THE ATS LINEUP
Peace of mind starts here.
Bridging the gap between loss of utility and standby power is no small task. KOHLER® automatic transfer switches (ATS) are designed to meet that challenge, distributing power to feed the critical loads of your facility.
Every transfer switch needs a controller to ensure transfer of power from utility to generator and back again. KOHLER Decision-Maker® MPAC® controllers offer clear choices in matching function to application.
STANDARD FEATURES
- Multiple Applications: Find the perfect option. KOHLER automatic transfer switches are available in standard, bypass-isolation and service-entrance configurations with open, closed and programmed transition operating modes, from 30 to 4000 amps.
- Seamless System Integration: Everything works together. KOHLER transfer switches are designed to interface perfectly with KOHLER generators and paralleling switchgear.
- Advanced Communications: Every transfer switch comes fully loaded with the technology to do the job. Ethernet and Modbus communications capabilities are available.
- Certified Packages: Transfer switches are UL-listed and have CSA and IBC certifications available.
The document shows images of two large Kohler Automatic Transfer Switch cabinets with digital displays labeled 'KOHLER. Decision-Maker MPAC 1500' and 'KOHLER. Decision-Maker MPAC 1200'. It also shows images of a Standard ATS, a Service-Entrance ATS, and a Bypass-Isolation ATS.
CUSTOM CONFIGURATION
The chart tells the story. You can custom configure switches by choosing the exact components needed. This standard process allows Kohler to provide the correct switch for your application with delivery in the shortest amount of time. Each letter and numeral corresponds to a specific element of the ATS. Here's an example.
Example Configuration Code: KBP-DMVA-0150S
This code represents a Kohler Automatic Transfer Switch (K) with the following configuration:
- Mechanism: Bypass-isolation mechanism (B)
- Transition: Programmed transition (P)
- Controller: Decision-Maker® MPAC® 1500 controller (D)
- Voltage: 480 V, 60 Hz (M)
- Poles/Wires: 4-pole, 4-wire with switched neutral (V)
- Enclosure: NEMA 1 enclosure (A)
- Amps: Rated at 150 amps (0150)
- Connection: Standard connection (S)
An image shows a specific model: KBP-DMVA-0150B.
Configuration Details
Mechanism Options
Code | Description |
---|---|
S | STANDARD (SPECIFIC BREAKER) |
C | STANDARD (TIME BASED) |
B | MECHANICALLY OPERATED BYPASS-ISOLATION |
A | ELECTRICALLY OPERATED BYPASS-ISOLATION |
E | SERVICE ENTRANCE |
Transition Options
Code | Description |
---|---|
S | Standard |
P | Programmed |
C | Closed |
Controller Options
Code | Description |
---|---|
A | MPAC 1200 |
D | MPAC 1500 |
B | MPAC 1200 Nonautomatic |
F | MPAC 1500 Nonautomatic |
Voltage Options
Code | Description |
---|---|
C | 208 V / 60 Hz |
D | 220 V / 50 Hz |
F | 240 V / 60 Hz |
G | 380 V / 50 Hz |
H | 400 V / 50 Hz |
J | 416 V / 50 Hz |
K | 440 V / 60 Hz |
M | 480 V / 60 Hz |
N | 600 V / 60 Hz |
P | 380 V / 60 Hz |
R | 220 V / 60 Hz |
S | 400 V / 60 Hz |
Poles/Wires Options
Code | Description |
---|---|
T | 3-Pole / 4-Wire, Solid Neutral |
N | 2-Pole / 3-Wire, Solid Neutral |
V | 4-Pole / 4-Wire, Switched Neutral |
W | 4-Pole / 4-Wire, Overlapping Neutral |
Enclosure Options
Code | Description |
---|---|
A | NEMA 1 |
B | NEMA 12 |
C | NEMA 3R |
D | NEMA 4 |
F | NEMA 4X |
G | OPEN |
Amps Range
Range |
---|
30-4000 |
Connection Options
Code | Description |
---|---|
S | Standard |
F | Front |
Utility (KEP) Options
Code | Description |
---|---|
M | MCCB TM 100-200 A |
N | MCCB ET 250-800 A |
P | MCCB ET GF 1000-1200 A |
R | ICCB ET 800 A |
T | ICCB ET GF 1000-4000 A |
Generator (KEP) Options
Code | Description |
---|---|
K | MCSW 100-1200 A |
M | MCCB TM 100-200 A |
N | MCCB ET 250-1200 A |
Q | ICSW 800-4000 A |
R | ICCB ET 800-4000 A |
Definitions: MCCB = Molded-Case Circuit Breaker, ICCB = Insulated-Case Circuit Breaker, MCSW = Molded-Case Switch, ICSW = Insulated-Case Switch, TM = Thermal-Magnetic Trip Unit, ET = Electronic Trip Unit.
Configuration Overview
There are thousands of ways to custom configure an Automatic Transfer Switch. Here's an overview.
STANDARD ATS
Has a single mechanism that transfers the load from one power source to another power source.
Models | Mechanisms | Transitions | Controllers | Voltages | Poles/Wires | Enclosures | Amps | Connections |
---|---|---|---|---|---|---|---|---|
K | S | S | A, B | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V | A, B, C, D, F, G | 30, 70, 104, 150 | S |
K | S | S | A, B | C, D, F, G, H, J, K, M, P, R, S | N, T, V | A, B, C, D, F, G | 200, 230 | S |
K | S | S | A, B | N | N, T, V, W | A, B, C, D, F, G | 230 | S |
K | S | S | A, B | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V, W | A, B, C, D, F, G | 260, 400, 600, 800 | S |
K | S | S | A, B | C, D, F, G, H, J, K, M, N, P, R, S | T, V, W | A, B, C, D, F, G | 1000, 1200 | S |
K | C | S | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V | A, B, C, D, F, G | 30, 70, 104,150 | S |
K | C | S | A, B, D, F | C, D, F, G, H, J, K, M, P, R, S | N, T, V | A, B, C, D, F, G | 200, 230 | S |
K | C | S | A, B, D, F | N | N, T, V, W | A, B, C, D, F, G | 230 | S |
K | C | S | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V, W | A, B, C, D, F, G | 260, 400, 600, 800 | S |
K | C | S | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V, W | A, B, C, D, F, G | 1000, 1200 | S |
K | C | S | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V, W | A, C, G | 1600, 2000 | F |
K | C | S | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V, W | A, C, G | 1600, 2000, 2600, 3000 | S |
K | C | S | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V, W | A, C | 4000 | S |
K | C | P | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V | A, B, C, D, F, G | 150, 225, 260, 400, 600, 800 | S |
K | C | P | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, B, C, D, F, G | 1000, 1200 | S |
K | C | P | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, C, G | 1600, 2000 | F |
K | C | P | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, C, G | 1600, 2000, 2600, 3000 | S |
K | C | P | A, B, D, F | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, C | 4000 | S |
K | C | C | A, D | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V | A, B, C, D, F | 150, 260, 400, 600, 800 | S |
K | C | C | A, D | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, B, C, D, F | 1000, 1200 | S |
K | C | C | A, D | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, C | 1600, 2000 | F |
K | C | C | A, D | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, C | 1600, 2000, 2600, 3000, 4000 | S |
BYPASS-ISOLATION ATS
Bundles an automatic and a manual transfer switch into a single unit.
Models | Mechanisms | Transitions | Controllers | Voltages | Poles/Wires | Enclosures | Amps | Connections |
---|---|---|---|---|---|---|---|---|
K | B | S | D | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V, W | A, C | 150, 225, 260, 400, 600 | S |
K | B | S | D | C, D, F, G, H, J, K, M, N, P, R, S | T, V, W | A, C | 800, 1000, 1200 | F |
K | B | S | D | C, D, F, G, H, J, K, M, N, P, R, S | T, V, W | A, C | 800, 1000, 1200, 1600, 2000, 2600, 3000, 4000 | S |
K | B | P, C | D | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V, | A, C | 150, 225, 260, 400, 600 | S |
K | B | P, C | D | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, C | 800, 1000, 1200 | F |
K | B | P, C | D | C, D, F, G, H, J, K, M, N, P, R, S | T, V | A, C | 800, 1000, 1200, 1600, 2000, 2600, 3000, 4000 | S |
K | A | S | D | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V, W | A, C | 150,225,260,400,600 | S |
K | A | P | D | C, D, F, G, H, J, K, M, N, P, R, S | N, T, V, | A, C | 150,225,260,400,600 | S |
SERVICE ENTRANCE ATS
Serves as both ATS and utility disconnect; circuit breakers and motor operators are used as the switch mechanism.
Models | Mechanisms | Transitions | Controllers | Voltages | Poles/Wires | Enclosures | Amps | Connections | Utility Disconnects | Generator Disconnects |
---|---|---|---|---|---|---|---|---|---|---|
K | E | P | D | C, F, K, M, R | N, T, V | A, B, C, D, F | 100, 150 | S | M | K, M |
K | E | P | D | C, F, R | N, T | A, B, C, D, F | 200 | S | M | K, M |
K | E | P | D | C, F, K, M, R | N, T, V | A, B, C, D, F | 250, 400, 600, 800 | S | N | K, N |
K | E | P | D | C, F, K, M, R | T, V | A, B, C, D, F | 1000, 1200 | S | P | K, N |
K | E | P | D | C, F, K, M, R | T, V | A, C | 800 | S | R | Q, R |
K | E | P | D | C, F, K, M, R | T, V | A, C | 1000, 1200, 1600, 2000, 2500, 3000, 4000 | S | T | Q, R |
DECISION-MAKER MPAC CONTROLLERS
Two options. Two solutions.
The document shows images of the MPAC1200 and MPAC1500 controller displays, featuring similar interfaces with voltage readings and status indicators.
MPAC1200
A customizable solution for your specific application. The ATS1200 gives you full control of system behavior including extended I/O to customize your needs.
MPAC1500
When you need to manage your loads, use your system as a prime power application or have a backup for your backup (i.e., a three-source system); this controller gets the job done.
Feature | MPAC1200 | MPAC1500 |
---|---|---|
Voltage and Frequency Settings | ||
Pickup / Dropout normal source voltage | Programmable | Programmable |
Pickup / Dropout emergency source voltage | Programmable | Programmable |
Frequency selection | 50/60 Hz | 50/60 Hz |
Pickup / Dropout normal source frequency | Programmable | Programmable |
Pickup / Dropout emergency source frequency | Programmable | Programmable |
Overvoltage trip | Programmable | Programmable |
Overfrequency trip | Programmable | Programmable |
Normal and emergency voltage unbalance | Standard | Standard |
Inphase monitor | Standard | Standard |
Transfer commit | Standard | Standard |
Phase rotation sensing | Standard | Standard |
Time Delays and Configuration Settings | ||
Transfer to emergency / Transfer to normal | Programmable | Programmable |
Engine cooldown | Programmable | Programmable |
Generator exerciser | 21 exercise events | 21 exercise events |
Remote peak shave | Standard | Standard |
Start-time delay | Programmable (emergency only) | Programmable |
Fail to acquire | Programmable (emergency only) | Programmable |
Communications | ||
RS-485 | Standard | Standard |
Ethernet | Optional | Standard |
Accessories | ||
Programmable engine exerciser | Standard | Standard |
Extended I/O | Optional (Up to 4 modules) | Optional (Up to 4 modules) |
Digital meter | Optional | Optional |
Source priority selector | Optional | Optional |
Extended engine start-time delay | Optional | Optional |
Controller disconnect switch | Optional | Optional |
Load shed | Optional | Optional |
Load control | Time-based | Time- or current-based |
Three-source system | Standard | Standard |
Prime power | Standard | Standard |