Kohler RDT Automatic Transfer Switch (100-400 Amps)
This document provides detailed specifications, features, and model information for the Kohler RDT Series Automatic Transfer Switches.
Product Overview
The Kohler RDT Automatic Transfer Switch is designed for reliable power transfer between a primary (utility) power source and a secondary (generator) power source. It ensures continuous power supply for essential loads during outages. The series covers current ratings from 100 to 400 Amps.
A visual representation of the Kohler RDT Automatic Transfer Switch unit shows its robust construction, typically featuring a grey metal enclosure with a control panel displaying indicators and operational buttons.
MPAC® 500 Controller Features
- User-friendly interface with easy-to-read international symbols.
- Source available and contactor position indicators.
- LED indication of system faults:
- Failure to acquire standby source.
- Failure to transfer.
- Auxiliary switch fault.
- Common fault contact: latches closed on system faults shown above.
- Engine start contact: provides contact closure to start the generator set.
- Load control contact: allows 5-minute delay in startup of selected loads.
- Test button (with or without load).
- Exercise set button.
- Weekly 20-minute generator set exercise (with or without load).
- Single-phase voltage sensing on both sources, ±5%.
- Line-to-line frequency sensing, ±2%.
- Fixed time delays.
Standard Features
- UL listed.
- UL 1008 listed, file #E58962.
- Models with load centers use UL 67 listed components.
- cUL listed.
- 100 and 200 amp models with load centers available.
- CSA certification available, file #LR58301 (not applicable to service entrance or load center models).
- 220/240 VAC, 50/60 Hz (selectable).
- 100, 200, and 400 amp models available.
- Two-pole, single-phase open-transition transfer switch.
- Contactor electrically and mechanically interlocked.
- Double throw inherently interlocked design.
- Solid neutral.
- Contactor manually operable for maintenance purposes.
- Silver alloy main contacts.
- Automatic transfer switches are 100% equipment rated and can be applied at the rated current without derating (except service entrance models).
- 100 and 200 amp models available with or without prewired Square D type QO load center.
- 100 amp load center models use up to 16 circuit breakers (up to 8 tandem breakers for a maximum of 24 circuits).
- 200 amp load center models use up to 24 circuit breakers.
- 200 amp service entrance model with 42-circuit breaker load center is available.
- Two enclosure types available:
- NEMA Type 1 steel ANSI 49 gray enclosure for indoor installation. (100 and 200 amp models without load centers can be recess-mounted between wall studs, not service entrance models).
- NEMA Type 3R corrosion-resistant aluminum ANSI 49 gray padlockable enclosure, approved for indoor or outdoor installation.
- Five-year limited warranty.
- Refer to page 5 for available accessories.
Service Entrance Model Features
- 200 and 400 amp service entrance rated automatic transfer switches available.
- Service disconnect circuit breaker on the normal (utility) source (80% rated).
- NEMA 3R aluminum ANSI 49 gray enclosure.
- Circuit breaker for generator set battery charger.
- Refer to page 5 for available SE model accessories.
Specifications
Environmental Specifications
Parameter | Value |
---|---|
Operating temperature | -20°C to 70°C (-4°F to 158°F) |
Storage temperature | -40°C to 85°C (-40°F to 185°F) |
Humidity | 5 to 95% noncondensing |
Contact Ratings
Contact Type | Rating | Type |
---|---|---|
Engine start | 1 A @ 30 VDC | SPST normally closed (NC) |
Common fault | 0.5 A @ 125 VAC; 2 A @ 30 VDC | SPST normally open (NO) |
Load control | 10 A @ 120 VAC | SPST normally open (NO) |
Auxiliary contacts (optional) | 10 A @ 250 VAC | Form C |
Source Sensing
- Undervoltage dropout: 80%
- Undervoltage pickup: 85%
- Underfrequency dropout: 90%
- Underfrequency pickup: 96%
Time Delays
Time Delay | Factory Setting | Adjustment with Accessory Board* | |
---|---|---|---|
Range | Increment | ||
Engine start | 3 seconds | 1-10 seconds | 1 second |
Transfer from Normal to Emergency | 3 seconds | 1-10 seconds | 1 second |
Retransfer from Emergency to Normal | 6 minutes | 3-30 minutes | 3 minutes |
Engine cooldown | 5 minutes | 1-10 minutes | 1 minute |
Exercise run time | 20 minutes | 5-50 minutes | 5 minutes |
Exercise interval | 1 week | 1 week/2 week (DIP switch) | - |
Load control connection delay | 5 minutes | 5 or 10 minutes (DIP switch) | - |
Failure to acquire Emergency source | 78 seconds | NA | - |
Undervoltage dropout | 0.5 second | NA | - |
Underfrequency dropout | 3 seconds | NA | - |
* Optional accessory board required for time delay adjustments. NA = not adjustable.
Cable Sizes (AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections)
Switch Size, Amps | Range of Wire Sizes, Cu/Al | Neutral | Ground | ||
---|---|---|---|---|---|
Normal (per phase) | Emergency (per phase) | Load (per phase) | |||
100 | (1) #14 - 1/0 AWG | (1) #14 - 1/0 AWG | per customer-supplied branch circuit breakers | (5) #12 - 250 KCMIL(Cu) or (5) #10 - 250 KCMIL(AI) | (9) #14 - #6 AWG |
100 B | (1) #14 - 1/0 AWG | (1) #14 - 1/0 AWG | per customer-supplied branch circuit breakers | (26) #14 - #4AWG or (2) #14 - 1/0 AWG or (1) #6 - 2/0 AWG | (4) #14 - 1/0 AWG |
200 | (1) #6 AWG - 250 KCMIL | (1) #6 AWG - 250 KCMIL | per customer-supplied branch circuit breakers | (5) #12 - 250 KCMIL(Cu) or (5) #10 - 250 KCMIL(AI) | (9) #14 - #6 AWG |
200 B | (1) #6 AWG - 250 KCMIL | (1) #6 AWG - 250 KCMIL | per customer-supplied branch circuit breakers | (38) #14 - #4 AWG or (3) #14 - 1/0 AWG or (1) #4 AWG - 250 KCMIL | (4) #14 - 1/0 AWG |
200 BSE | (1) #4 - 300 KCMIL | (1) #6 - 250 KCMIL | per customer-supplied branch circuit breakers | (4) #12 - 250 KCMIL(Cu) or (4) #10 - 250 KCMIL(AI) | (6) #6 - 3/0 AWG |
200 SE | (1) #4 - 300 KCMIL | (1) #6 - 250 KCMIL | (1) #6 AWG - 250 KCMIL | (5) #12 - 250 KCMIL(Cu) or (5) #10 - 250 KCMIL(AI) | (6) #6 - 3/0 AWG |
400 | (2) 1/0 - 250 KCMIL or (1) 4 AWG - 600 KCMIL | (2) 1/0 - 250 KCMIL or (1) 4 AWG - 600 KCMIL | (3) #4 - 600 KCMIL (6) 1/0 - 250 KCMIL | (6) #4 - 600 KCMIL (12) 1/0 - 250 KCMIL | (6) #6 - 3/0 AWG |
400 SE | (1) #1 - 600 KCMIL or (2) #1 - 250 KCMIL | (2) 1/0 - 250 KCMIL or (1) 4 AWG - 600 KCMIL | (6) #4 - 600 KCMIL (12) 1/0 - 250 KCMIL | (6) #4 - 600 KCMIL (12) 1/0 - 250 KCMIL | (6) #6 - 3/0 AWG |
Note: B = Load center model, SE = Service entrance model. Data is subject to change. Refer to the transfer switch dimension drawings and wiring diagrams for planning and installation.
Withstand and Close-On Ratings (WCR)
Service Entrance Transfer Switch Ratings
The service entrance transfer switch is factory-equipped with a normal source disconnect circuit breaker.
Switch Rating, Amps | WCR, RMS Symmetrical Amps at 240 VAC |
---|---|
200 | 22,000 |
400 | 35,000 |
Contactor Ratings with Coordinated Circuit Breakers
The transfer switches are UL listed at 240 VAC maximum. The following table lists contactor withstand current ratings (WCR) for 100-400 ampere non-service entrance rated switches with specific manufacturer's circuit breakers per UL and Canadian safety standards. Suitable for control of motors, electric discharge lamps, tungsten filament lamps and electric heating equipment where the sum of motor full-load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of switch rating.
Switch Rating, Amps | Voltage, max. | WCR, RMS Symmetrical Amps | Manufacturer | Type or Class | Maximum Size, Amps |
---|---|---|---|---|---|
100 / 200 | 240 | 10,000 | Any Breaker * | Any Breaker (0.025 seconds max.) | — |
65,000 | GE | THLC4 | 350 | ||
Eaton/Cutler-Hammer | HMC | 800 | |||
400 | 240 | 42,000 | GE | THKM3F | 1200 |
35,000 | Any Breaker | Any Breaker (0.05 seconds max.) | — |
* For higher WCR values, contact the factory for additional specific breaker ratings.
Codes and Standards
The ATS meets or exceeds the requirements of the following specifications:
- Underwriters Laboratories UL 1008, Standard for Automatic Transfer Switches for Use in Emergency Systems, file #E58962.
- Underwriters Laboratories UL 508, Standard for Industrial Control Equipment.
- CSA certified, file #LR58301 (not applicable to service entrance models).
- NFPA 70, National Electrical Code.
- NFPA 110, Emergency and Standby Power Systems.
- IEEE Standard 446, IEEE Recommended Practice for Emergency and Standby Power Systems for Commercial and Industrial Applications.
- NEMA Standard IC10-1993 (formerly ICS2-447), AC Automatic Transfer Switches.
- ANSI C37.90.1 (IEEE472), 2000, EFT/Surge Relay Systems.
- EN61000-4-5 Surge Immunity Class 4 (voltage sensing and programmable inputs only).
- EN61000-4-4 Fast Transient Immunity Severity Level 4.
- IEC Specifications for EMI/EMC Immunity:
- CISPR 11, Radiated and Conducted Emissions, Class B.
- IEC 61000-4-2, 2001, Electrostatic Discharge.
- IEC 61000-4-3, 2002, Radiated Immunity.
- IEC 61000-4-4, 2001, Electrical Fast Transients (Bursts).
- IEC 61000-4-5, 2001, Surge Voltage Immunity.
- IEC 61000-4-6, 2003, Conducted RF Immunity.
- IEC 61000-4-8, Magnetic Field Immunity.
- IEC 61000-4-11, Voltage Dips and Interruptions.
Weights and Dimensions
Note: Always use the transfer switch dimension drawing for planning and installation. Weights and dimensions may vary for different configurations. See the Operation/Installation Manual or your local distributor for dimension drawings.
Transfer switch weights and dimensions shown in the table do not include packaging. To estimate the shipping weight, add 3 kg (5 lbs.) or 10% (whichever is larger) to the weight shown.
Amps | Load Center | Enclosure Type | Weight kg (lb.) | Transfer Switch Dimensions H x W x D, mm (in.) | Dimension Drawing |
---|---|---|---|---|---|
100 | None | NEMA 1 (steel) | 7 (15) | 610 x 330 x 154 * (24.0 x 13.0 x 6.0) * | ADV-8437 |
100 B | 16 circuits | 18 (40) | 914 x 406 x 154 (36.0 x 16.0 x 6.0) | ADV-9181 | |
200 | None | 7 (15) | 610 x 330 x 154 * (24.0 x 13.0 x 6.0) * | ADV-8438 | |
200 B | 24 circuits | NEMA 3R (aluminum) | 21 (45) | 914 x 406 x 154 (36.0 x 16.0 x 6.0) | ADV-9182 |
100 | None | 7 (15) | 613 x 340 x 177 (24.1 x 13.4 x 7.0) | ADV-8440 | |
100 B | 16 circuits | 8 (18) | 917 x 416 x 177 (36.1 x 16.4 x 7.0) | ADV-9183 | |
200 | None | 7 (15) | 613 x 340 x 177 (24.1 x 13.4 x 7.0) | ADV-8441 | |
200 B | 24 circuits | NEMA 3R (aluminum) | 8 (18) | 917 x 416 x 177 (36.1 x 16.4 x 7.0) | ADV-9184 |
200 SE | None | 12 (26) | 858 x 473 x 163 (33.8 x 18.6 x 6.4) | ADV-8444 | |
200 BSE | 42 circuits | NEMA 3R (aluminum) | 32 (70) | 967 x 762 x 165 (38.1 x 30.0 x 6.5) | ADV-9185 |
400 | None | NEMA 3R (aluminum) | 40 (89) | 1222 x 560 x 269 (48.1 x 22.0 x 10.6) | ADV-9769 |
400 SE | None | NEMA 3R (aluminum) | 59 (130) | 1448 x 628 x 329 (57.0 x 24.7 x 12.9) | ADV-9767 |
Note: B = Load center model, SE = Service entrance model. * Can be recess-mounted between 16 in. O.C. wall studs.
Accessories
Auxiliary position-indicating contacts
- One closed on normal position and one closed on emergency position.
- Form C contacts rated 15 A @ 250 VAC.
Accessory board
- Alarm horn indicates system faults.
- Adjustable time delays:
- Engine start.
- Engine cooldown.
- Preferred to standby.
- Standby to preferred.
- Exercise duration.
- Inputs and Outputs:
- Remote start/stop input (loaded).
- Programmable exerciser input.
- Generator set supplying load output: 10 A @ 120 V SPST normally open (NO) contact.
- External alarm module connection.
- Dip switches:
- 1 week/2 week exerciser.
- Load/no load exercise mode (for optional programmable exerciser).
- Momentary/maintained external start/stop input: Selects momentary (1 second) push button or maintained contact closure for remote start/stop signal.
- Load control, 5 minutes/10 minutes: Allows adjustment of the startup delay after transfer to generator set for selected loads (e.g., air conditioners or other large motor starting loads).
- Audible alarm disable.
External alarm module
- Alarm horn.
- Alarm silence/lamp test button.
- Remote start/stop button.
- Generator supplying load indicator.
- Fault indicator.
- Fits into standard outlet box.
- Multiple alarm modules can be connected.
- Accessory board required.
Load shed kit
- Automatically sheds non-critical loads when essential appliances are running.
- Prevents generator overload in compliance with NEC 2008.
- Provides two (2) HVAC relays, rated 10 A @ 125 VAC, to control two independent air conditioner loads.
- Includes four (4) pilot relays rated 120VAC, 125VA (pilot duty), 10 A @ 125 VAC (general purpose) to control customer-provided power relays for non-essential loads.
- Mounts inside the ATS enclosure.
- Uses Kohler's exclusive RBUS communication protocol.
- Requires Kohler® residential generator set with RDC2 or DC2 controller.
- See specification sheet G11-124.
Power relay modules
- 50 amp power relay mounted in a NEMA Type 3R enclosure.
- Use up to four modules with the load shed kit.
- UL/cUL listed.
- Dimensions: 172 x 233 x 92 mm (6.8 x 9.2 x 3.6 in.).
- For more information, see specification sheet G6-143.
Programmable exerciser
- Seven-day programmable timer allows scheduling up to 56 on/off events.
- LCD display indicates day, time, program/run modes, and on/off/skip status.
- Skip next cycle button.
- Lithium backup battery with 5-year expected life.
- Accessory board required.
Wall-mount bezel (for Type 1 enclosures)
- For 100 and 200 amp recess-mounted switches.
- For NEMA type 1 enclosures only (not for NEMA 3R or service entrance switches).
Additional Accessories for Service Entrance Models
Accessory circuit breaker
- For generator set engine heater or other AC accessory.
- Single-pole Square D type QO circuit breaker.
- 15 amp and 20 amp circuit breakers are available.
Enclosure space heater
- 150 Watts.
- Hygrostat (humidity control).
- Built-in temperature limiter for overheat protection.
- 15 A single-pole Square D type QO circuit breaker.
Utility-side surge suppressor
- Surge protection reduces transient voltages to harmless levels.
- Protection modes: L-L / L-N / L-G / N-G.
- Replaceable phase and neutral cartridges for service.
- Frequency: 50-60 Hz.
- Operating Temperature Range: -40 to 176°F (-40 to 80°C).
- Remote contacts for customer-supplied status indicators: Contacts: 1 NO, 1 NC. Min Load: 12VDC / 10 mA. Max. Load: 250 VAC / 1 A. Wire Size (max.): 16AWG.
- Fuse protection: 30 amps / 600 V.
- UL 1449, 3rd Edition for Type 2 applications.
- IEC 61-643-1, 2nd Edition T2/11.
- See additional specifications below.
Surge Suppressor Specifications
Nominal Voltage (V ±15%) | Max. Discharge Current (kA) | Phase Split | Poles | UL VPR 3rd Ed (L-N/N-G/L-G) (kV) | Limiting Voltage, (L-N/N-G/L-G) (kV) | Short Circuit Withstand Current (kA) | Maximum Continuous Operating Voltage (VAC) | |
---|---|---|---|---|---|---|---|---|
at 3kA | at 10kA | |||||||
240 / 120 | 40 | 3 | 0.6 / 1.2 / 0.7 | 0.6 / 0.4 / 0.6 | 0.8 / 0.7 / 0.8 | 200 | 175 / 350 |
Kohler® Model Designation Key
This chart explains the Kohler® transfer switch model designation system. The sample model designation shown is for a Model R service entrance rated automatic transfer switch that uses a standard-transition contactor with MPAC® 500 electrical controls rated at 240 Volts/60 Hz with 2 poles, 3 wires, and solid neutral in a NEMA 3R enclosure with a current rating of 200 amperes and no load center.
Component | Designation | Description |
---|---|---|
Model | R | Model R automatic transfer switch |
Mechanism | D | Specific-breaker rated |
Transition | T | Standard transition |
Electrical Controls | C | MPAC® 500 (Microprocessor ATS Control) |
Voltage/Frequency | F | 240 Volts/60 Hz (A jumper on the controller allows conversion to 50 Hz) |
Number of Poles/Wires | N | 2-pole, 3-wire, solid neutral |
Enclosure | A: NEMA 1 (steel) * C: NEMA 3R (aluminum) | |
Current Rating | 0100: 100 amps 0200: 200 amps 0400: 400 amps | Numbers indicate the current rating of the switch in amperes. |
Load Center | A: Without load center B: With load center (not available on 400 amp models) | |
Service Entrance | SE: Service entrance model (200 and 400 amp models available) Blank: Not rated for service entrance |
SAMPLE MODEL DESIGNATION: RDT-CFNC-0200ASE
* NEMA 1 only: 100 and 200 amp models without load centers can be recess-mounted between wall studs. Optional wall-mount bezel available.
Contact Information and Distribution
KOHLER CO.
Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444
KOHLERPower.com
DISTRIBUTED BY:
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler® generator distributor for availability.
© 2021 Kohler Co. All rights reserved.