KOHLER

Model KSS Automatic Transfer Switches

Standard Specific-Breaker Rated

Transfer Switch Standard Features

Available Controllers

Select one of the following controllers for your automatic transfer switch.

Decision-Maker® MPAC 750 Controller

Features:

For more information about Decision-Maker® MPAC 750 features and functions, see specification sheet G11-126.

Decision-Maker® MPAC 1200 Controller

Features:

For more information about Decision-Maker® MPAC 1200 features and functions, see specification sheet G11-127.

Ratings

Model Current Voltage, Frequency
KSS 40-600 amps 208-600 VAC, 50/60 Hz
KSS 800-1000 amps 208-480 VAC, 50/60 Hz

Codes and Standards

The ATS meets or exceeds the requirements of the following specifications:

Application Data

Environmental Specifications

UL-Listed Solderless Screw-Type Terminals for External Power Connections

Range of Wire Sizes, Copper or Aluminum*

Model Switch Rating, Amps Normal, Emergency, and Load Neutral Ground
KSS 40-150 (1) #8 to 3/0 AWG (3) #6 - 3/0 AWG (3) #6 - 3/0 AWG
200-225 (1) #6 AWG to 250 KCMIL (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL (3) #4 - 600 KCMIL or (6) 1/0 - 250 KCMIL
260 (1) #6 AWG to 350 KCMIL
400 (1) #4 AWG to 600 KCMIL or (2) #6 AWG to 250 KCMIL (6) #2 - 600 KCMIL (6) #2 - 600 KCMIL
600 (2) #2 AWG to 600 KCMIL (12) #2 - 600 KCMIL (12) #2 - 600 KCMIL
800 (2) #1/0 AWG to 750 KCMIL N/A N/A
1000 (4) #2 AWG to 600 KCMIL N/A N/A

* Use 60°C minimum wire for #14 to #1 AWG. Use 75°C minimum wire for 1/0 AWG and larger.

Contact Ratings

Resistive Load Inductive Load Motor Load
NC NO
Engine Start Contacts 2 A @ 30 VDC N/A N/A N/A
Auxiliary Contacts, (40-600A) ‡ 15 A @ 250 VAC N/A N/A N/A
Auxiliary Contacts, (800-1000A) ‡ 15 A @ 480 VAC 15 A @ 250 VAC;
6 A @ 500 VAC
5 A @ 125 VAC;
3 A @ 250 VAC;
1.5 A @ 500 VAC
2.5 A @ 125 VAC;
1.5 A @ 250 VAC;
0.75 A @ 500 VAC

‡ Auxiliary position-indicating contacts, one set Normal and one set Emergency.

Weights and Dimensions

Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for different configurations. See your local distributor for dimension drawings.

Weights and dimensions are shown for transfer switches in NEMA type 1 and type 3R enclosures. Consult the factory for open units and other enclosures.

Amps NEMA Type Dimensions mm (in.) Weight kg (lb.) ADV Drawing
Height Width Depth § 2-Pole 3-Pole 4-Pole
40-225 1, 3R 791 (31.1) 450 (17.7) 316 (12.5) 28 (62) 30 (65) 31 (68) ADV-8584
260 1, 3R 1219 (48.0) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131) ADV-8586
400 1, 3R 1223 (48.1) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131) ADV-8588
600 1, 3R 1702 (67.0) 610 (24.0) 514 (20.2) 179 (395) 183 (403) 186 (410) ADV-8590
800 1, 3R 1932 (76.1) 864 (34.0) 515 (20.3) N/A 226 (498) 236 (520) ADV-8592
1000 1, 3R 1932 (76.1) 864 (34.0) 515 (20.3) N/A 231 (509) 241 (531) ADV-8592

§ Allow enough room to fully open the door for inspection and service per NEC and local codes. The NEMA type 3R enclosures have a security cover on the controller that extends 54 mm (2.1 in.) beyond the door.

Withstand and Close-On Ratings (WCR)

Ratings Summary

The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical Amperes listed at the specified maximum voltage below, but no greater than the interrupting capacity of the selected circuit breaker or fuse. Circuit breakers and fuses are supplied by the customer.

Certified Withstand Current Ratings in RMS Symmetrical Amperes

Switch Rating, Amps With Current-Limiting Fuses Specific Coordinated Breaker Rating, (see the following tables) Any Breaker Ratings ** Time Duration, Seconds Max.
Fuse Class Fuse Size, Max Amps Maximum Circuit Amps Maximum Voltage Maximum Circuit Amps Maximum Voltage Maximum Circuit Amps Maximum Voltage
480 VAC 600 VAC 480 VAC 600 VAC 480 VAC 600 VAC
40-150 J 400 200,000 200,000 600 V 30,000 22,000 600 V 10,000 10,000 0.025
200-225 J 400 200,000 N/A 600 V 30,000 22,000 600 V 10,000 10,000 N/A
260 N/A N/A N/A N/A 480 V 35,000 N/A N/A N/A N/A N/A
400 J 600 200,000 200,000 600 V 50,000 42,000 600 V 35,000 35,000 0.050
RK5 600 100,000 N/A
600 RK1 600 N/A N/A 600 V 50,000 42,000 N/A N/A N/A N/A
800 L 3000 200,000 N/A 480 V 65,000 N/A N/A N/A N/A N/A
1000 L 4000

* All values are available symmetrical RMS Amperes and tested in accordance with the withstand/closing requirements of UL 1008.

** Applicable to breakers with instantaneous trip elements.

Ratings with Specific Manufacturers' Circuit Breakers

Molded-Case Circuit Breakers

Switch Rating, Amps Voltage, Max. WCR, Amps RMS Manufacturer Type Max. Size, Amps
40-225 480 30,000 Eaton FCL 100
JGS, JGH, JGC, JGU, JGX, JBD, JD, HJD, JDC, LCL, LCLA 250
LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD 400
ITE/Siemens CED6, HED4, HED6 125
CFD6, FD6A, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 250
CJD6 400
General Electric SEL, SEP, THLC1 150
THLC2 225
SFH, SFL, SFP 250
SGH, SGL, SGP, FGN, FGH, FGL, FGP 400
Schneider HG, HJ, HL, HR 150
JJ, JL, JR 250
LG, LJ, LL, LR 400
600 22,000 Eaton JGS, JGH, JGC, JGU, JGX, JDB, JD, HJD, JDC, LCL, LCLA 250
800 480 50,000 LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD 400
ITE/Siemens CED6, HED4, HED6 125
CFD6, FD6, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 250
General Electric SEL, SEP, THLC1 150
THLC2 225
SFH, SFL, SFP 250
SGH, SGL, SGP, FGN, FGH, FGL, FGP 400
Schneider HG, HJ, HL, HR 150
JJ, JL, JR 250
LG, LJ, LL, LR 400
260 480 35,000 Eaton HJD, JDC, JGC, JGH, JGU, JGX 250
CHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD, CHMDL4, CMDL4 400
CHLD6, HDL6, CHMDL6, CMDL6, CLDC, CLD6, LDC6, CLDC6 600
CHMDL8, HMDL8, MDL8, CMDL8 800
ITE/Siemens CFD6, HFD6, HFXD6, HHFD6, HHFXD6 250
General Electric SFL, SFP 250
FGL, FGP 600
Schneider LJ, LL, LR 600
400 480 50,000 Eaton JGU, JGX 250
CLDC4, KDC, LDC4 400
CLDC6, LDC6, NB Tri-Pac 600
NB Tri-Pac 800
ITE/Siemens CFD6 250
CJD6, SCLD6 400
CLD6, HHLD6, HHLXD6, SCLD6 600
CMD6, HMD6, HMXD6, SCMD6, SHMD6 800
600 600 42,000 General Electric THLC1 150
FGL4, FGP4, THLC4, TLB4 400
SGL, SGP, FGL6, FGP6 600
SKL8, SKP8 800
Schneider JL, JR 250
Eaton JGS, JGH, JGC, JGU, JGX, JBD, JD, HJD, JDC, LCL, LCLA 250
LDC, CLDC, KDB, KD, HKD, KDC, LD, CLD, HLD, CHLD 400
CED6, HED4, HED6 125
ITE/Siemens CFD6, FD6A, FXD6, HFD6, HFXD6, HHFD6, HHFXD6 250
General Electric SEL, SEP, THLC1 150
THLC2 225
SFH, SFL, SFP 250
SGH, SGL, SGP, FGN, FGH, FGL, FGP 400
Schneider HG, HJ, HL, HR 150
JJ, JL, JR 250
LG, LJ, LL, LR 400
Eaton HJD, JDC, JGC, JGH, JGU, JGX 250
CHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD, CHMDL4, CMDL4 400
CHLD6, HDL6, CHMDL6, CMDL6, CLDC, CLD6, LDC6, CLDC6 600
CHMDL8, HMDL8, MDL8, CMDL8 800
ITE/Siemens CFD6, HFD6, HFXD6, HHFD6, HHFXD6 250
General Electric SFL, SFP 250
FGL, FGP 600
Schneider LJ, LL, LR 600
Eaton JGU, JGX 250
CLDC4, KDC, LDC4 400
CLDC6, LDC6, NB Tri-Pac 600
NB Tri-Pac 800
ITE/Siemens CFD6 250
CJD6, SCLD6 400
CLD6, HHLD6, HHLXD6, SCLD6 600
CMD6, HMD6, HMXD6, SCMD6, SHMD6 800
General Electric THLC1 150
FGL4, FGP4, THLC4, TLB4 400
SGL, SGP, FGL6, FGP6 600
SKL8, SKP8 800
Schneider JL, JR 250
Eaton/ Cutler-Hammer TRI-PAC NB, CHMDL, HMDL, CHND, HND, NDC, CNDC 800
TRI-PAC NB, CNDC, NDC, CRDC, TRI-PAC PB, RDC, CHND, HND, RD. CRD 1200
Schneider/ Square D MJ, PJ, PL, RJ 800
PJ, PL, RL 1000
ITE/Siemens CMD6, HMD6, SCMD6, SHMD6, CND6, HND6, SCND6, SHND6, CPD6 800
General Electric CND6, HND6, SCND6, CPD6, SHND6, HPD6 1200
TB8, TC, THC, THP 1000
THC, THP, TRP 1200

Transfer Switch Accessories

Accessories are available either factory-installed or as loose kits, unless otherwise noted.

Seismic Certification

Certification depends on application and geographic location. Contact your distributor for details. Available for 40-1000 amp KSS models with NEMA 1, 3R, 4, 4X, and 12 enclosures.

Surge Protection Device (SPD)

Surge protection reduces transient voltages to harmless levels. Protection modes: L-L / L-N / L-G / N-G. Replaceable phase and neutral cartridges for service. Frequency: 50-60 Hz. Operating Temperature Range: -40 to 176°F (-40 to 80°C). Remote contacts for customer-supplied status indicators: Contacts: 1 NO, 1 NC; Min Load: 12VDC / 10 mA; Max. Load: 250 VAC / 1 A; Wire Size (max.): 16AWG. Fuse protection: 30 amps / 600 V. UL 1449, 3rd Edition for Type 2 applications; IEC 61-643-1, 2nd Edition T2/11.

SPD Specifications

Nominal Voltage (V ±15%) Max. Discharge Current (kA) Phase Poles UL VPR 3rd Ed (L-N/N-G/L-G) (kV) Limiting Voltage, (L-N/N-G/L-G) (kV) Short Circuit Withstand Current (kA) Maximum Continuous Operating Voltage (VAC)
at 3kA at 10kA
240/120 40 Split 3 0.6/1.2/0.7 0.6/0.4/0.6 0.8/0.7/0.8 200 175/350
208/120 40 Wye 4 0.6/1.2/0.7 0.6/0.4/0.6 0.8/0.7/0.8 200 175/350
480/277 40 Wye 4 1.0/1.2/1.1 1.0/0.4/1.0 1.2/0.7/1.2 200 320/460
240/120 40 HLD 4 1.0/1.2/1.1 1.0/0.4/1.0 1.2/0.7/1.2 200 320/460
600/347 40 Wye 4 1.3/1.2/1.4 1.3/0.4/1.3 1.5/0.7/1.5 200 440/880

Additional Controller Accessories

See the controller spec sheet for more information.

Model Designation

The transfer switch model designation defines characteristics and ratings as explained below. Record the transfer switch model designation in the boxes provided.

Sample Model Designation: KSS-JCNA-0100S

Model Components Breakdown:

Note: Some selections are not available for every model. Contact your Kohler distributor for availability.

PDF preview unavailable. Download the PDF instead.

kohler-0cef5767dedf59be2e87838af8c59c13 Acrobat Distiller 10.1.7 (Windows)

Related Documents

Preview Kohler KSS Automatic Transfer Switches: Features, Ratings, Specifications, and Accessories
Comprehensive guide to Kohler KSS Automatic Transfer Switches, detailing standard features, available controllers (MPAC 750, MPAC 1200), electrical ratings, UL/CSA certifications, application data, withstand/close-on ratings, circuit breaker compatibility, and accessories.
Preview Kohler KSS Automatic Transfer Switch: Features, Ratings, and Specifications
Detailed specifications, features, ratings, and accessories for the Kohler KSS series Automatic Transfer Switches. Includes information on controllers, codes, standards, application data, withstand/close-on ratings, and model designation.
Preview Kohler KSSB Series Automatic Transfer Switches: Features, Specifications, and Ratings
Detailed datasheet for the Kohler KSSB Series Automatic Transfer Switches, covering features, electrical specifications, controller options, compliance standards, and model designation for industrial and commercial standby power applications.
Preview Kohler Automatic Transfer Switch Product Guide: Configuration and Features
Explore the Kohler Automatic Transfer Switch (ATS) product line, including detailed configuration options, Decision-Maker MPAC controller features, and available models. This guide helps select the right ATS for your power needs.
Preview Kohler KSS Automatic Transfer Switch: Features, Ratings, and Specifications
Explore the features, technical specifications, ratings, and model designations for Kohler KSS Automatic Transfer Switches, designed for reliable backup power solutions.
Preview Kohler Automatic Transfer Switches for Industrial Power Systems | Product Overview
Explore Kohler's comprehensive range of Automatic Transfer Switches (ATS) designed for industrial power systems. This document details system integration, various ATS types, enclosure ratings, transition modes, controller options (MPAC 1200, MPAC 1500), pole and neutral switching, withstand and close-on ratings, load management features, accessories, and global service and support.
Preview Kohler Automatic Transfer Switches (ATS) Product Guide & Configuration
Explore the Kohler Automatic Transfer Switch (ATS) product line, including standard, bypass-isolation, and service-entrance models. Learn about Decision-Maker MPAC controllers and custom configuration options for reliable power transfer.
Preview Kohler RXT Automatic Transfer Switch: Features, Specifications, and Ratings
Comprehensive details on the Kohler RXT Automatic Transfer Switch (100-400 Amps), including features, technical specifications, environmental and interface module data, cable sizing, withstand and close-on ratings, dimensions, weights, and model designation.