SENECA S311AK / S311AK-4-L Installation Manual

S311AK / S311AK-4-L Installation Manual

Analogue Panel Indicator with 4-digit Display

Model: S311AK, S311AK-4-L Version

Language: [English]

Product Overview & Documentation

The SENECA S311AK is an analogue panel indicator featuring a 4-digit display, designed for industrial applications.

Documentation

For manuals in other languages and configuration software, visit: www.seneca.it/products/s311ak-4-l

Manufacturer: SENECA s.r.l.

Address: Via Austria, 26 – 35127 – PADOVA – ITALY

Contact: Tel. +39.049.8705355 - 8705359, Fax +39.049.8706287

Certification: [ISO 9001:2015 Certified]

Module Layout and Dimensions

The S311AK module is designed for panel mounting.

Dimensions:

  • Overall Width: 96 mm
  • Height: 48 mm
  • Depth: 40 mm
  • Front Panel Cutout Width: 92 mm
  • Front Panel Cutout Height: 45 mm
  • Side Dimensions: 22 mm, 15 mm

Weight: 100 g

Enclosure Material: UL94-V0 self-extinguishing PC/ABS, black.

Preliminary Warnings

WARNING: Indicates conditions or actions that put the user's safety at risk.

CAUTION: Indicates conditions or actions that might damage the instrument or connected equipment. The warranty is void in case of improper use, tampering, or failure to follow instructions.

Important Safety Note: The full content of this manual must be read before operation. The module is intended for use by qualified electricians only. Specific documentation is available via the QR-CODE on page 1.

Maintenance: The module must be repaired and damaged parts replaced by the Manufacturer.

Electrostatic Discharge (ESD) Sensitivity: The product is sensitive to ESD. Take appropriate measures during operation.

Waste Disposal: Electrical and electronic waste must be disposed of at authorized collection centres, as indicated by the symbol on the product or packaging (applicable in the EU and other recycling countries).

Technical Specifications

StandardDescription
EN61000-6-4Electromagnetic emissions, industrial environment.
EN61000-6-2Electromagnetic immunity, industrial environment.
EN60950Safety

Insulation: Input to Display, Input to Power Supply: -1500 Vac

ParameterValue
Power SupplyVoltage: 10 ÷ 40 Vdc, 19 ÷ 28 Vac; Max. absorption 0.9 W
Environmental Temperature-10°C ÷ +65°C
Environmental Humidity30% ÷ 90% non-condensing
Storage Temperature-30°C ÷ +85°C
AltitudeUp to 2000 m above sea level
Measurement Solution16 bit, 40000 points max
Accuracy0.05%
Thermal Coefficient0.005 %°K
Linearity Error0.05%
Sensor Power Supply16V (Max 25mA)
Connections (Supply)2-way removable screw terminals, 5.08 mm pitch
Connections (Inputs)3-way removable screw terminals, 5.08 mm pitch

Installation Regulations

The module is designed for panel mounting. For optimal operation and longevity, ensure adequate ventilation. Avoid mounting modules near heat-generating equipment.

Menu Parameter Modification

Parameter modification is done digit by digit. The digit to be modified flashes (appears larger). The following describes the button functions:

  • [Up Arrow Button]: Increases the value of the digit by one unit.
  • [Down Arrow Button]: Decreases the value of the digit by one unit.
  • [OK/MENU Button]: Confirms the value of the digit and moves to the next. If it's the last digit, it confirms the value and subsequent presses return to the parameter selection.

Negative Values: The last digit allows entry of the '-' sign or the value '-1'.

CAUTION: Parameter values entered outside the allowed range are automatically reset to the nearest valid value within the range and then displayed. For example, setting HI-E to 40.0 will result in it being set to the maximum value of 20.00.

Parameter Configuration Example

Objective: Configure the instrument to display a 0 ÷ 10 V voltage input with an activated filter.

  1. Access the menu by pressing [DOWN Button] + [MENU Button] simultaneously for 3 seconds until the 'I.N.P.T' menu appears.
  2. Press the [OK/MENU Button] to access the 'I.N.P.T' sub-menu and set:
    • TYPE = 0 (Voltage input)
    • LO-E = 00.00
    • HI-E = 10.00
  3. Press the [OK/MENU Button] to access the 'S.C.A.L.' sub-menu and set:
    • LO-D = 0
    • HI-D = 1000
    • D.P.-D = 2 (Sets decimal point for 00.00 format)
    • F.I.L.T. = 1 (Activates filter level 1)

Electrical Connections

The module supports both Current Input and Voltage Input, with options for external power supply or power supplied by the instrument.

Power Supply

Connects to 10÷40Vdc or 10÷28Vac. Maximum absorption is 1W.

Current Input (0-20mA)

Connection: Terminals 4 and 5.

Power Source: Can be powered by an external sensor supply or by the instrument.

Voltage Input (-10 to +10V)

Connection: Terminals 4 (Signal+) and 5 (-).

Power Source: Can be powered by an external sensor supply or by the instrument.

Error Types

The display may show specific codes indicating errors or operational states:

  • nnnn: Indicates the displayed value is 3% higher than the 'HI-D' parameter set, or higher than 9999.
  • UUUU: Indicates the displayed value is 3% higher than the 'LO-D' parameter set, or higher than -1999. Also indicates quick transition from 'nnnn' to 'UUUU' due to overcurrent protection (input > 25mA).

Menu Parameters

ParameterFunctionDefault Value
PASS (C.O.N.F)Password enabling for menu access. Setting a value other than 5477 requires a password. Default is 5477 (disabled).5477: Password disabled.
TYPE (I.N.P.T)Input type: 1 = Current, 0 = Voltage.1
LO-E (I.N.P.T)Electrical Scale Start: Start of scale in Volts or mA. Defines input quantity for minimum display value (LO-d). Min settable: 0 (current), -10.00 (voltage). Max settable: 20.00 (current), 10.00 (voltage).4.00 (mA)
HI-E (I.N.P.T)Electrical Full Scale: Full scale in Volts or mA. Defines input quantity for maximum display value (HI-d). Min settable: 0 (current), -10.00 (voltage). Max settable: 20.00 (current), 10.00 (voltage).20.00 (mA)
HI-d (S.C.A.L.)Display Full Scale: Integer values between -1999 and 9999.1000
LO-d (S.C.A.L.)Start of Display Scale: Integer values between -1999 and 9999.0
dP-d (S.C.A.L.)Position of Decimal Point: 0=No decimal point, 1=Decimal point on 1st digit (000.0), 2=Decimal point on 2nd digit (00.00).No decimal point
FILT (S.C.A.L.)Filter Level: 0=No filter, 1-5=Filter activated.0
dFLt (s.y.s.)Default Settings: 1 = Overwrites set parameters with defaults and exits menu.0
COnt (s.y.s.)Contrast: 0-3 = Adjusts display contrast.1
EXIT (E.X.I.T)Menu Exit: Confirm with OK/MENU to save parameters to flash memory.-

Menu Navigation

The programming menu can be accessed by pressing the [DOWN Button] and [MENU Button] simultaneously for a few seconds. The menu structure allows navigation through parameters like PASS, TYPE, LO-E, HI-E, LO-D, HI-D, dP-d, FILT, dFLt, CONT, and EXIT using the UP, DOWN, and OK/MENU buttons. Each parameter can be modified, and changes are confirmed by pressing OK/MENU. The 'EXIT' function saves all settings.

Contact Information

Technical Support: supporto@seneca.it

Product Information: commerciale@seneca.it

This document is the property of SENECA srl. Unauthorized copying or reproduction is prohibited. Data may be modified for technical or sales purposes.

Models: S311AK, S311AK-4-L, S311AK Analogue Panel Indicator With 4 Digit Display, S311AK, Analogue Panel Indicator With 4 Digit Display, Panel Indicator With 4 Digit Display, Digit Display, Display

PDF preview unavailable. Download the PDF instead.

mi00173-7-en Adobe PDF Library 17.0 Adobe InDesign 18.5 (Windows)

Related Documents

Preview SENECA T201DC100 Installation Manual and Technical Specifications
This document provides comprehensive installation instructions, technical specifications, and usage guidelines for the SENECA T201DC100 DC current transducer. It covers electrical connections, module layout, safety precautions, and performance data for industrial applications.
Preview SENECA R203 Installation Manual: Comprehensive Guide
This comprehensive installation manual provides detailed instructions for the SENECA R203 industrial measurement and control device. It covers module layout, technical specifications, electrical connections for various inputs and outputs including Rogowski sensors, Ethernet configuration, and safety warnings. Essential for qualified electricians performing installation and setup.
Preview SENECA Z-10-D-IN Digital Input Module User Manual
Detailed user manual for the SENECA Z-10-D-IN, a 10-channel digital input module with Modbus RTU communication. Covers features, connections, configuration, and Modbus register mapping.
Preview SENECA ZE Series Industrial I/O Modules Installation Manual
Comprehensive installation manual for SENECA ZE-4DI-2AI-2DO, ZE-4DI-2AI-2DO-P, Z-4DI-2AI-2DO, ZE-2AI, and ZE-2AI-P industrial I/O modules. Covers technical specifications, electrical connections, configuration, and safety warnings.
Preview SENECA R-32DIDO / R-32DIDO-P Installation Manual
Installation guide for SENECA R-32DIDO and R-32DIDO-P digital input/output modules, covering preliminary warnings, module layout, technical specifications, electrical connections, and configuration.
Preview SENECA T201DC100 Installation Manual
Installation manual for the SENECA T201DC100 AC/DC current transducer, detailing technical specifications, electrical connections, and usage instructions.
Preview SENECA T201DCH-MU Series User Manual: AC/DC Current Transducers
Comprehensive user manual for SENECA T201DCH-MU series AC/DC True RMS and DC Bipolar Current Transducers. Details device features, configuration via dip switches or Easy Setup software, Modbus RTU protocol, register tables, and testing procedures for industrial automation.
Preview SENECA R203 and R204 Series User Manual
Comprehensive user manual for the SENECA R203 and R204 series smart energy meters. Details features, protocols (Modbus, Profinet IO, Ethernet/IP, OPC-UA), configuration, and technical specifications.