Reznor Maxitrol Amplifier Replacement Kit Installation

For Indirect-Fired Duct Furnaces - Units with Electronic Modulation Option AG7, AG8, AG9, or AG9H

Brand: Reznor

Model Series: AG7, AG8, AG9, AG9H

Kit Part Numbers: 262320, 262321

Revision: OPT-AG7,8,9,9H (01-22)

Supersedes: CP-AG7/8/9 Amplifier Kits (01-16) PN262319R3

Introduction

This document provides instructions for installing the Maxitrol Amplifier Replacement Kit for Reznor indirect-fired duct furnaces equipped with electronic modulation options AG7, AG8, AG9, or AG9H. The replacement amplifier functions identically to the original. Note that wire connections may differ when replacing an older amplifier.

Image Description: Figure 1 shows a Maxitrol amplifier module, a rectangular electronic component with branding.

Safety and Preparation

Refer to the installation manual provided with the heater for important safety information.

Ensure all components listed in Table 1 are available before beginning installation.

Table 1: Amplifier Replacement Kit Components

Kit PNReplaces (PN)OptionComponentComponent PN (Quantity)
26232048035, 48036, 260863AG7, AG9, AG9HAmplifier260863 (1)
Blue wire159289 (1)
Wire terminal142860 (9)
26232148037, 48038, 260864AG8Amplifier260864 (1)
Blue wire159289 (1)
Wire terminal142860 (9)

Installation Procedure

  1. Turn OFF gas and electric power.
  2. Open cabinet and mark and disconnect wires from the amplifier being replaced. Remove the amplifier.
  3. Install the replacement amplifier and secure using supplied screws.
  4. Reconnect wires to the replacement amplifier as follows:
    • For units with amplifier PN 260863 or 260864, wire connections do not change. Note: The blue wire and the terminals in the kit are not used.
      1. Reconnect wires as marked.
      2. If installing amplifier PN 260863 on unit with option AG7, remove R55 resistor between T5 and T7.
    • For units with amplifier PN 48035, 48036, 48037, or 48038, refer to instructions in Table 2.
  5. Close cabinet.
  6. Turn ON electric power and gas.
  7. Check for proper operation.

Table 2: Replacement Amplifier Wiring Instructions

OptionFigure ReferenceStep
AG7Figure 2, DETAIL A
  1. Remove R55 resistor between T5 and T7.
  2. Connect wire terminal to each of nine wires and connect wires to replacement amplifier (PN 260863).
  3. Connect one end of new blue wire to T10 and other end to terminal block with blue wire from T9.
AG8Figure 2, DETAIL B
  1. If there are two orange wires connected to T3, cut and splice wires before connecting wire terminals.
  2. Connect wire terminal to each wire and connect to eight terminals on replacement amplifier (PN 260864).
  3. Connect one end of new blue wire to T10 and other end to terminal block with blue wire from T9.
AG9, AG9HFigure 2, DETAIL C
  1. If there are two orange wires connected to T3, cut and splice wires before connecting wire terminals.
  2. Connect wire terminal to each wire and connect to eight terminals on replacement amplifier (PN 260863).
  3. Connect one end of new blue wire to T10 and other end to terminal block with blue wire from T9.

Figure 2: Replacement Amplifier Wiring Diagrams Description

The following describes the wiring connections shown in Figure 2, distinguishing between original and replacement amplifiers for each option.

Detail A: Wiring for Option AG7

Original Amplifier (Models A1010B P/N 48035, A1011B P/N 48036): Depicts terminal connections (T1, T2, T3, T4, T5, T7, T8, T9, T10, T11) with associated wires (BL, BK, BR, W, G, PR, R). Includes a "TEMPERATURE SETTING DIAL" indicator.

Replacement Amplifier (Model A1010U P/N 260863): Shows similar terminal layout. Key instructions:

  • A new blue wire from the kit is used.
  • When replacing models 48035 or 48036, connect this new blue wire to terminal T10.
  • Connect the other end of this new blue wire to the same terminal block where the blue wire from T9 is connected.
  • Important: Remove the R55 resistor located between terminals T5 and T7.

Detail B: Wiring for Option AG8

Original Amplifier (Models A1010F P/N 48037, A1011F P/N 48038): Depicts terminal connections (T1, T2, T3, T4, T9, T10, T11, T14) with associated wires (BL, R, BK, BR, W, PR). Includes a "TEMPERATURE SETTING DIAL" indicator.

Replacement Amplifier (Model AD1010U P/N 260864): Shows similar terminal layout. Key instructions:

  • A new blue wire from the kit is used.
  • When replacing models 48037 or 48038, connect this new blue wire to terminal T10.
  • Connect the other end of this new blue wire to the same terminal block where the blue wire from T9 is connected.
  • Note for specific models: If two orange wires were connected to T3 on the original amplifier, cut and splice these wires before connecting them to the new amplifier. A twist-on wire connector is supplied in the field.

Detail C: Wiring for Option AG9(H)

Original Amplifier (Models A1010B P/N 48035, A1011B P/N 48036): Depicts terminal connections identical to the AG7 original amplifier.

Replacement Amplifier (Model A1010U P/N 260863): Depicts terminal connections identical to the AG7 replacement amplifier. Key instructions:

  • A new blue wire from the kit is used.
  • When replacing models 48035 or 48036, connect this new blue wire to terminal T10.
  • Connect the other end of this new blue wire to the same terminal block where the blue wire from T9 is connected.
  • Note for specific models: If two orange wires were connected to T3 on the original amplifier, cut and splice these wires before connecting them to the new amplifier. A twist-on wire connector is supplied in the field.

Final Steps

  1. Close cabinet.
  2. Turn ON electric power and gas.
  3. Check for proper operation.

Notes and Disclaimer

Keep this manual for future reference.

Specifications and illustrations are subject to change without notice or incurring obligations. The latest version of this manual is available at www.reznorhvac.com.

©2022 Nortek Global HVAC LLC, O'Fallon, MO. All rights reserved.

Models: CP-AG7 Maxitrol Amplifier Replacement Kit, CP-AG7, Maxitrol Amplifier Replacement Kit, Replacement Kit

File Info : application/pdf, 2 Pages, 240.98KB

PDF preview unavailable. Download the PDF instead.

OPT-AG7,8,9,9H (01-22) 262319-A

References

Adobe InDesign 17.0 (Windows) Adobe PDF Library 16.0.3

Related Documents

Preview Reznor Maxitrol Amplifier Replacement Kit Installation Guide for Gas-Fired Duct Furnaces
Installation instructions for the Reznor Maxitrol amplifier replacement kit (P/N 262320, 262321) for various Reznor gas-fired duct furnace models including EEDU, RP, SC, X, HRPD, RPB, RPBL, SCE, and SSCBL with electronic modulation options AG7, AG8, or AG9. Features component lists, wiring diagrams, and safety information.
Preview Reznor Fan Control Replacement Kit (PN 209184) Installation Guide
Instructions for installing the Reznor replacement kit (PN 209184) for discontinued fan controls on Thermocore® 1 heat exchanger duct furnaces and packaged systems. Includes component list and step-by-step installation procedures.
Preview Reznor Vertical Louver Kit Installation Guide for Gas-Fired Unit Heaters (OPT-CD1)
Installation instructions for the Reznor OPT-CD1 Vertical Louver Kit, designed for gas-fired unit heaters (models UBX, UBXC, UBZ, UDX, UDXC, UDZ, UEZ). Includes component list and step-by-step assembly guide.
Preview Reznor Relay Replacement Kit (PN 259521) Installation Guide
Installation instructions for the Reznor Relay Replacement Kit (PN 259521), designed to replace time delay relays (PN 46233, PN 259518) in Reznor power-vented HVAC units. Includes detailed wiring diagrams and safety warnings for models F and B.
Preview Reznor CL31/CL32 Relay Kit Installation Guide for Multiple Heater Control
Comprehensive installation guide for Reznor CL31 and CL32 relay kits, enabling multiple heater control for models APD, F, B, UDAP, UDAS, UDBP, UDBS, UEAS, and VR. Includes component lists, safety precautions, and wiring specifications.
Preview Reznor Stepdown Transformer Kit Installation Guide for Gas-Fired Unit Heaters
Detailed installation instructions for Reznor stepdown transformer kits (CG1, CG2, CG4) for UDAP, UDAS, UDX, UDZ, UDBP, UDBS, UBX, and UBZ gas-fired unit heaters. Includes component lists, wiring guidance, and safety precautions.
Preview Reznor Downturn Nozzle Kit Installation Guide for Unit Heaters
Installation instructions and component lists for Reznor downturn nozzle kits (OPT-CD2,3,4,5) for UBX, UBXC, UBZ, UDX, UDXC, UDZ, UEZ, and UWS unit heaters.
Preview Reznor LDAP Heat Exchanger Gasket Kit Installation Guide
Comprehensive guide for installing the Reznor LDAP heat exchanger gasket kit, including component details, safety warnings, and step-by-step instructions for unit heaters.