGC, JGU, JGX, JDB, JD, HJD, JDC, LCL, LCLA | 250 |
80 | 480 | 30,000 | Eaton | LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD | 400 |
80 | 480 | 30,000 | ITE/Siemens | CED6, HED4, HED6 | 125 |
80 | 480 | 30,000 | ITE/Siemens | CFD6, FD6, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 | 250 |
80 | 480 | 30,000 | ITE/Siemens | CJD6 | 400 |
80 | 480 | 30,000 | General Electric | SEL, SEP, THLC1 | 150 |
80 | 480 | 30,000 | General Electric | THLC2 | 225 |
80 | 480 | 30,000 | General Electric | SFH, SFL, SFP | 250 |
80 | 480 | 30,000 | General Electric | SGH, SGL, SGP, FGN, FGH, FGL, FGP | 400 |
100 | 480 | 30,000 | Schneider | HG, HJ, HL, HR | 150 |
100 | 480 | 30,000 | Schneider | JJ, JL, JR | 250 |
100 | 480 | 30,000 | Schneider | LG, LJ, LL, LR | 400 |
150 | 480 | 30,000 | Eaton | JGS, JGH, JGC, JGU, JGX, JDB, JD, HJD, JDC, LCL, LCLA | 250 |
150 | 480 | 30,000 | Eaton | LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD | 400 |
150 | 480 | 30,000 | ITE/Siemens | CED6, HED4, HED6 | 125 |
150 | 480 | 30,000 | ITE/Siemens | CFD6, FD6, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 | 250 |
150 | 480 | 30,000 | ITE/Siemens | CJD6 | 400 |
150 | 480 | 30,000 | General Electric | SEL, SEP, THLC1 | 150 |
150 | 480 | 30,000 | General Electric | THLC2 | 225 |
150 | 480 | 30,000 | General Electric | SFH, SFL, SFP | 250 |
150 | 480 | 30,000 | General Electric | SGH, SGL, SGP, FGN, FGH, FGL, FGP | 400 |
200 | 480 | 30,000 | Schneider | HG, HJ, HL, HR | 150 |
200 | 480 | 30,000 | Schneider | JJ, JL, JR | 250 |
200 | 480 | 30,000 | Schneider | LG, LJ, LL, LR | 400 |
225 | 480 | 30,000 | Eaton | JGS, JGH, JGC, JGU, JGX, JDB, JD, HJD, JDC, LCL, LCLA | 250 |
225 | 480 | 30,000 | Eaton | LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD | 400 |
225 | 480 | 30,000 | ITE/Siemens | CED6, HED4, HED6 | 125 |
225 | 480 | 30,000 | ITE/Siemens | CFD6, FD6, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 | 250 |
225 | 480 | 30,000 | ITE/Siemens | CJD6 | 400 |
225 | 480 | 30,000 | General Electric | SEL, SEP, THLC1 | 150 |
225 | 480 | 30,000 | General Electric | THLC2 | 225 |
225 | 480 | 30,000 | General Electric | SFH, SFL, SFP | 250 |
225 | 480 | 30,000 | General Electric | SGH, SGL, SGP, FGN, FGH, FGL, FGP | 400 |
260 | 480 | 35,000 | Eaton | JGS, JGH, JGC, JGU, JGX, JDB, JD, HJD, JDC, LCL, LCLA | 250 |
260 | 480 | 35,000 | Eaton | LDC, CLDC, LD, CLD, HLD, CHLD, KDB, KD, HKD, KDC | 400 |
260 | 480 | 35,000 | Eaton | CED6, HED4, HHED6 | 125 |
260 | 480 | 35,000 | ITE/Siemens | CFD6, FD6, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 | 250 |
260 | 480 | 35,000 | ITE/Siemens | SEL, SEP, THLC1 | 150 |
260 | 480 | 35,000 | ITE/Siemens | THLC2 | 225 |
260 | 480 | 35,000 | General Electric | SFH, SFL, SFP | 250 |
260 | 480 | 35,000 | General Electric | SGH | 350 |
260 | 480 | 35,000 | General Electric | SGH, SGL, SGP, FGN, FGH, FGL, FGP | 400 |
260 | 480 | 35,000 | Schneider | HG, HJ, HL, HR | 150 |
260 | 480 | 35,000 | Schneider | JJ, JL, JR | 250 |
260 | 480 | 35,000 | Schneider | LG, LJ, LL, LR | 400 |
400 | 480 | 50,000 | Eaton | HJD, JDC, JGC, JGH, JGU, JGX | 250 |
400 | 480 | 50,000 | Eaton | CHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD, CHMDL4, CMDL4 | 400 |
400 | 480 | 50,000 | Eaton | CHLD6, HDL6, CHMDL6, CMDL6, CLDC, CLD6, LDC6, CLDC6 | 600 |
400 | 480 | 50,000 | Eaton | CHMDL8, HMDL8, MDL8, CMDL8 | 800 |
400 | 480 | 50,000 | ITE/Siemens | CFD6, HFD6, HFXD6, HHFD6, HHFXD6 | 250 |
400 | 480 | 50,000 | General Electric | SFL, SFP | 250 |
400 | 480 | 50,000 | General Electric | FGL, FGP | 600 |
400 | 480 | 50,000 | Schneider | LJ, LL, LR | 600 |
400 | 600 | 42,000 | Eaton | JGU, JGX | 250 |
400 | 600 | 42,000 | Eaton | CLDC4, KDC, LDC4 | 400 |
400 | 600 | 42,000 | Eaton | CLDC6, LDC6, NB Tri-Pac | 600 |
400 | 600 | 42,000 | Eaton | NB Tri-Pac | 800 |
400 | 600 | 42,000 | ITE/Siemens | CFD6 | 250 |
400 | 600 | 42,000 | ITE/Siemens | CJD6, SCLD6 | 400 |
400 | 600 | 42,000 | ITE/Siemens | CLD6, HHLD6, HHLXD6, SCLD6 | 600 |
400 | 600 | 42,000 | ITE/Siemens | CMD6, HMD6, HMXD6, SCMD6, SHMD6 | 800 |
400 | 600 | 42,000 | General Electric | THLC1 | 150 |
400 | 600 | 42,000 | General Electric | FGL4, FGP4, THLC4, TLB4 | 400 |
400 | 600 | 42,000 | General Electric | SGL, SGP, FGL6, FGP6 | 600 |
400 | 600 | 42,000 | General Electric | SKL8, SKP8 | 800 |
400 | 600 | 42,000 | Schneider | JL, JR | 250 |
600 | 480 | 50,000 | Eaton | HJD, JDC, JGC, JGH, JGU, JGX | 250 |
600 | 480 | 50,000 | Eaton | CHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD, CHMDL4, CMDL4 | 400 |
600 | 480 | 50,000 | Eaton | CHLD6, HLD6, CHMDL6, CMDL6, CLDC6, LDC6, CLD6, CLDC | 600 |
600 | 480 | 50,000 | Eaton | CHMDL8, HMDL8, MDL8, CMDL8 | 800 |
600 | 480 | 50,000 | ITE/Siemens | CFD6, HFD6, HFXD6, HHFD6, HHFXD6 | 250 |
600 | 480 | 50,000 | General Electric | SFL, SFP | 250 |
600 | 480 | 50,000 | General Electric | FGL, FGP | 600 |
600 | 480 | 50,000 | Schneider | LJ, LL, LR | 600 |
600 | 600 | 42,000 | Eaton | JGU, JGX | 250 |
600 | 600 | 42,000 | Eaton | CLDC4, KDC, LDC4 | 400 |
600 | 600 | 42,000 | Eaton | CLDC6, LDC6, NB Tri-Pac | 600 |
600 | 600 | 42,000 | Eaton | NB Tri-Pac | 800 |
600 | 600 | 42,000 | ITE/Siemens | CFD6 | 250 |
600 | 600 | 42,000 | ITE/Siemens | CJD6, SCLD6 | 400 |
600 | 600 | 42,000 | ITE/Siemens | CLD6, HHLD6, HHLXD6, SCLD6 | 600 |
600 | 600 | 42,000 | ITE/Siemens | CMD6, HMD6, HMXD6, SCMD6, SHMD6 | 800 |
600 | 600 | 42,000 | General Electric | THLC1 | 150 |
600 | 600 | 42,000 | General Electric | FGL4, FGP4, THLC4, TLB4 | 400 |
600 | 600 | 42,000 | General Electric | SGL, SGP, FGL6, FGP6 | 600 |
600 | 600 | 42,000 | General Electric | SKL8, SKP8 | 800 |
600 | 600 | 42,000 | Schneider | JL, JR | 250 |
800 | 480 | 50,000 | Eaton/ Cutler-Hammer | TRI-PAC NB, CHMDL, HMDL, CHND, HND, NDC, CNDC | 800 |
800 | 480 | 50,000 | Eaton/ Cutler-Hammer | TRI-PAC NB, CNDC, NDC, CRDC, TRI-PAC PB, RDC, CHND, HND, RD. CRD | 1200 |
800 | 480 | 50,000 | Schneider/ Square D | MJ, PJ, PL, RJ | 800 |
800 | 480 | 50,000 | Schneider/ Square D | PJ, PL, RL | 1000 |
1000 | 480 | 65,000 | ITE/Siemens | CMD6, HMD6, SCMD6, SHMD6, CND6, HND6, SCND6, SHND6, CPD6 | 800 |
1000 | 480 | 65,000 | ITE/Siemens | CND6, HND6, SCND6, CPD6, SHND6, HPD6 | 1200 |
1000 | 480 | 65,000 | General Electric | TB8, TC, THC, THP | 1000 |
1000 | 480 | 65,000 | General Electric | THC, THP, TRP | 1200 |
Accessories are available either factory-installed or as loose kits, unless otherwise noted.
Certification depends on application and geographic location. Contact your distributor for details.
Surge protection reduces transient voltages to harmless levels.
Nominal Voltage (V ±15%) | Max. Discharge Current (kA) | Phase | Poles | UL VPR 3rd Ed (L-N/N-G/L-G) (kV) | Limiting Voltage, (L-N/N-G/L-G) (kV) | Short Circuit Withstand Current (kA) | Maximum Continuous Operating Voltage (VAC) | ||||
---|---|---|---|---|---|---|---|---|---|---|---|
at 3kA | at 10kA | ||||||||||
240/120 | 40 | Split | 3 | 0.6/1.2/0.7 | 0.6/0.4/0.6 | 0.8/0.7/0.8 | 200 | 175/350 | |||
208/120 | 40 | Wye | 4 | 0.6/1.2/0.7 | 0.6/0.4/0.6 | 0.8/0.7/0.8 | 200 | 175/350 | |||
480/277 | 40 | Wye | 4 | 1.0/1.2/1.1 | 1.0/0.4/1.0 | 1.2/0.7/1.2 | 200 | 320/460 | |||
240/120 | 40 | HLD | 4 | 1.0/1.2/1.1 | 1.0/0.4/1.0 | 1.2/0.7/1.2 | 200 | 320/460 | |||
600/347 | 40 | Wye | 4 | 1.3/1.2/1.4 | 1.3/0.4/1.3 | 1.5/0.7/1.5 | 200 | 440/880 |
See the controller spec sheet for more information.
Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below.
Sample Model Designation: KSS-JCNA-0100S
Note: Some selections are not available for every model. Contact your Kohler distributor for availability.
Kohler, Wisconsin 53044 USA
Phone: 920-457-4441, Fax: 920-459-1646
For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444
7 Jurong Pier Road, Singapore 619159
Phone: (65) 6264-6422, Fax: (65) 6264-6455
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler® Power Systems distributor for availability.
© 2014 by Kohler Co. All rights reserved.
![]() |
Kohler KSS Automatic Transfer Switches: Features, Ratings, and Specifications Comprehensive technical specifications for Kohler KSS Standard Specific-Breaker Rated Automatic Transfer Switches. Details features, controller options (MPAC 750, MPAC 1200), electrical ratings, dimensions, circuit breaker compatibility, accessories, and model designation. |
![]() |
Kohler KSS Automatic Transfer Switch: Features, Ratings, and Specifications Detailed specifications, features, ratings, and accessories for the Kohler KSS series Automatic Transfer Switches. Includes information on controllers, codes, standards, application data, withstand/close-on ratings, and model designation. |
![]() |
Kohler Automatic Transfer Switches for Industrial Power Systems | Product Overview Explore Kohler's comprehensive range of Automatic Transfer Switches (ATS) designed for industrial power systems. This document details system integration, various ATS types, enclosure ratings, transition modes, controller options (MPAC 1200, MPAC 1500), pole and neutral switching, withstand and close-on ratings, load management features, accessories, and global service and support. |
![]() |
Kohler KSSB Series Automatic Transfer Switches: Features, Specifications, and Ratings Detailed datasheet for the Kohler KSSB Series Automatic Transfer Switches, covering features, electrical specifications, controller options, compliance standards, and model designation for industrial and commercial standby power applications. |
![]() |
Kohler KSS Automatic Transfer Switch: Features, Ratings, and Specifications Explore the features, technical specifications, ratings, and model designations for Kohler KSS Automatic Transfer Switches, designed for reliable backup power solutions. |
![]() |
Kohler RDT Automatic Transfer Switch: Features, Specifications, and Model Guide Comprehensive guide to Kohler RDT Series Automatic Transfer Switches (100-400 Amps), detailing features, environmental specifications, contact ratings, time delays, cable sizes, withstand ratings, codes, dimensions, accessories, and model designation. |
![]() |
Kohler Automatic Transfer Switch Product Guide: Configuration and Features Explore the Kohler Automatic Transfer Switch (ATS) product line, including detailed configuration options, Decision-Maker MPAC controller features, and available models. This guide helps select the right ATS for your power needs. |
![]() |
Kohler Automatic Transfer Switches (ATS) Product Guide & Configuration Explore the Kohler Automatic Transfer Switch (ATS) product line, including standard, bypass-isolation, and service-entrance models. Learn about Decision-Maker MPAC controllers and custom configuration options for reliable power transfer. |